AS/NZS 3000:2018
Appendix P, Paragraphs P2 to P4
Electric vehicle charging circuits, guidance
The EV charger tool reads Appendix P for Australia: the demand of each charging point and the residual current device. Appendix P is informative, so the tool reports guidance.
Na-verify: binasa laban sa naka-print na standard, mga pahina 77, 570–571 (PDF 81, 574–575). Na-check noong 1 Oct 2026.
Mga unit: Demand percent %, Simultaneous percent %, Rcd milliamps mA, Dc detect milliamps mA
Ito ang mga value na ine-encode ng AmpSize. Walang text ng standard na inilalathala. I-verify laban sa kasalukuyang standard.
7 na row
| Clause | Demand percent (%) | Simultaneous percent (%) | Rcd type | Rcd milliamps (mA) | Dc detect milliamps (mA) | Own device | All live | Station exempt | Ip |
|---|---|---|---|---|---|---|---|---|---|
| P2 | 100 | 100 | — | — | — | — | — | — | — |
| P3.1 | — | — | — | — | — | yes | — | — | — |
| P3.2.1 | — | — | — | — | — | — | — | — | IPX4 |
| P3.2.2 | — | — | — | — | — | — | — | — | IP4X |
| P4.1 | — | — | A | 30 | — | yes | yes | — | — |
| P4.1 | — | — | B | — | 6 | yes | yes | yes | — |
| P4.2 | — | — | — | — | — | yes | — | — | — |