RCD arrangement check
Tingnan ang mga circuit kada RCD at ang lighting split.
Reads AS/NZS 3000:2018. Tables checked 1 Oct 2026.
Subukan ang isang job 4
Nilalagyan ng halimbawang value ang bawat job. Palitan ang mga ito ng sarili mong value.
- Find an RCD with too many circuitsA house board with four circuits on one RCD.
- Split a large board onto three RCDsNine circuits and three lighting circuits spread over three RCDs.
- Check an Australian board of RCBOsEvery final subcircuit on its own RCBO in an AU home.
- Check the lighting split in an officeOffice lighting circuits spread over two RCDs.
Mga input
Worked example gamit ang mga default na input.
- Bansa
- New Zealand
- Installation
- Residential
- Mga final subcircuit sa board
- 8 row
Ayos ng RCD
Pumapasa
- Mga RCD sa board
- 2
- Mga circuit na nangangailangan ng RCD
- 6
- Pinakamaraming circuit sa isang RCD
- 3
- Mga lighting circuit
- 2
Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.
Mga hakbang ng kalkulasyon
- Circuit 1Lighting
- Rating ng Circuit 110A
- RCD ng Circuit 1RCD 1
- Kailangan ng Circuit 1 ng RCD na hindi lalampas sa30mA
AS/NZS 3000:2018 Cl 2.6.3.3.1
- Circuit 2Mga socket‑outlet
- Rating ng Circuit 220A
- RCD ng Circuit 2RCD 1
- Kailangan ng Circuit 2 ng RCD na hindi lalampas sa30mA
AS/NZS 3000:2018 Cl 2.6.3.3.1
- Circuit 3Mga socket‑outlet
- Rating ng Circuit 320A
- RCD ng Circuit 3RCD 1
- Kailangan ng Circuit 3 ng RCD na hindi lalampas sa30mA
AS/NZS 3000:2018 Cl 2.6.3.3.1
- Circuit 4Lighting
- Rating ng Circuit 410A
- RCD ng Circuit 4RCD 2
- Kailangan ng Circuit 4 ng RCD na hindi lalampas sa30mA
AS/NZS 3000:2018 Cl 2.6.3.3.1
- Circuit 5Mga socket‑outlet
- Rating ng Circuit 520A
- RCD ng Circuit 5RCD 2
- Kailangan ng Circuit 5 ng RCD na hindi lalampas sa30mA
AS/NZS 3000:2018 Cl 2.6.3.3.1
- Circuit 6Mga socket‑outlet
- Rating ng Circuit 620A
- RCD ng Circuit 6RCD 2
- Kailangan ng Circuit 6 ng RCD na hindi lalampas sa30mA
AS/NZS 3000:2018 Cl 2.6.3.3.1
- Circuit 7Fixed o stationary na kagamitan
- Rating ng Circuit 732A
- RCD ng Circuit 7Wala
- Kailangan ng Circuit 7 ng RCDHindi ayon sa mga clause na sinusuri ng tool na ito
AS/NZS 3000:2018 Cl 2.6.3.3.1
- Circuit 8Fixed o stationary na kagamitan
- Rating ng Circuit 820A
- RCD ng Circuit 8Wala
- Kailangan ng Circuit 8 ng RCDHindi ayon sa mga clause na sinusuri ng tool na ito
AS/NZS 3000:2018 Cl 2.6.3.3.1
- RCD 13 circuit, 1 lighting
- RCD 23 circuit, 1 lighting
- Mga RCD sa board2
- Mga circuit na nangangailangan ng RCD6
- Pinakamaraming circuit sa isang RCD3
AS/NZS 3000:2018 Cl 2.6.2.4(b)(i)
Tungkol sa calculator na ito
How this is calculated
You list the final subcircuits on one switchboard. For each circuit you give what it supplies, its rating and the RCD it sits on. An RCBO is an RCD with one circuit, so give each RCBO its own number. A circuit on no RCD has the number 0.
First the tool asks, circuit by circuit, whether the clauses call for additional protection by an RCD, and at what rated residual current. It reads the same rows as the RCD selection tool. In New Zealand homes that is every circuit that supplies socket‑outlets, lighting points or hand-held equipment. In Australian homes it is every final subcircuit. Schools, childcare, outdoor and public places and other buildings follow their own items. A circuit that needs an RCD and sits on none fails.
Then it groups the circuits by RCD and checks the arrangement clause. In every installation with more than one RCD and more than one lighting circuit, the lighting circuits must be on more than one RCD, so one trip does not put out every light. In a residential installation, one RCD may protect three final subcircuits at most. Every circuit on that RCD counts, even one that would not need it. A residential board with more than one circuit that needs an RCD must have at least two RCDs.
The result lists each circuit, each RCD with its count, and the four checks with their clause.
| Step | Table or clause | What it decides |
|---|---|---|
| Which circuits need an RCD, New Zealand | Cl 2.6.3.3.1 and Cl 2.6.3.3.2 | The circuits that must be on an RCD, and its rated residual current |
| Which circuits need an RCD, Australia | Cl 2.6.3.2.2 and Cl 2.6.3.2.3.3 | The same for an Australian installation |
| Lighting spread | Cl 2.6.2.4(a) | Lighting circuits on more than one RCD |
| Circuits on one RCD | Cl 2.6.2.4(b)(i) | The most final subcircuits one residential RCD may protect |
| Number of RCDs | Cl 2.6.2.4(b)(ii) | The fewest RCDs on a residential board |
Worked examples
- A house board with four circuits on RCD 1. The arrangement fails: 4 on the fullest RCD, one more than a residential RCD may protect. Move one circuit to RCD 2.
- A larger house on three RCDs. The arrangement passes every check, with 3 on the fullest RCD and a lighting circuit on each RCD. The car charger counts as one of the three on RCD 3.
- An Australian home of RCBOs. The arrangement passes every check, with 1 on the fullest RCD. Every final subcircuit needs an RCD in an Australian home, the oven and water heater too, and each has its own.
- An office with both lighting circuits on RCD 1. The arrangement fails the lighting spread, with 3 on the fullest RCD. The count limit does not apply outside a residential installation, but the lighting spread does.
Limits
The tool checks one board. It takes each socket‑outlet as 10 A; use the RCD selection tool for a larger socket‑outlet, a trip time or a device type. It does not check the exceptions in Cl 2.6.3, such as a dedicated cooking socket‑outlet or equipment where a trip is more dangerous. It does not check discrimination between RCDs, or standing leakage on one RCD.
See also: How many circuits can go on one RCD, RCD arrangement for a house board and RCD selection.
Mga tanong
Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.
Ilang circuit ang puwede sa isang RCD?
Sa residential installation, hanggang tatlong final subcircuit lang, ayon sa AS/NZS 3000 Cl 2.6.2.4. Binibilang ang bawat circuit sa RCD, kasama ang hindi mangangailangan nito. Ang ibang installation ay walang limit sa bilang sa clause na iyon.
Kailangan ba ng bahay ng dalawang RCD?
Oo, kapag higit sa isang final subcircuit ang nangangailangan ng RCD protection. Hinihingi ng Cl 2.6.2.4 ang hindi bababa sa dalawang RCD sa residential installation, para hindi mawalan ng kuryente ang buong bahay sa isang trip lang.
Bakit ikalat ang lighting sa mga RCD?
Para hindi madilim ang buong gusali sa isang trip ng RCD. Kung ang board ay may higit sa isang RCD at higit sa isang lighting circuit, ilagay ang mga lighting circuit sa magkakaibang RCD. Naaangkop ito sa bawat installation.
Paano binibilang ang RCBO?
Ang RCBO ay RCD na may iisang circuit. Bigyan ang bawat RCBO ng sarili nitong RCD number sa listahan. Ang board ng RCBO ay sumusunod na sa tatlo-kada-RCD rule at sa lighting spread sa sarili nito.
Aling mga circuit ang nangangailangan ng RCD?
Ginagamit ng tool ang parehong sagot ng RCD selection tool, mula sa Cl 2.6.3. Sa mga bahay sa NZ, socket‑outlet, lighting at hand-held na circuit. Sa mga bahay sa AU, bawat final subcircuit. Ang ibang installation ay sumusunod sa sarili nilang item.
Mga worked example
- RCD tripping with no fault: add up the leakageAn RCD on a home office and kitchen trips with no fault found. Add up the standing leakage, check it against a third of 30 mA, and split it over two RCDs.
- RCD arrangement for a house boardCheck a New Zealand house board of eight circuits on two RCDs. See what fails with a fourth circuit on one RCD or both lights on one, and the AU change.
Background
- How many circuits can go on one RCDThe AS/NZS 3000 Cl 2.6.2.4 arrangement rules in plain words, which circuits need a 30 mA RCD in NZ and AU homes, how RCBOs count, and why the rules exist.
- RCD leakage and nuisance trippingWhy an RCD trips with no fault. Where standing leakage comes from, the one-third and one-half points of Cl 2.6.2.1, class limits against measured figures.
Mga clause at table na binabasa ng tool na ito
- AS/NZS 3000:2018 Cl 2.6.2.4Arrangement of circuits on RCDs
- AS/NZS 3000:2018 Cl 2.6.3.2.2Additional protection in Australia, domestic and residential
- AS/NZS 3000:2018 Cl 2.6.3.2.3.3Additional protection in Australia, non‑domestic
- AS/NZS 3000:2018 Cl 2.6.3.3.1Additional protection in New Zealand, residential
- AS/NZS 3000:2018 Cl 2.6.3.3.2Additional protection in New Zealand, non‑residential
- AS/NZS 3000:2018 Cl 2.6.2.4Arrangement of final subcircuits on RCDs
- AS/NZS 3000:2018 Cl 2.6.3, Cl 7.9.3 and Cl 7.9.4Additional protection by RCD, required residual current and circuit limits
Bawat clause at table, kasama kung paano ito na-verify
Huling na-check ang mga table noong 1 Oct 2026.
Mga kaugnay na tool
- RCD Selection calculatorCheck if an RCD is required and test the trip time.AS/NZS 3000Electricity (Safety) Regulations 2010
- RCD standing leakage budgetHow much standing leakage one RCD can carry.AS/NZS 3000AS/NZS 3760
- Test and tag intervalsRetest intervals and pass limits for portable gear.AS/NZS 3760
Nakatulong ba ito?
May tanong, o may value na mukhang mali? Makipag-ugnayan sa amin.