AmpSize

Site cord length calculator

Ang pinakamahabang run ng cord o cable na puwede sa construction site.

Reads AS/NZS 3012:2019. Tables checked 1 Oct 2026.

Mga input

Worked example gamit ang mga default na input.

Rated current
10 A
Lawak ng conductor
2.5 mm²
Cable
Single phase, 3 core
Gamit
Pangkalahatang gamit, gaya ng saw, grinder at drill
Kabuuang haba mula sa socket-outlet hanggang sa kagamitan
40 m
Lead ng supply ng PSOA
0 m
Voltage drop na ginagamit ng fixed wiring bago ang socket-outlet
0 %
Dalawa o higit pang cord extension set ang pinagdugtong
Hindi
Ginagamit nang nakapulupot o nasa reel ang cord
Hindi

Pinakamataas na haba

60m

Nasuri ang haba
40m
Lead ng supply ng PSOA
0m
Nasa loob ng limit
Oo
Voltage drop na batayan ng haba
5%
Voltage drop na nagamit na sa itaas
0%
Kabuuang voltage drop sa kagamitan
5%
Sanggunian
AS/NZS 3012:2019 Table 1

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Nailagay na haba40m

    AS/NZS 3012:2019 Table 1

  2. Supply lead ng PSOA0m

    AS/NZS 3012:2019 Cl 2.6.10(b)

  3. Sinuri ang haba laban sa Table 140m

    AS/NZS 3012:2019 Table 1

  4. Rated current10A

    AS/NZS 3012:2019 Table 1

  5. Area ng conductor2.5mm²

    AS/NZS 3012:2019 Table 1

  6. Voltage drop na batayan ng haba5%

    AS/NZS 3012:2019 Table 1

  7. Voltage drop na nagamit na sa upstream0%

    AS/NZS 3012:2019 Table 1

  8. Kabuuang voltage drop na ipinapahiwatig ng haba na ito5%

    AS/NZS 3012:2019 Table 1

  9. Pinakamahabang haba60m

    AS/NZS 3012:2019 Table 1

  10. Pangkalahatang gamit, single phaseResulta60m

    AS/NZS 3012:2019 Table 1

  11. Pangkalahatang gamit, three phase120m

    AS/NZS 3012:2019 Table 1

  12. Espesipikong gamit, single phase35m

    AS/NZS 3012:2019 Table 1

  13. Espesipikong gamit, three phase70m

    AS/NZS 3012:2019 Table 1

Tungkol sa calculator na ito

How this is calculated

The tool checks a cord or flexible cable on a construction site. It uses the length limit in AS/NZS 3012:2019 Table 1. The limit depends on the rated current, the conductor area, the use and the phases.

  1. Length entered. You enter the length of the cord run. You can add the length of the PSOA supply lead, under Cl 2.6.10(b).
  2. Length checked. The tool adds the two. It checks that total against Table 1.
  3. Rated current and area. It reads the Table 1 row for your rated current and conductor area.
  4. Use and phases. It picks the column: general or specific use, single or three phase.
  5. Maximum length. It gives the Table 1 length. The inside-the-limit answer passes when the length checked is at or under it.
  6. Total drop. The Table 1 length is based on a 5 % drop. The tool adds the drop already used upstream and gives the total at the equipment.
StepTable or clauseWhat it decides
PSOA leadAS/NZS 3012 Cl 2.6.10(b)The length counted with the cord
Maximum lengthTable 1The limit for the rating, area and use
Total dropTable 1The drop at the equipment, with the upstream drop

Worked example

A 10 A single‑phase cord of 1.5 mm², 50 m long, for general use. The maximum length is 35 m. The 50 m run fails. A 2.5 mm² cord at 40 m passes, with a maximum of 60 m.

Limits

  • The 5 % drop is in addition to the drop the fixed installation already used. Enter the real upstream drop.
  • A zero upstream drop is the default. Treat it as optimistic.
  • The figures suit ordinary site power tools.
  • The smallest flexible cord conductor is 1 mm². Every cord carries its own earth conductor.
  • Cord extension sets use heavy duty sheathed cable (Cl 2.6.3).
  • Do not use double adaptors or piggyback plug adaptors (Cl 2.6.6).

See also: Construction site supplies, AS/NZS 3012, Builder's pole house build supply, RCDs and cord lengths and the site supply tool.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Gaano kahaba puwedeng i-run ang extension cord sa construction site?

Nagbibigay ang Table 1 ng AS/NZS 3012:2019 ng limit para sa bawat rated current at conductor size. Ang 10 A, 2.5 mm² single phase cord para sa general use ay humihinto sa 60 m. Ang three phase, four core cable na may ganoong laki ay umaabot sa 120 m.

Ano ang pagkakaiba ng general use at specific use?

Sakop ng General use ang karaniwang site tools gaya ng lagari, grinder at drill. Pinapayagan ng haba nito ang 5 % na drop sa rated current. Ang Specific use ay para sa equipment na kapag pumalya ang motor start ay naglalagay sa panganib sa isang tao. Pinapayagan ng haba nito ang 3 %, kaya mas maikli ang mga ito.

Kasama ba sa voltage drop ng table ang fixed wiring?

Hindi. Ang porsyento ng table ay dinadagdag sa voltage drop na nagamit na ng fixed wiring bago ang socket‑outlet. Ilagay ang figure na iyon, at ipinapakita ng tool ang kabuuan sa equipment. Sinasabi ito ng bawat resulta.

Puwede ko bang pagdugtungin ang dalawang extension lead?

Oo, kung nananatili sa loob ng isang Table 1 limit ang buong run. I-enter ang kabuuan ng bawat pinagdugtong na set, at tinitingnan ng tool ang kabuuang iyon. Kasama rin ang PSOA supply lead, kaya idinadagdag ito ng tool. Inirerekomenda ng AS/NZS 3012 ang iisang set, at sinasabing huwag gumamit ng cord na naka-coil o nasa reel.

Ano ang pinakamaliit na cord conductor na pinapayagan?

Itinatakda ng Cl 2.6.2 ang 1.0 mm² bilang pinakamababa para sa bawat core ng flexible cord. Kailangan din ng cord ng earth conductor sa tabi ng live conductors nito.

Mga worked example

Background

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 1 Oct 2026.