Wet area zones checker

Hanapin ang Section 6 zone, IP at RCD malapit sa tubig.

AS/NZS 3000Data na nire-review pa

Reads AS/NZS 3000:2018. Tables checked 1 Oct 2026.

Mga input

Worked example gamit ang mga default na input.

Sitwasyon
Bath
Bansa
New Zealand
Haba ng fixture
1.6 m
Lapad ng fixture
0.7 m
Taas ng connection o rose
0 m
Komunal na paliguan o shower
Hindi
Kagamitan
Luminaire
Distansya mula sa shower connection
0 m
Sa tubig o sa base (Zone 0)
Hindi
Distansya palabas
0.8 m
Taas mula sa sahig
2.4 m
IP rating
IPX4
Sa 30 mA RCD
Oo
Pag-print
A1 hanggang A3 (kasalukuyan)

Zone

Nasa labas ng bawat zone

Pinakamababang IP rating
Wala
Pinapayagan dito
Outside the zones

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. SitwasyonBathtub

    AS/NZS 3000:2018 Cl 6.2.2.1

  2. Distansyang sinukat mula saang panloob na rim

    AS/NZS 3000:2018 Cl 6.2.2.1

  3. Zone 10 m out, up to 2.25 m (Cl 6.2.2.1(b))

    AS/NZS 3000:2018 Cl 6.2.2.1

  4. Zone 20.6 m out, up to 2.25 m (Cl 6.2.2.1(d))

    AS/NZS 3000:2018 Cl 6.2.2.1

  5. Zone 33 m out, up to 2.25 m (Cl 6.2.2.1(e))

    AS/NZS 3000:2018 Cl 6.2.2.1

  6. Posisyon ng device0.8 m out, 2.4 m up

    AS/NZS 3000:2018 Cl 6.2.2.1

  7. ZoneResultaNasa labas ng bawat zone

    AS/NZS 3000:2018 Cl 6.2.2.1

Tungkol sa calculator na ito

How this is calculated

The tool places a light, switch or socket‑outlet in a zone. It then reads the least IP rating and the RCD rule for that zone. It follows Section 6 of AS/NZS 3000:2018.

  1. Situation. You pick the fitting: a bath, a shower, a basin, a spa, a pool or a sauna. Each one has its own table of zones.
  2. Reference point. Each situation measures from its own point. A bath measures from the internal rim. A shower measures from the fixed plumbing connection or the rose.
  3. Zone limits. The tool lists Zone 1, Zone 2 and Zone 3 (Cl 6.2.2.1). Each has a distance out and a height up.
  4. Device position. You enter the horizontal distance and the height of the device. The tool finds the first zone that holds that point.
  5. IP rating. The zone sets the least IP rating (Cl 6.2.4). The tool compares your rating with it.
  6. RCD and position. The tool adds the RCD rule for a home (Cl 2.6.3.3.1). It also gives the lowest height for a socket‑outlet or switch.
StepTable or clauseWhat it decides
Zone limitsCl 6.2.2.1The distance and height of each zone
IP ratingCl 6.2.4The least IP rating for the zone
Walls and fixed barriersCl 6.2.1Where a zone stops
RCDCl 2.6.3.3.1The 30 mA rule for a home
BondingCl 5.6.2.5The earth bond of conductive reinforcing

Worked example

Each link opens the tool with its inputs.

  • Luminaire at an open shower. The luminaire sits 0.3 m from the plumbing connection and 1.8 m up. It has an IPX2 rating. The tool puts it in Zone 1 and asks for IPX4 at least. The check fails on the IP rating.

Limits

  • The tool does not model a barrier that shrinks a zone. Walls, doors, floors and ceilings also limit the zones. Check the room.
  • A shower over a bath adds a radius from the shower connection. You must type that distance.
  • Equipment behind a fixed IPX4 panel that needs a tool to open is not in a zone. The tool does not decide this for you.
  • A recessed fitting with all live parts above the ceiling is outside the zones below it.
  • Protection by obstacles or by placing out of reach is not allowed in these zones.
  • The tool points at the clause. It is not a ruling on a design.

See also: Wire a bathroom: zones, IP and the RCD, Damp situations and the Section 6 zones and RCD selection.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Gaano kataas ang Zone 1 sa NZ at sa Australia?

Ang Zone 1 sa ibabaw ng bath o shower ay umaabot ng 2.25 m mula sa sahig sa New Zealand at 2.5 m sa Australia. Tumataas ito hanggang sa shower connection kapag mas mataas iyon. Humihinto ang Zone 2 sa 2.25 m sa parehong bansa. Sakop din ng Australian Zone 3 ang espasyo sa ibabaw ng Zone 2, hanggang 2.5 m.

Puwede bang ilagay ang socket‑outlet sa banyo?

Hindi ito puwede sa Zone 0 o Zone 1. Sa Zone 2, dapat itong shaver supply unit, o nakakabit sa 30 mA RCD sa loob ng cupboard. Sa Zone 3, kailangan nito ng 30 mA RCD, separated circuit o SELV. Panatilihin ang bawat socket‑outlet at switch na 0.3 m o higit pa mula sa sahig.

Anong IP rating ang kailangan ng downlight sa ibabaw ng shower?

IPX4 sa Zone 1 o Zone 2. Ang ceiling rose ay nagbibigay ng Zone 1 na 1.2 m sa NZ at 0.6 m sa Australia, hanggang sa taas ng rose. Ang recessed light na may lahat ng live parts sa ibabaw ng kisame ay nasa labas ng zone sa ibaba nito.

Sakop ba ng IPX7 ang zone na humihingi ng IPX5?

Hindi. Ang ikalawang numeral na hanggang 6 ay sumasaklaw sa lahat ng mas mababa, pero ang 7 o 8 lamang ay hindi sumasaklaw sa water jets (AS 60529 Cl 6). Ang pool Zone 1 ay humihingi ng IPX5, kaya hanapin ang dual code gaya ng IPX5/IPX7.

Bakit nagbabago ang spa sa 680 L at 5000 L?

Ang spa hanggang 680 L ay sumusunod sa bath at shower zones. Mula 680 L hanggang 5000 L, umaabot ang Zone 1 ng 1.25 m mula sa gilid, hanggang 2.5 m. Kapag higit sa 5000 L, o kapag konektado sa pool, sumusunod ang spa sa pool zones.

Sa plan

Mga worked example

Background

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 1 Oct 2026.

Nakatulong ba ito?

May tanong, o may value na mukhang mali? Makipag-ugnayan sa amin.