Idagdag ang drop ng mains, submain at final laban sa 5 %.

Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 1 Oct 2026.

Mga input

Worked example gamit ang mga default na input.

Point of supply
Network supply (limit na 5 %)
Standard
NZ · AS/NZS 3008.1.2
Power factor
0.9
Mga bahagi ng run, mula sa punto ng supply
3 row

Kabuuang voltage drop

4.25%

Limit ng voltage drop
5%
Mains at submains
1.98%
Natira para sa final subcircuit
3.02%
Naiwan sa punto ng paggamit
0.75%

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Bahagi 1Consumer mains
  2. Bahagi 1 mV/A·m2.6mV/A·m

    AS/NZS 3008.1.2:2017 Cl 4.5

  3. Voltage drop ng bahagi 12.6V
  4. Voltage drop ng bahagi 1, porsyento ng 230 V1.13%

    AS/NZS 3000:2018 App C Para C4.1

  5. Running total pagkatapos ng bahagi 11.13%

    AS/NZS 3000:2018 App C Para C4.1

  6. Bahagi 2Submain
  7. Bahagi 2 mV/A·m4.09mV/A·m

    AS/NZS 3008.1.2:2017 Cl 4.5

  8. Voltage drop ng bahagi 21.96V
  9. Voltage drop ng bahagi 2, porsyento ng 230 V0.85%

    AS/NZS 3000:2018 App C Para C4.1

  10. Running total pagkatapos ng bahagi 21.98%

    AS/NZS 3000:2018 App C Para C4.1

  11. Bahagi 3Final subcircuit
  12. Bahagi 3 mV/A·m16.31mV/A·m

    AS/NZS 3008.1.2:2017 Cl 4.5

  13. Voltage drop ng bahagi 35.22V
  14. Voltage drop ng bahagi 3, porsyento ng 230 V2.27%

    AS/NZS 3000:2018 App C Para C4.1

  15. Running total pagkatapos ng bahagi 34.25%

    AS/NZS 3000:2018 App C Para C4.1

  16. Limitasyon ng voltage drop5%

    AS/NZS 3000:2018 Cl 3.6.2

  17. Kabuuang voltage dropResulta4.25%

    AS/NZS 3000:2018 Cl 3.6.2

  18. Mains at submains1.98%
  19. Natira para sa final subcircuit3.02%

    AS/NZS 3000:2018 Cl 3.6.2

  20. Naiwan sa punto ng paggamit0.75%

Tungkol sa calculator na ito

How this is calculated

AS/NZS 3000 limits the voltage drop from the point of supply to any point in the installation. It is one limit for the whole run, not one per circuit. So the drop in the consumer mains, every submain and the final subcircuit must add up to no more than the limit. This tool adds them.

You enter each part of the run in order from the point of supply: the consumer mains, up to three submains and the final subcircuit. For each part you give the phases, the current, the route length and the cable. The tool works each part with the same calculation as the voltage drop tool. It reads the cable's resistance and reactance from AS/NZS 3008.1, finds the mV/A·m at the power factor, and gives the drop in volts.

Each drop is then taken as a percent of that part's own circuit voltage: 230 V for single phase and 400 V for three phase. Appendix C of AS/NZS 3000 adds the percents directly, so a three‑phase submain adds to a single‑phase final subcircuit with no conversion. The running total is the drop at the end of each part.

The limit is 5 % of the nominal voltage. Where the point of supply is the low voltage terminals of a substation on the premises, which supplies only this installation, it is 7 %. The clause sets no split between the parts. The tool shows what the mains and submains take, and what that leaves for a final subcircuit from the last board.

StepTable or clauseWhat it decides
Resistance and reactance of each partAS/NZS 3008.1 Tables 34 and 35The impedance of the cable
Drop of each partAS/NZS 3008.1 Cl 4.5The mV/A·m and the drop in volts
Percent of each partAS/NZS 3000 App C Para C4.1The drop as a percent of its circuit voltage, added part by part
The limitAS/NZS 3000 Cl 3.6.2The most the total may be from the point of supply
A substation on the premisesAS/NZS 3000 Cl 3.6.2 Exception 3The higher limit where it applies
A load spread along a final subcircuitAS/NZS 3000 Cl 3.6.2 Exception 1The current you may use for that part

Worked examples

Limits

The tool works a.c. runs at 230 V and 400 V nominal. It does not check extra-low voltage circuits, which Cl 3.6.2 leaves out, or a stand-alone system, which Exception 4 judges on the utilisation voltage. Single‑core parts use the highest reactance the table gives for the formation. Use the voltage drop tool for one run with a known formation or an unbalanced neutral.

Motor starting and other short transient drops are not part of the limit. Check those against the equipment.

See also: Voltage drop, The 5 % voltage drop limit from supply to load and Total voltage drop: mains, submain and final.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Para ba sa bawat circuit o sa buong installation ang 5 % voltage drop?

Ang buong installation. Nililimitahan ng AS/NZS 3000 Cl 3.6.2 ang voltage drop mula sa point of supply hanggang sa anumang point. Ang consumer mains, submains at ang final subcircuit ay nagbabahagi ng iisang 5 %, kaya ito ang idinadagdag ng tool.

May hati bang 2 % at 3 % sa pagitan ng mains at final subcircuits?

Hindi ito nasa AS/NZS 3000. Ang Cl 3.6.2 ay nagtatakda ng isang limitasyon at walang hati. Madalas magplano ng isa ang mga designer, pero ang clause ay humihingi lamang na manatili ang kabuuan sa loob ng limitasyon. Ipinapakita ng tool kung ano ang kinukuha ng mains at submains, at kung ano ang natitira.

Paano ako magdaragdag ng three‑phase submain sa single‑phase final subcircuit?

Ayon sa percent. Ang bawat bahagi ay kinukuwenta bilang percent ng sarili nitong circuit voltage, 400 V para sa three phase at 230 V para sa single phase. Diretsong idinadagdag ng Appendix C ng AS/NZS 3000 ang mga percent na iyon.

Kailan 7 % ang limit?

Kapag ang point of supply ay ang low voltage terminals ng substation sa parehong premises na nagsusupply lang sa installation na ito. Piliin ang Own substation at 7 % ang gamit ng tool.

Anong current ang dapat kong gamitin para sa bawat part?

Ang maximum demand ng bawat bahagi, ang connected load nito, o ang protective device rating nito, alinman ang alam mo. Ang final subcircuit na may load na nakakalat sa buong haba nito ay puwedeng gumamit ng kalahati ng device rating.

Mga worked example

Background

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 1 Oct 2026.