Cable size calculator

Libreng cable size calculator para sa New Zealand at Australia. Binabasa nito ang AS/NZS 3008.1.2:2017, o ang AS/NZS 3008.1.1:2025 na may pagpipiliang 2017, at tinitingnan ang AS/NZS 3000.

Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

Subukan ang isang job 24

Nilalagyan ng halimbawang value ang bawat job. Palitan ang mga ito ng sarili mong value.

Mga input

Worked example gamit ang mga default na input.

Mga phase
Three phase
Voltage
400 V
Design current
50 A
Power factor
0.9
Standard
NZ · AS/NZS 3008.1.2
Haba ng run
60 m
Installation method
Enclosed sa hangin
Ambient na temperatura
30 °C
Naka-group na circuit
1
Third harmonic content
0 %
Material
Tanso
Insulation
PVC 75 °C
Mga core
Multicore
Mga cable na parallel
1
Limit ng voltage drop
5 %
Suriin ang protective device
Hindi
Prospective fault current
0 kA

Laki ng conductor

10mm²

Derated na kapasidad
50A
Voltage drop
2.66%
Earth conductor
4mm²
Kabuuang derating factor
1.00

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Ambient derating factor×1.00

    AS/NZS 3008.1.2:2017 Tables 27(1), 27(2) p.88

  2. Grouping derating factor×1.00

    One circuit, no grouping factor

  3. Soil derating factor×1.00

    AS/NZS 3008.1.2:2017 Table 29 p.90

  4. Derating factor ng lalim ng paglilibing×1.00

    AS/NZS 3008.1.2:2017 Tables 28(1), 28(2) p.89

  5. Total derating factor×1.00
  6. Kinakailangang tabulated current50A

    AS/NZS 3000:2018 Cl 3.4

  7. Napiling laki ng conductorResulta10mm²

    AS/NZS 3008.1.2:2017 Table 13 p.62–64

  8. Derated na current capacity50A

    AS/NZS 3000:2018 Cl 3.4

  9. Voltage drop2.66%

Tungkol sa calculator na ito

How this is calculated

The tool tests every standard conductor size in turn. It reports the smallest size that passes each check you ask for.

  1. Tabulated current. It reads the current each size can carry for your material, insulation, core count and installation method. The Standard select decides which part it reads. It reads AS/NZS 3008.1.2:2017 for New Zealand or AS/NZS 3008.1.1 for Australia. For Australia, the Edition select picks 2025 or the superseded 2017 edition.
  2. Correction factors. It multiplies the ambient, grouping, soil, burial depth and harmonic factors into one correction factor (derating factor in 2017). It divides the design current by that factor. Above 33 % third harmonic, it uses the neutral current instead. The result is the current the cable must carry in the table.
  3. Voltage drop. It works out the drop for the run length, the power factor and the conductor. It compares the drop with the limit you set. The default limit is 5 %.
  4. Protective device. If you name a device, its rating must sit at or below the derated capacity. The circuit's earth fault loop impedance must stay under the maximum for that device.
  5. Fault withstand. If you enter a prospective fault current, the conductor must withstand it for the clearing time. The k factor sets that limit. It depends on the material, the insulation and the conductor size.
  6. Result. The tool lists each size that fails and the check it failed. Each step names its table or clause where one applies.
StepTable or clauseWhat it decides
Current ratingTable 13 or 14 for multicore, Tables 4, 5, 7 and 8 for single coreThe current each size carries in your installation method
AmbientTables 27(1) and 27(2)The correction factor for the air or soil temperature
GroupingTables 22, 25(1) and 25(2)The correction factor for circuits run together
Buried cableTable 29, Tables 28(1) and 28(2)The correction factors for soil resistivity and depth
HarmonicsTable 2 and Cl 3.5.9The reduction for third harmonic current in the neutral
Required currentAS/NZS 3000 Cl 3.4The current the cable must carry after correction
Voltage dropTables 30, 34 and 35, Cl 4.5, AS/NZS 3000 Cl 3.6.2The drop over the run and the limit it must meet
DeviceAS/NZS 3000 Cl 2.5.3.1That the rating sits between the design current and the capacity
Earth and ZsAS/NZS 3000 Table 5.1 and Table 8.1The earth conductor size and the maximum loop impedance
Fault withstandTable 52 and Cl 5.3The k factor and the smallest size that survives the fault

Tables without a standard named are in the part of AS/NZS 3008.1 you pick. AS/NZS 3008.1.1:2025 numbers them by section, such as Table 3.18 for Table 13.

Common circuits, worked with the tool

Each line states its route. Change one input and the size can change, so run your own circuit before you buy cable. Every line uses multicore copper with PVC insulation and one circuit on the route. The power factor is 0.9, except where a line names a different value. Ze is 0.35 Ω and every size uses the New Zealand tables.

New Zealand and Australia

The Standard select picks the part of AS/NZS 3008.1 the tool reads. Part 1.2 holds the New Zealand tables. They assume 30 °C air and 15 °C soil. Part 1.1 holds the Australian tables. They assume 40 °C air and 25 °C soil. The checks from AS/NZS 3000 are the same in both countries.

For Australia, the Edition select picks AS/NZS 3008.1.1:2025 or the superseded 2017 edition. A new calculation starts on 2025. A link with no edition reads 2017, so an old link keeps its numbers.

A single‑phase circuit at 32 A runs 25 m on the 2025 Australian edition. It sits enclosed in air at 40 °C, grouped with one other circuit. It needs 10 mm² with a derated capacity of 35.2 A. Open the Australian example.

A three‑phase circuit at 30 A and 400 V runs 30 m, buried direct in soil at 25 °C. On the 2025 edition it needs 2.5 mm² with a derated capacity of 34 A. The 2017 edition gives 4 mm² with a derated capacity of 33 A. Open it on 2025 or on 2017.

Keep the result

Every input sits in the page address, so the link in your browser reproduces the calculation. The PDF button prints the result with its steps and table references. Saving a calculation to a project needs a free account.

See also: Cable size for a 32 A single‑phase 25 m run, EV charger cable size for a 7 kW 32 A circuit and Current-carrying capacity and derating.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Anong laki ng cable ang kailangan ko para sa 32 A circuit sa NZ?

10 mm² copper sa karaniwang ruta. Single‑phase ang circuit, 32 A, sa haba na 25 m. Enclosed sa hangin sa 35 °C, naka-group kasama ang isa pang circuit. Ang derated capacity nito ay 37.6 A at ang voltage drop ay 1.42 %. Iba ang sagot kapag iba ang ruta, kaya ilagay ang sarili mong inputs.

Kaya ba ng 6 mm² cable ang 40 A?

Hindi sa karaniwang ruta. Ang ruta ay may haba na 20 m sa 40 A single‑phase, enclosed in air sa 30 °C. Sa ruta na iyon, bumabagsak ang 6 mm² copper sa current capacity check. Pinipili ng tool ang 10 mm², na may 50 A ng derating capacity. Hindi nito binabago ang resulta kahit mas maikli ang run, dahil ang capacity ay nakadepende sa ruta, hindi sa haba.

Anong laki ng cable para sa 63 A three‑phase submain?

25 mm² copper sa route na ito, na may 95 A derated capacity. May run na 35 m sa 63 A, 400 V, XLPE, nakabalot sa hangin sa 35 °C. Ang device ay 63 A C curve, at ang Ze ay 0.3 Ω. Pumapasa sa current at drop checks ang 16 mm², pero ang loop impedance nitong 0.49 Ω ay bagsak sa Table 8.1.

Gumagana ba ang cable size calculator para sa Australia?

Oo. Itakda ang Standard sa AU · AS/NZS 3008.1.1. Pagkatapos, pipiliin ng Edition select ang AS/NZS 3008.1.1:2025, ang default, o ang napalitang 2017 edition. Piliin ang 2017 para maulit ang mas lumang disenyo. Parehong edition ang gumagamit ng 40 °C na hangin at 25 °C na lupa. Ang NZ · AS/NZS 3008.1.2 ang default na Standard. Ang mga check ng AS/NZS 3000, na madalas isulat bilang AS3000, ay pareho sa dalawang bansa.

Aling AS/NZS 3008 table ang ginagamit ng cable size calculator?

Sa AS/NZS 3008.1.2:2017 o 3008.1.1:2017, ang single‑core ratings ay galing sa Tables 4, 5, 7 at 8, at ang multicore ay sa 13 at 14. Ang derating ay galing sa Tables 22 at 25 hanggang 29, ang impedance ay sa Tables 30 hanggang 35, at ang k ay sa Table 52. Nire-renumber ng AS/NZS 3008.1.1:2025 ang bawat isa, kaya ang Table 13 ay 3.18. Ang AS/NZS 3000:2018 Tables 5.1 at 8.1 ang nagbibigay ng earth size at maximum Zs.

Mga worked example

Lahat ng 24 na guide para sa calculator na ito

Background

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 27 Sept 2026.