AS/NZS 3008.1.2:2017
Table 5
Current ratings, single‑core cable, two cables per circuit, cross-linked 90 °C
The cable size tool reads the printed rating here for single‑core cross-linked cable on a single‑phase circuit, in copper or aluminium, for each installation method.
Na-verify: binasa laban sa naka-print na standard, mga pahina 38–40. Na-check noong 24 Sept 2026.
Mga unit: Rating A
Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.
20 na row
| Size | Cu spaced apart | Cu spaced from surface | Cu touching | Cu sun | Cu enclosed air | Cu insulation partial | Cu insulation complete | Cu buried direct | Cu underground one enclosure | Cu underground separate enclosures | Al spaced apart | Al spaced from surface | Al touching | Al sun | Al enclosed air | Al insulation partial | Al insulation complete | Al buried direct | Al underground one enclosure | Al underground separate enclosures |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 22 | 22 | 18 | 13 | 18 | 14 | 9 | 21 | 21 | 26 | — | — | — | — | — | — | — | — | — | — |
| 1.5 | 29 | 28 | 22 | 17 | 23 | 18 | 11 | 28 | 28 | 32 | — | — | — | — | — | — | — | — | — | — |
| 2.5 | 40 | 40 | 31 | 23 | 33 | 26 | 15 | 39 | 39 | 44 | — | — | — | — | — | — | — | — | — | — |
| 4 | 53 | 52 | 41 | 31 | 42 | 33 | 21 | 49 | 49 | 57 | — | — | — | — | — | — | — | — | — | — |
| 6 | 67 | 66 | 52 | 40 | 52 | 42 | 26 | 62 | 62 | 71 | — | — | — | — | — | — | — | — | — | — |
| 10 | 92 | 90 | 72 | 53 | 72 | 57 | 35 | 83 | 83 | 93 | — | — | — | — | — | — | — | — | — | — |
| 16 | 123 | 119 | 95 | 70 | 92 | 74 | 47 | 149 | 107 | 120 | 96 | 92 | 74 | 55 | 72 | 57 | 36 | 114 | 83 | 93 |
| 25 | 166 | 160 | 129 | 95 | 124 | 99 | 64 | 192 | 140 | 156 | 129 | 123 | 100 | 73 | 96 | 77 | 50 | 149 | 109 | 122 |
| 35 | 205 | 195 | 158 | 116 | 149 | 119 | 79 | 230 | 168 | 187 | 158 | 151 | 122 | 89 | 116 | 92 | 62 | 179 | 131 | 146 |
| 50 | 251 | 238 | 194 | 140 | 183 | 146 | — | 273 | 202 | 226 | 195 | 184 | 150 | 109 | 142 | 113 | — | 212 | 157 | 175 |
| 70 | 320 | 300 | 246 | 176 | 224 | 180 | — | 335 | 249 | 276 | 249 | 233 | 191 | 136 | 175 | 140 | — | 260 | 194 | 214 |
| 95 | 397 | 372 | 306 | 217 | 281 | 224 | — | 401 | 305 | 331 | 308 | 288 | 238 | 168 | 218 | 174 | — | 311 | 236 | 256 |
| 120 | 464 | 432 | 358 | 252 | 321 | 256 | — | 457 | 348 | 383 | 361 | 336 | 278 | 196 | 249 | 199 | — | 355 | 270 | 297 |
| 150 | 535 | 496 | 413 | 288 | 362 | 289 | — | 514 | 391 | 429 | 415 | 385 | 320 | 224 | 281 | 224 | — | 398 | 303 | 333 |
| 185 | 622 | 574 | 480 | 333 | 426 | 340 | — | 581 | 453 | 495 | 483 | 447 | 374 | 260 | 331 | 265 | — | 453 | 352 | 384 |
| 240 | 746 | 684 | 574 | 395 | 507 | 406 | — | 674 | 532 | 574 | 580 | 534 | 449 | 308 | 396 | 317 | — | 526 | 415 | 446 |
| 300 | 866 | 790 | 666 | 454 | — | — | — | 761 | 601 | 663 | 673 | 618 | 520 | 355 | — | — | — | 595 | 471 | 516 |
| 400 | 1015 | 920 | 779 | 526 | — | — | — | 865 | 699 | 755 | 795 | 726 | 615 | 415 | — | — | — | 683 | 552 | 592 |
| 500 | 1186 | 1063 | 903 | 605 | — | — | — | 977 | 791 | 856 | 935 | 849 | 722 | 483 | — | — | — | 780 | 631 | 676 |
| 630 | 1387 | 1224 | 1045 | 692 | — | — | — | 1098 | 916 | 995 | 1103 | 994 | 849 | 562 | — | — | — | 891 | 744 | 792 |
Mga tool na bumabasa nito (2)
Mga guide at learn page na nagbabanggit nito (9)
- Hot water cylinder cable size for a 3 kW element
- Cable size for a 20 A heat pump circuit in summer
- AmpSize vs jCalc vs free cable sizing tools
- EV charger cable size for a 7 kW 32 A circuit
- AS/NZS 3008.1.2 Tables 4 to 21: current ratings
- AS/NZS 3008 vs BS 7671: cable sizing compared
- Motor full load current: 11 kW 400 V DOL
- Cable size for a 32 A single‑phase 25 m run
- Current-carrying capacity and derating