EV charger circuit calculator

Tingnan ang mga EV charger para sa spare capacity, cable size at RCD.

Reads AS/NZS 3000:2018. Tables checked 1 Oct 2026.

Mga input

Worked example gamit ang mga default na input.

Bansa
New Zealand · Clause 7.9
Charging mode
Mode 3
Installation
Pang-tahanang electrical installation
Bilang ng charger
1
Supply ng charger
Single‑phase
Rated current ng charger
32 A
Supply ng board
Single‑phase
Rating ng main switch o supply
0 A
Maximum demand nang walang charger
0 A
Load management device
Hindi
Haba ng run
20 m
Installation method
Enclosed sa hangin
Material
Tanso
Insulation
PVC 75 °C
Charger SDoC
Hindi nakasaad
Bersyon ng SDoC
Hindi nakasaad
Petsa ng SDoC
Hindi nakasaad
RCD na naka-install
Hindi naitala
Marking text ng RCD
Hindi nakasaad
Lokasyon ng RCD
Hindi nakasaad
Load control
Hindi naitala
Demand response
Hindi naitala

Cable size

6mm²

Spare capacity
Hindi pa nasusuri
Residual current device
30 mA Type B, hiwalay, sa bawat live conductor
Demand ng charger
32A
Pinakamababang kapasidad ng single-phase final subcircuit
32A
Isolating switch
32A
Mga clause na babasahin
AS/NZS 3000:2018 Cl 7.9.3.3

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Clause na binasa para sa mga figure na ito7.9.3.3

    AS/NZS 3000:2018 Cl 7.9.3.3

  2. Pinakamaliit na kapasidad ng single‑phase final subcircuit32A

    AS/NZS 3000:2018 Cl 7.9.3.3

  3. Iba pang punto sa huling subcircuitWala, hindi sakop ng clause ang mga ito

    AS/NZS 3000:2018 Cl 7.9.3.3

  4. Pinakamataas na rated residual current30mA

    AS/NZS 3000:2018 Cl 7.9.3.3

  5. Uri ng residual current deviceB

    AS/NZS 3000:2018 Cl 7.9.3.3

  6. Ayos ng residual current deviceHiwalay na device, sa bawat live conductor, kasama ang neutral

    AS/NZS 3000:2018 Cl 7.9.3.3

  7. Alternatibong device sa ExceptionA with RDC-DD

    AS/NZS 3000:2018 Cl 7.9.3.3

  8. Antas ng detection ng RDC-DD, mula sa NOTE6mA

    AS/NZS 3000:2018 Cl 7.9.3.3

  9. Pinakamababang rating ng isolating switch32A

    AS/NZS 3000:2018 Cl 7.9.3.3

  10. Pinakamababang taas mula sa sahig o lupa800mm

    AS/NZS 3000:2018 Cl 7.9.3.3

  11. Mga charger na binilang sa pinakamabigat na phase1
  12. Bahagi ng rated current na binibilang100%

    AS/NZS 3000:2018 Table C1 group (j)(iv)

  13. Demand ng charger sa pinakamabigat na phase32A

    AS/NZS 3000:2018 Table C1 group (j)(iv)

  14. Design current ng cable32A
  15. Laki ng cableResulta6mm²

    AS/NZS 3008.1.2:2017

  16. Voltage drop sa sukat na iyon2.09%

    AS/NZS 3008.1.2:2017

Tungkol sa calculator na ito

How this is calculated

The tool checks an EV charger circuit. It reads Clause 7.9.3.3 of AS/NZS 3000:2018 for the circuit, the RCD and the isolating switch. It reads Table C1 for the charger demand. It then takes a cable size from the cable size calculator.

  1. Circuit rules. The tool prints the minimum final subcircuit capacity and the other points allowed on it. It also prints the isolating switch rating (Cl 7.9.3.3).
  2. RCD. It prints the maximum rated residual current, the type and the arrangement of the device. It also lists the Exception that allows a device with RDC-DD.
  3. Charger demand. It counts the chargers on the heaviest phase. It applies the share of rated current that group (j)(iv) of Table C1 counts. Load management can set a lower limit.
  4. Spare capacity. It subtracts your maximum demand from the supply rating. It then subtracts the charger demand.
  5. Cable. It takes the design current for the charger. It sizes the cable and gives the drop over your run.
StepTable or clauseWhat it decides
Circuit and switchCl 7.9.3.3The capacity, the points and the isolator
RCDCl 7.9.3.3The type, the rating and the arrangement
Charger demandTable C1 group (j)(iv)The current counted for each charger
CableAS/NZS 3008.1.2The size and the drop for the run

Worked example

Limits

  • The tool reads the clause and prints its figures. It is a pointer to the clause, not a ruling on a design.
  • Clause 7.9 adds to Sections 2 to 7. A figure the tool does not report can still come from those Sections.
  • The clause prints a capacity figure for single‑phase circuits only. It prints none for a three‑phase circuit.
  • The RDC-DD level comes from a NOTE. A NOTE is not a requirement.
  • The cable uses the default inputs of the cable size tool. Open that tool to set grouping or ambient.
  • The tool reads the 2018 edition with Amendments 1, 2 and 3. It does not read the supply authority rules.
  • The install record lists what to check and keep, with each source. You tick the rows. The tool judges none of them.

See also: Clause 7.9 and EV charging in NZ, EV charging load and spare capacity and EV charger spare capacity on a 63 A main switch.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Ano ang ginagawa ng EV charger tool?

Tinitingnan nito ang mga charger laban sa spare capacity sa board, ini-size ang cable at pinapangalanan ang residual current device. Sa New Zealand, binabasa nito ang AS/NZS 3000:2018 Clause 7.9. Para sa domestic Mode 2, idinadagdag nito ang 30 mA ng Clause 2.6.3.3.1, na pinananatiling may bisa ng Clause 7.9.1. Ang Clause 7.9.3.3 ay naglilimbag ng 32 A na capacity para sa single‑phase final subcircuits lang.

Paano gumagana ang spare-capacity check?

I-enter ang rating ng main switch at ang maximum demand nang walang charger, kada phase. Ang pagkakaiba ay ang spare capacity. Binibilang ng tool ang bawat charger sa rated current nito sa pinakamabigat na phase: Table C1 group (j)(iv) sa New Zealand home, Appendix P Paragraph P2 sa ibang lugar. Kapag may load management, ipinapakita nito ang managed case sa tabi ng unmanaged.

Ano ang binabasa ng tool para sa Australia?

Tumuturo ang Clause 2.2.1.4 sa Appendix P, na informative. Binabanggit ng Paragraph P4.1 ang 30 mA na device na hindi bababa sa Type A para sa bawat charging point. Nagdadagdag ang Mode 3 o Mode 4 outlet ng d.c. measure: Type B, o Type A na may 6 mA d.c. detection. Kapag ang charger mismo ang nakakadetect ng d.c. fault current, Type A ang susunod.

Aling residual current device figure ang iniuulat ng tool para sa Mode 3?

Ang mga iyon ay nasa Clause 7.9.3.3 at sa Exception nito. Itinatakda ng clause ang hiwalay na Type B device sa 30 mA sa bawat live conductor, kasama ang neutral. Para sa Mode 3, ang Exception ay nagbabanggit ng Type A na may RDC-DD bilang kapalit. Ang 6 mA RDC-DD figure ay nasa NOTE, hindi sa katawan ng clause. Minamarkahan ito ng tool bilang note.

Ruling ba ito kung sumusunod ang installation ko?

Hindi. Ang mga figure ng clause ay mga gabay sa clause number. Ikinukumpara ng spare capacity check ang mga figure na tina-type mo, at galing sa cable size tool ang cable. Binabasa ng lisensiyadong electrical worker ang mga clause at nagpapasya kung paano sila nalalapat sa trabahong nasa harap niya.

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 1 Oct 2026.

Nakatulong ba ito?