Wet area zones checker
Hanapin ang Section 6 zone, IP at RCD malapit sa tubig.
Reads AS/NZS 3000:2018. Tables checked 1 Oct 2026.
Subukan ang isang job 12
Nilalagyan ng halimbawang value ang bawat job. Palitan ang mga ito ng sarili mong value.
- Check a downlight over a showerWhether an IP20 downlight 0.5 m from a 2.4 m ceiling rose passes.
- Put a socket‑outlet by a basinThe zone and the conditions for a socket‑outlet 0.1 m from a basin.
- Light a spa poolThe zone and IP rating for a light 1 m from a 1500 L spa.
- Put a socket‑outlet beside a bathThe zone and the conditions 0.4 m from a bath.
- Put a switch in a bathroomThe zone for a light switch 0.7 m from a shower.
- Put a socket‑outlet by a kitchen sinkThe zone and the conditions 0.2 m from a sink.
- Light a swimming pool surroundThe zone and IP rating for a light 2 m from a pool.
- Put a socket‑outlet near a poolWhether a socket‑outlet 3 m from a pool passes.
- Fit a light in a saunaThe zone for a luminaire above a sauna heater.
- Light a fountainThe zone and IP rating for a light in a fountain.
- Check a communal shower roomThe IP rating a communal shower asks for.
- Check a bathroom in AustraliaThe zone and IP rating for a light near an open shower, to the Australian rules.
Mga input
Worked example gamit ang mga default na input.
- Sitwasyon
- Bath
- Bansa
- New Zealand
- Haba ng fixture
- 1.6 m
- Lapad ng fixture
- 0.7 m
- Taas ng connection o rose
- 0 m
- Komunal na paliguan o shower
- Hindi
- Kagamitan
- Luminaire
- Distansya mula sa shower connection
- 0 m
- Sa tubig o sa base (Zone 0)
- Hindi
- Distansya palabas
- 0.8 m
- Taas mula sa sahig
- 2.4 m
- IP rating
- IPX4
- Sa 30 mA RCD
- Oo
- Pag-print
- A1 hanggang A3 (kasalukuyan)
Zone
Nasa labas ng bawat zone
- Pinakamababang IP rating
- Wala
- Pinapayagan dito
- Outside the zones
Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.
Mga hakbang ng kalkulasyon
- SitwasyonBathtub
AS/NZS 3000:2018 Cl 6.2.2.1
- Distansyang sinukat mula saang panloob na rim
AS/NZS 3000:2018 Cl 6.2.2.1
- Zone 10 m out, up to 2.25 m (Cl 6.2.2.1(b))
AS/NZS 3000:2018 Cl 6.2.2.1
- Zone 20.6 m out, up to 2.25 m (Cl 6.2.2.1(d))
AS/NZS 3000:2018 Cl 6.2.2.1
- Zone 33 m out, up to 2.25 m (Cl 6.2.2.1(e))
AS/NZS 3000:2018 Cl 6.2.2.1
- Posisyon ng device0.8 m out, 2.4 m up
AS/NZS 3000:2018 Cl 6.2.2.1
- ZoneResultaNasa labas ng bawat zone
AS/NZS 3000:2018 Cl 6.2.2.1
Tungkol sa calculator na ito
How this is calculated
The tool places a light, switch or socket‑outlet in a zone. It then reads the least IP rating and the RCD rule for that zone. It follows Section 6 of AS/NZS 3000:2018.
- Situation. You pick the fitting: a bath, a shower, a basin, a spa, a pool or a sauna. Each one has its own table of zones.
- Reference point. Each situation measures from its own point. A bath measures from the internal rim. A shower measures from the fixed plumbing connection or the rose.
- Zone limits. The tool lists Zone 1, Zone 2 and Zone 3 (Cl 6.2.2.1). Each has a distance out and a height up.
- Device position. You enter the horizontal distance and the height of the device. The tool finds the first zone that holds that point.
- IP rating. The zone sets the least IP rating (Cl 6.2.4). The tool compares your rating with it.
- RCD and position. The tool adds the RCD rule for a home (Cl 2.6.3.3.1). It also gives the lowest height for a socket‑outlet or switch.
| Step | Table or clause | What it decides |
|---|---|---|
| Zone limits | Cl 6.2.2.1 | The distance and height of each zone |
| IP rating | Cl 6.2.4 | The least IP rating for the zone |
| Walls and fixed barriers | Cl 6.2.1 | Where a zone stops |
| RCD | Cl 2.6.3.3.1 | The 30 mA rule for a home |
| Bonding | Cl 5.6.2.5 | The earth bond of conductive reinforcing |
Worked example
Each link opens the tool with its inputs.
- Luminaire at an open shower. The luminaire sits 0.3 m from the plumbing connection and 1.8 m up. It has an IPX2 rating. The tool puts it in Zone 1 and asks for IPX4 at least. The check fails on the IP rating.
Limits
- The tool does not model a barrier that shrinks a zone. Walls, doors, floors and ceilings also limit the zones. Check the room.
- A shower over a bath adds a radius from the shower connection. You must type that distance.
- Equipment behind a fixed IPX4 panel that needs a tool to open is not in a zone. The tool does not decide this for you.
- A recessed fitting with all live parts above the ceiling is outside the zones below it.
- Protection by obstacles or by placing out of reach is not allowed in these zones.
- The tool points at the clause. It is not a ruling on a design.
See also: Wire a bathroom: zones, IP and the RCD, Damp situations and the Section 6 zones and RCD selection.
Mga tanong
Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.
Gaano kataas ang Zone 1 sa NZ at sa Australia?
Ang Zone 1 sa ibabaw ng bath o shower ay umaabot ng 2.25 m mula sa sahig sa New Zealand at 2.5 m sa Australia. Tumataas ito hanggang sa shower connection kapag mas mataas iyon. Humihinto ang Zone 2 sa 2.25 m sa parehong bansa. Sakop din ng Australian Zone 3 ang espasyo sa ibabaw ng Zone 2, hanggang 2.5 m.
Puwede bang ilagay ang socket‑outlet sa banyo?
Hindi ito puwede sa Zone 0 o Zone 1. Sa Zone 2, dapat itong shaver supply unit, o nakakabit sa 30 mA RCD sa loob ng cupboard. Sa Zone 3, kailangan nito ng 30 mA RCD, separated circuit o SELV. Panatilihin ang bawat socket‑outlet at switch na 0.3 m o higit pa mula sa sahig.
Anong IP rating ang kailangan ng downlight sa ibabaw ng shower?
IPX4 sa Zone 1 o Zone 2. Ang ceiling rose ay nagbibigay ng Zone 1 na 1.2 m sa NZ at 0.6 m sa Australia, hanggang sa taas ng rose. Ang recessed light na may lahat ng live parts sa ibabaw ng kisame ay nasa labas ng zone sa ibaba nito.
Sakop ba ng IPX7 ang zone na humihingi ng IPX5?
Hindi. Ang ikalawang numeral na hanggang 6 ay sumasaklaw sa lahat ng mas mababa, pero ang 7 o 8 lamang ay hindi sumasaklaw sa water jets (AS 60529 Cl 6). Ang pool Zone 1 ay humihingi ng IPX5, kaya hanapin ang dual code gaya ng IPX5/IPX7.
Bakit nagbabago ang spa sa 680 L at 5000 L?
Ang spa hanggang 680 L ay sumusunod sa bath at shower zones. Mula 680 L hanggang 5000 L, umaabot ang Zone 1 ng 1.25 m mula sa gilid, hanggang 2.5 m. Kapag higit sa 5000 L, o kapag konektado sa pool, sumusunod ang spa sa pool zones.
Sa plan
Mga worked example
- IP ratings for an outdoor point and a hosed shedWhich IP code an outdoor power point, a milking shed light and a hosed switchboard need, and why an IP67 light can fail where IP65 passes.
- Kitchen power points and the cooktop zonePlace power points and switches near a cooktop, an outdoor gas bottle and a gas vent. Check each distance to AS/NZS 3000 and hand the sink to the wet area tool.
- Wire a bathroom: zones, IP ratings and the RCDA New Zealand bathroom with a 1.6 m bath and an open shower, worked through the AS/NZS 3000 Section 6 zones, the IP each item needs, the RCD and bonding.
Background
- IP ratings explained: each digit and letterWhat the two numerals of an IP code mean, what X, the letters A to D and H, M, S, W add, why IP67 is not better than IP65 for jets, and where 3000 sets a code.
- Power points near a cooktop, gas bottle and sinkThe AS/NZS 3000 zones that keep power points, switches and lights away from cooktops, gas cylinders, gas vents and regulators, and where sinks are checked.
- Damp situations: the Section 6 zonesHow AS/NZS 3000 Section 6 zones the space around baths, showers, basins, spas, pools, fountains and saunas, how to read an IP code, and what A2 changed.
Mga clause at table na binabasa ng tool na ito
- AS/NZS 3000:2018 Cl 2.6.3.2.2AU domestic RCD circuits
- AS/NZS 3000:2018 Cl 2.6.3.3.1NZ residential RCD circuits
- AS/NZS 3000:2018 Cl 5.6.2.5Bonding in showers and bathrooms
- AS/NZS 3000:2018 Cl 5.6.2.6Bonding at swimming and spa pools
- AS/NZS 3000:2018 Cl 5.6.3.2Size of the wet area bonding conductor
- AS/NZS 3000:2018 Cl 6.2.1Limits of the bath and shower zones
- AS/NZS 3000:2018 Cl 6.2.2.1Zones for baths and showers
- AS/NZS 3000:2018 Cl 6.2.2.2Zones for basins, sinks and tubs
Bawat clause at table, kasama kung paano ito na-verify
Huling na-check ang mga table noong 1 Oct 2026.
Mga kaugnay na tool
- RCD Selection calculatorCheck if an RCD is required and test the trip time.AS/NZS 3000Electricity (Safety) Regulations 2010
- Power point location checkPower points near a cooktop, gas cylinder, vent or sink.AS/NZS 3000
- IP rating chart at decoderDecode an IP code and find the least for a location.AS 60529AS/NZS 3000