VSD motor lead check
Tingnan ang motor lead ng drive: peak voltage, haba at cable.
Reads AS/NZS 3000:2018. Tables checked 2 Oct 2026.
Subukan ang isang job 4
Nilalagyan ng halimbawang value ang bawat job. Palitan ang mga ito ng sarili mong value.
- Check a drive motor leadWhether a pump on a drive needs an output filter for its motor lead.
- Check a long fan lead on a VSDA fan motor far from its drive, against the drive maker limit.
- Size a conveyor drive lead with a filterA long conveyor lead on a sine filter and the current for its cable.
- Check an inverter-rated motor on a driveWhether an inverter-rated motor takes the reflected peak without a filter.
Mga input
Worked example gamit ang mga default na input.
- Power ng motor
- 22 kW
- Supply voltage
- 400 V
- Power factor ng motor
- 0.85
- Rated peak voltage ng motor
- 1,000 V
- Haba ng motor lead
- 60 m
- Cable
- Screened, symmetrical
- Output filter
- Wala
- Lead limit ng gumawa, walang filter
- 100 m
- Pulse rise time
- 0.1 µs
- Bilis ng pulse sa cable
- 150 m/µs
Lead ng motor
Pumalya
- Peak sa motor, hanggang
- 1,131V
- Limitasyon ng lead ng maker
- 100m
- Kritikal na haba ng lead
- 7.5m
- Current para sa laki ng cable
- 41.51A
- Drive sa d.c. bus
- 565.7V
Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.
Mga hakbang ng kalkulasyon
- Current para sa laki ng cable41.51A
- Drive sa d.c. bus565.7V
- Kritikal na haba ng lead sa 0.1 µs na rise time7.5m
- Peak sa motor, hanggang1,131V
- Motor insulation, rated peak1,000V
- Limit ng lead ng gumawa, walang filter100m
- Lead ng motorResultaBigo
Tungkol sa calculator na ito
How this is calculated
A variable speed drive does not send a smooth sine wave down the motor lead. It sends fast pulses at the voltage of its d.c. bus, and each pulse can reflect at the motor. On a long enough lead the reflection nearly doubles the voltage at the motor terminals, which can break down the insulation of a motor not rated for it. This tool works that peak, checks the lead against the drive maker's limit, and gives the current to size the cable for.
The bus voltage is the supply voltage times √2. The critical length is how far a pulse travels in half its rise time; on a lead longer than that the reflection is full and the peak at the motor reaches about twice the bus. On a shorter lead the tool scales it down. A dv/dt filter or an output reactor slows the edge but does not end the reflection, so the tool makes no estimate of its own: you enter the peak at the motor from the filter maker's data for your lead, and the result says it is the maker's figure. Only a sine filter brings the peak down to the bus voltage. The peak is compared with the motor maker's rating. The lead is compared with the drive maker's limit, with or without the filter.
The current is the motor tool's full load current. The rise time, the pulse speed, the limits and the motor's rating are makers' data, entered by you, so the result calls them assumptions. AS/NZS 3000 warns of high frequency current on the protective earth, and notes the cable tables are for 50 Hz.
| Step | Table or clause | What it decides |
|---|---|---|
| Cable current | The motor tool | The current for the cable size |
| Bus voltage | Supply voltage times √2 | The height of each pulse |
| Critical length | Pulse speed times half the rise time | Where the reflection becomes full |
| Peak at the motor | Up to twice the bus; the filter maker's figure with a dv/dt filter or reactor; the bus with a sine filter | The voltage the motor sees |
| Lead length | The drive maker's limit | Whether the lead needs a filter |
| Earthing and ratings | AS/NZS 3000 Cl 5.4.8 and Cl 4.12.8 Note 1 | The earth current and the 50 Hz basis |
Worked examples
- A 22 kW pump on a 60 m lead, standard motor fails: the peak can reach 1,131 V against the motor's 1000 V rating. The cable carries 41.51 A.
- The same pump with a dv/dt filter passes if the filter maker gives a peak of 900 V at the motor for 60 m. The tool prints that 900 V as the maker's figure; it is an example, not an estimate.
- The same pump with an inverter-rated motor passes with a peak of up to 1,131 V on a 1600 V rating.
- A 7.5 kW fan on a 150 m lead fails on length: the drive maker allows 100 m with no filter, though the peak of up to 1,131 V is within the motor's rating.
- A 55 kW conveyor on a 250 m lead with a sine filter passes with a peak near 566 V, inside the 300 m limit with the filter.
Limits
The peak is a first estimate from the lead length alone. The real peak depends on the cable's and motor's surge impedance, the switching pattern and the drive's own output stage, which the makers test. The tool does not size the cable for harmonics on the drive's supply side, the cable's capacitive charging current, or bearing currents.
See also: Motor, Motor starting and Cable size.
Mga tanong
Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.
Bakit mahalaga ang mahabang motor lead sa VSD?
Nagpapadala ang drive ng mabilis na voltage pulses. Sa mahabang lead, bumabalik ang bawat pulse sa motor at halos nagdodoble ang voltage doon. Puwede nitong masira ang insulation ng motor na hindi rated para dito.
Ano ang critical lead length?
Ang haba na nalalakbay ng pulse sa kalahati ng rise time nito. Lampas dito, buo na ang reflection. Sa rise time na 0.1 µs at pulse speed na 150 m/µs, 7.5 m ito, kaya lampas dito ang karamihan ng motor lead.
Kailangan ko ba ng dv/dt o sine filter?
Kapag lumampas ang lead sa limit ng drive maker, o lumampas ang peak sa rating ng motor. Pinapabagal ng dv/dt filter o reactor ang edge pero may natitirang overshoot, kaya kinukuha ng tool ang peak na iyon mula sa datos ng filter maker. Pinapakinis ng sine filter ang output halos hanggang sa sine wave.
Anong cable ang dapat gamitin ng VSD?
Screened at symmetrical na cable na may screen na naka-bond sa lahat ng gilid sa magkabilang dulo, ayon sa sinasabi ng drive maker. I-size ito para sa motor current, at tandaan na ang ratings ng AS/NZS 3008.1 ay para sa 50 Hz.
Bakit puwedeng makakuha ng shock mula sa naka-earth na metal ang VSD?
Binabalaan ng AS/NZS 3000 Cl 5.4.8 na puwedeng maglagay ang drive ng high frequency current sa protective earth, na may touch voltages hanggang 100 V. Puwedeng hindi ito makita ng 50 Hz tester. I-earth ang drive ayon sa sinasabi ng maker nito.
Mga clause at table na binabasa ng tool na ito
- AS/NZS 3000:2018 Cl 4.12.8Equipment on a converter output
- AS/NZS 3000:2018 Cl 5.4.8Variable frequency devices
- AS/NZS 3000:2018 Cl 5.4.8 and Cl 4.12.8Variable frequency drives
Bawat clause at table, kasama kung paano ito na-verify
Huling na-check ang mga table noong 2 Oct 2026.
Mga kaugnay na tool
- Cable size calculatorFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Motor calculatorFind motor full load current, starting current and torque.Walang standard
- Paghahambing ng motor starting methodCompare DOL, star-delta, soft start and drive starts.Walang standard
Nakatulong ba ito?
May tanong, o may value na mukhang mali? Makipag-ugnayan sa amin.