AmpSize

Correction factor calculator

Basahin ang bawat correction factor at ang rating na kailangan ng cable.

Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Mga input

Worked example gamit ang mga default na input.

Standard
NZ · AS/NZS 3008.1.2
Installation method
Enclosed sa hangin
Ambient na temperatura
40 °C
Naka-group na circuit
3
Mga phase
Single phase
Design current
32 A
Cable size
6 mm²
Material
Tanso
Insulation
PVC 75 °C
Mga core
Multicore
Mga cable na parallel
1

Pinagsamang correction factor

0.62x

Kinakailangang tabulated current
51.95A
Tabulated rating na 6 mm²
38A
Itinamang rating Iz
23.41A
Ambient correction factor
×0.88
Correction factor ng grouping
×0.70

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Ambient correction factor×0.88

    AS/NZS 3008.1.2:2017 Table 27(1) p.88

  2. Correction factor ng grouping×0.70

    AS/NZS 3008.1.2:2017 Tables 22, 25(1), 25(2) p.79, p.84–85

  3. Pinagsamang correction factorResulta×0.62
  4. Kinakailangang tabulated current51.95A

    AS/NZS 3000:2018 Cl 3.4

  5. Tabulated rating ng 6 mm²38A

    AS/NZS 3008.1.2:2017 Table 13 p.62–64

  6. Naitamang rating Iz23.41A

    AS/NZS 3000:2018 Cl 3.4

Tungkol sa calculator na ito

How this is calculated

The tool reads every factor that lowers or raises the current a cable can carry on your route. It is the same code the cable size calculator runs before it tests each size.

  1. Ambient. It reads the factor for the air temperature, or the soil temperature on a buried route. AS/NZS 3008.1.2 rates New Zealand cables for 30 °C air and 15 °C soil. AS/NZS 3008.1.1 rates Australian cables for 40 °C air and 25 °C soil, so a cooler route gives a factor above 1.
  2. Grouping. It reads the factor for the circuits that share the route, by how they sit. On a tray, ladder, rack or cleats, pick the cable support. Each parallel cable set counts as a circuit.
  3. Buried cable. For a buried route it reads the soil thermal resistivity factor and the burial depth factor. Cable buried direct reads its depth factor by conductor size.
  4. Harmonics. On three phases with third harmonic current, it reads the reduction factor. Above 33 %, it sizes on the neutral current.
  5. Product. It multiplies the factors into one correction factor (derating factor in 2017). It divides the design current by that factor to give the tabulated current the cable needs.
  6. One size. It reads the tabulated rating of the size you pick and multiplies it by the factor. The result is Iz, which it checks against the design current.
StepTable or clauseWhat it decides
AmbientTables 27(1) and 27(2)The factor for the air or soil temperature
GroupingTables 22, 25(1) and 25(2)The factor for circuits run together
Cable supportTables 23 and 24The factor on a tray, ladder, rack or cleats
Buried cableTable 29, Tables 28(1) and 28(2)The factors for soil resistivity and depth
HarmonicsTable 2 and Cl 3.5.9The reduction for third harmonic current in the neutral
Required currentAS/NZS 3000 Cl 3.4The current the cable must carry in the table
Current ratingTable 13 or 14 for multicore, Tables 4, 5, 7 and 8 for single coreThe tabulated rating of the size you pick

Tables without a standard named are in the part of AS/NZS 3008.1 you pick. AS/NZS 3008.1.1:2025 numbers them by section, such as Table 3.44 for Table 27(1).

Common routes, worked with the tool

Each line states its route. Every line uses multicore copper cable with PVC insulation, except where a line names single‑core cable.

New Zealand and Australia

The Standard select picks the part of AS/NZS 3008.1 the tool reads. For Australia, the Edition select picks 2025 or the superseded 2017 edition. The 2025 edition changed several ambient and grouping factors, so run both when you check an older design.

To size the cable from these factors, use the cable size calculator. To check a cable that is already installed, use the circuit check.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Pareho ba ang correction factor at derating factor?

Oo. Tinatawag ng AS/NZS 3008.1.1:2025 ang mga ito na correction factors. Tinatawag ng 2017 parts ang mga ito na derating factors. Parehong pinaparami sa tabulated rating para makuha ang current na dala ng cable sa route mo.

Paano ko pagsasamahin ang mga factor?

I-multiply ang mga ito. Ang ambient, grouping, soil resistivity, burial depth at harmonic factor ay nalalapat bawat isa sa rating. Hatiin ang design current sa produkto para makuha ang tabulated current na kailangan ng cable.

Bakit lumalampas sa 1 ang factor ng Australian cable sa 30 °C?

Ang AS/NZS 3008.1.1 ay nagre-rate ng cable para sa 40 °C na hangin at 25 °C na lupa. Mas malamig na route, mas maraming dala ang cable. Ang AS/NZS 3008.1.2 ay nagre-rate ng New Zealand cable para sa 30 °C na hangin at 15 °C na lupa.

Binibilang ba ang mga parallel na cable bilang grouped circuits?

Oo. Ang bawat cable set ng parallel circuit ay binibilang na isang circuit sa grupo. Ang tatlong circuit na may dalawang parallel set ay bumabasa ng factor para sa anim na circuit.

Bakit magkaiba ang depth factor para sa mas malaking cable?

Para sa cable na direktang ibinaon, ang depth table ay naghahati ng factor ayon sa laki ng conductor: hanggang 50 mm², higit sa 50 hanggang 300 mm², at higit sa 300 mm². Binabasa ng tool ang band ng size na pipiliin mo.

Mga worked example

Background

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 27 Sept 2026.

Nakatulong ba ito?