Power point location check
Power point malapit sa cooktop, gas cylinder, vent o lababo.
Reads AS/NZS 3000:2018. Tables checked 1 Oct 2026.
Subukan ang isang job 4
Nilalagyan ng halimbawang value ang bawat job. Palitan ang mga ito ng sarili mong value.
- Check a power point beside a cooktopA socket‑outlet 100 mm from the cooktop edge.
- Place a power point near a gas bottleA socket‑outlet 1.2 m from an exchange gas cylinder outdoors.
- Check a light near a gas relief ventA light 1 m ahead of a 20 mm gas relief vent.
- Place the cooktop isolating switchThe cooktop switch 600 mm from the cooktop edge.
Mga input
Worked example gamit ang mga default na input.
- Bansa
- New Zealand
- Accessory
- Socket‑outlet (power point)
- Malapit
- Cooktop (bukas na ibabaw ng pagluluto)
- Pahalang na distansya
- 300 mm
- Taas mula sa sahig o lupa
- 1,100 mm
- Taas ng cooking surface
- 900 mm
- Range hood o cabinet sa itaas
- 0 mm
- Ito ang cooktop switch
- Hindi
Ang posisyong ito
Pinapayagan
- Panuntunan
- Cl 4.7.3
- Figure
- Figure 4.17
Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.
Mga hakbang ng kalkulasyon
- Mula sa gilid ng cooking surface300mm
- Ipinagbabawal sa loob ng150mm
AS/NZS 3000:2018 Cl 4.7.3
- Ipinagbabawal mula sa900mm
AS/NZS 3000:2018 Cl 4.7.3
- Ipinagbabawal hanggang2,500mm
AS/NZS 3000:2018 Cl 4.7.3
- Taas mula sa sahig1,100mm
- Ang posisyong itoResultaPinapayagan
AS/NZS 3000:2018 Cl 4.7.3
Tungkol sa calculator na ito
How this is calculated
AS/NZS 3000 keeps socket‑outlets and switches out of a few places in a kitchen and around gas, and sets one rule near the floor. You pick the accessory, what it is near and the distances. The tool finds the rule, draws its zone and says whether the position is inside it.
Beside a cooktop, no socket‑outlet or switch may sit within 150 mm of the edge of an open gas or electric cooking surface. That band runs up from the cooking surface to the range hood, cupboard or ceiling above it, or to 2.5 m above the floor, whichever is lower. The cooktop's own switch must also be near it, in sight, not on the appliance and not reached across the cooking surface. The standard advises within 2 m, so the tool warns beyond that.
Around an outdoor gas cylinder, no ignition source may sit in the hazardous area. It is widest at the base and narrower at the top, 0.5 m above the cylinder, and an in-situ fill cylinder has a larger area than an exchange cylinder. The standard dimensions the base and the top. Between them the tool takes the edge as a straight line, as drawn, and says when a result rests on that reading. A gas relief vent has a zone ahead of it and a smaller one behind, scaled up for a vent over 50 mm. New Zealand adds an indoor cylinder compartment and the zone about a reticulated gas regulator.
Sinks, basins, baths and showers have zones of their own. The tool sends those to the wet area zones tool.
| Step | Table or clause | What it decides |
|---|---|---|
| Near the floor | Cl 4.4.2.2(b) | How a low socket‑outlet is fitted |
| Beside a cooktop | Cl 4.7.3 and Figure 4.17 | The prohibited band beside and above the cooking surface |
| The cooktop switch | Cl 4.7.1 | Where the cooktop's own switch goes |
| An outdoor gas cylinder | Cl 4.18.2.1 and Figure 4.18 | The hazardous area by cylinder type |
| An indoor cylinder | Cl 4.18.3 | No ignition source in the compartment, New Zealand |
| A gas relief vent | Cl 4.18.4 and Figure 4.19 | The exclusion zone by vent size |
| A gas regulator | Cl 4.18.5 and Figure 4.20 | The zone about the riser, New Zealand homes |
Worked examples
- A power point 100 mm from the cooktop edge. The position is Not allowed and fails: it is inside the 150 mm band, below 2.5 m.
- The cooktop switch 600 mm from the edge. The position is Allowed: outside the band, within 2 m and not reached across.
- A power point 1.2 m from a gas bottle, 300 mm up. The position is Not allowed and fails: at that height the hazardous area of an exchange cylinder reaches 1,333 mm. That figure is the straight-line reading between A and B.
- A light 1 m ahead of a gas relief vent. The position is Not allowed and fails: the zone of a 20 mm vent runs 1,500 mm along the discharge.
- A power point beside a kitchen sink. The position is Check in the wet area zones tool. Section 6 sets the zones about the sink.
Limits
The tool checks the rules named here. It does not check the hazardous area classification of Cl 7.7, equipment rated for a Zone 2 area, or the gas fitting standards. It does not set general mounting heights: AS/NZS 3000 sets none outside the rules above and Section 6. Measure on site where a result is close to a boundary.
See also: Power points near a cooktop, gas bottle and sink, Kitchen power points and the cooktop zone and Wet area zones.
Mga tanong
Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.
Gaano kalayo dapat ang power point mula sa cooktop?
Hindi puwede ang socket‑outlet o switch sa loob ng 150 mm mula sa gilid ng bukas na gas o electric cooking surface. Umaabot ang zone mula sa cooking surface paitaas hanggang sa range hood, cupboard o kisame sa itaas, o 2.5 m sa ibabaw ng floor, alinman ang mas mababa.
Gaano kalayo dapat ang power point sa gas bottle?
Sa labas ng hazardous area ng AS/NZS 3000 Figure 4.18. Para sa exchange cylinder, umaabot ito ng 1500 mm sa base at 500 mm sa itaas, 0.5 m sa ibabaw ng cylinder. Para sa in-situ fill cylinder, 3500 mm at 1500 mm.
Gaano kalayo dapat ang power point sa sink?
Itinatakda ito ng AS/NZS 3000 sa Section 6, ayon sa zones sa paligid ng lababo o basin. Gamitin ang wet area zones tool na may napiling lababo. Sakop ng tool na ito ang cooktops, gas at sahig.
Saan ilalagay ang cooktop isolating switch?
Malapit sa cooktop, nakikita at madaling maabot, pero hindi sa mismong appliance at hindi kung saan kailangang umabot ang user sa ibabaw ng cooking surface. Nagpapayo ang standard na nasa loob ng 2 m. Hindi ito puwedeng nasa prohibited zone sa tabi ng cooktop.
Puwede bang ilagay ang power point malapit sa sahig?
Oo. Kapag nasa loob ng 75 mm mula sa sahig, ikinakabit ito para pahalang na mahila palabas ang plug, maliban kung floor socket‑outlet na ginawa para doon. May sariling floor clearance ang wet rooms sa Section 6.
Mga worked example
Background
Mga clause at table na binabasa ng tool na ito
- AS/NZS 3000:2018 Cl 4.4.2.2(b)Socket‑outlets near a floor
- AS/NZS 3000:2018 Cl 4.7.1Switch for a cooktop
- AS/NZS 3000:2018 Cl 4.7.3Clearance from a cooktop
- AS/NZS 3000:2018 Cl 4.18.2.1Gas cylinders outdoors
- AS/NZS 3000:2018 Cl 4.18.3Gas cylinders indoors, New Zealand
- AS/NZS 3000:2018 Cl 4.18.4Gas relief vents
- AS/NZS 3000:2018 Cl 4.18.5Reticulated gas regulators, New Zealand
- AS/NZS 3000:2018 Cl 4.4.2.2, Cl 4.7 and Cl 4.18Where socket‑outlets, switches and other accessories may not go: floors, cooktops and gas
Bawat clause at table, kasama kung paano ito na-verify
Huling na-check ang mga table noong 1 Oct 2026.