حاسبة سلسلة PV
الوحدات في كل سلسلة وتيار السلسلة ومفتاح العزل لـ PV.
Reads AS/NZS 5033:2021 and AS/NZS 4777.2:2020. Tables checked 2 Oct 2026.
جرّب مشروعاً 8
تملأ كل مهمة قيماً توضيحية. استبدلها بقيمك.
- Size solar strings for a 600 V inverterThe modules per string for 49.5 V modules on a 600 V inverter at −5 °C.
- Check string fuses on three parallel stringsWhether three parallel strings of 13.9 A modules call for string fuses, and their rating.
- Size strings for a 1000 V inverterThe modules per string for a commercial inverter.
- Size strings for a cold inland siteThe modules per string at a record low of −8 °C, on a 600 V inverter.
- Check a string on a hot roofWhether the hot voltage stays above the tracker's minimum.
- Check two strings need no fuseWhether two strings in parallel need string fuses.
- Check the array current at the inverterThe array's short-circuit current against the inverter input.
- Size strings for a house trackerThe modules per string for a 450 V window.
المدخلات
مثال محلول بالمدخلات الافتراضية.
- Voc للوحدة
- 49.5 V
- Vmp للوحدة
- 41.5 V
- Isc للوحدة
- 13.9 A
- معامل حرارة Voc
- −0.27 %/K
- معامل حرارة Vmp
- −0.35 %/K
- أقصى صمام توالي للوحدة
- 25 A
- تصحيح الجهد للظروف الباردة
- معامل الشركة المصنعة، Cl 4.2.1.2(a)
- أدنى درجة حرارة مسجلة
- −5 °C
- أعلى درجة حرارة مسجلة
- 35 °C
- ارتفاع درجة الخلية فوق المحيط
- 35 K
- التركيب
- منزلي، حد 1000 V
- وحدات لكل سلسلة
- 10
- السلاسل المتوازية
- 2
- KI، معامل ثنائي الوجه
- 1
- تيار الإرجاع من العاكس
- 0 A
- تقنين فيوز السلسلة
- 0 A
- الحد الأقصى لجهد التيار المستمر للعاكس
- 600 V
- الحد الأدنى لجهد MPPT
- 150 V
- الحد الأقصى لجهد MPPT
- 550 V
- عاكس Isc PV
- 0 A
وحدات لكل سلسلة
من 5 إلى 11
- أقصى جهد للسلسلة
- 535.1V
- Vmp للسلسلة عند أسخن خلية
- 349.6V
- أقصى تيار للسلسلة
- 17.38A
- تيار المصفوفة إلى العاكس
- 34.75A
- فاصل تيار مستمر d.c.، على الأقل
- 34.75 A عند 535.1 V
- مصاهر السلاسل
- Not called for
هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
خطوات الحساب
- تصحيح Voc، 1 + المعامل × (Tmin − 25 °C)×1.08
AS/NZS 5033:2021 Cl 4.2.1.2
- أقصى جهد للوحدة عند أبرد خلية53.51V
AS/NZS 5033:2021 Cl 4.2.1.2
- الحد لتركيب منزلي1,000V
AS/NZS 5033:2021 Cl 3.1
- أكبر عدد من الوحدات لكل سلسلة11
AS/NZS 5033:2021 Cl 4.2.1.3.1
- أسخن خلية، أعلى قيمة مسجلة مضافاً إليها الارتفاع70°C
- Module Vmp عند أسخن خلية34.96V
- أقل عدد من الوحدات لكل سلسلة للحد الأدنى لـ MPPT5
- الجهد الأقصى للسلسلة535.1V
AS/NZS 5033:2021 Cl 4.2.1.3.1
- Vmp للسلسلة عند أسخن خلية349.6V
- Vmp للسلسلة عند أبرد خلية458.6V
- أقصى تيار للسلسلة، 1.25 × KI × Isc17.38A
AS/NZS 5033:2021 Cl 3.3.3.1
- تيار العطل من السلاسل الأخرى، (SA − 1) × ISTRING MAX17.38A
AS/NZS 5033:2021 Cl 3.3.3.2
- نافذة مصهر السلسلة، أعلى من 1.2 × ISTRING MAX وبحد أقصى تصنيف الوحدةمن 20.85 إلى 25A
AS/NZS 5033:2021 Table 3.1
- تيار كابل السلسلة17.38A
AS/NZS 5033:2021 Table 4.2
- تيار كابل المصفوفة إلى العاكس34.75A
AS/NZS 5033:2021 Table 4.2
- تصنيف تيار المفتاح العازل المستمر، على الأقل34.75A
AS/NZS 5033:2021 Table 4.3
- تصنيف جهد المفتاح العازل المستمر، على الأقل535.1V
AS/NZS 5033:2021 Table 4.3
- أصغر موصل4mm²
AS/NZS 5033:2021 Cl 4.4.2.3
- درجة حرارة الكابل بالقرب من الوحدات، أعلى قيمة مسجلة زائد 40 K75°C
AS/NZS 5033:2021 Cl 4.4.2.2
حول هذه الحاسبة
How this is calculated
The tool sizes a PV string. It finds how many modules fit in a string, the string current, the fuses and the d.c. isolator. It reads AS/NZS 5033:2021. It reads the inverter limits from the plate you enter.
- Cold voltage. The tool corrects the module Voc for the coldest cell (Cl 4.2.1.2). The factor is 1 + coefficient × (Tmin − 25 °C). Tmin is the record low.
- Most modules. It divides the voltage limit by the corrected Voc. The limit is the lower of the inverter maximum and the domestic limit in Cl 3.1 (Cl 4.2.1.3.1).
- Fewest modules. It finds the hot cell as the record high plus the cell rise you enter. It then finds the fewest modules that keep Vmp above the MPPT minimum.
- String current. It works 1.25 × KI × Isc (Cl 3.3.3.1). It adds the fault current from the other strings (Cl 3.3.3.2).
- Fuses. A fuse window sits above 1.2 times the string current and at most the module rating (Table 3.1).
- Cable and isolator. It gives the cable currents (Table 4.2), the isolator ratings (Table 4.3) and the smallest conductor (Cl 4.4.2.3).
| Step | Table or clause | What it decides |
|---|---|---|
| Cold voltage | Cl 4.2.1.2 | The module voltage at the coldest cell |
| String length | Cl 4.2.1.3.1 | The most modules in a string |
| String current | Cl 3.3.3.1 and Cl 3.3.3.2 | The current for cable and fuse |
| Fuse window | Table 3.1 | The fuse range |
| Isolator | Table 4.3 | The current and voltage ratings |
Worked example
- 10 modules of 49.5 V Voc, 2 strings, 600 V inverter. The tool gives 5 to 11 modules per string. The string maximum voltage is 535.1 V. The string current is 17.38 A and the array current is 34.75 A. No string fuses are called for.
Limits
- The tool derives the AS/NZS 5033 figures from the text until the Standard is checked. It says so in a warning.
- AS/NZS 5033 sets no cell rise. The tool uses the rise you enter.
- The inverter limits are the ones on its plate. Read them from the data sheet.
- The tool does not size the cable. Use the DC cable size calculator at these currents and at the hot cable temperature.
- Above 120 V, hold the voltage drop from the furthest module to the inverter to 5 % of Vmp.
See also: PV string voltage and temperature, Solar string sizing for a 600 V inverter and PV and inverter basics.
الأسئلة
النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
كيف تجد الأداة أكبر عدد من الوحدات لكل سلسلة؟
تصحّح الأداة Voc للوحدة إلى أدنى درجة حرارة مسجّلة، باستخدام معامل الصانع أو AS/NZS 5033 Table 4.1. تقسم الأدنى من الحد الأقصى للعاكس وحد 1000 V أو 1500 V على ذلك الجهد، وتقرّب إلى الأسفل.
كيف تجد الأداة أقل عدد من الوحدات لكل سلسلة؟
تحسب الأداة Vmp للوحدة عند أسخن خلية: أعلى درجة حرارة مسجّلة مضافاً إليها ارتفاع الخلية الذي تدخله. تقسم الحد الأدنى لـ MPPT على ذلك الجهد وتقرّب إلى أعلى. لا يحدد AS/NZS 5033 ارتفاعاً للخلية، لذلك فإن القيمة الافتراضية 35 K هي افتراض AmpSize.
متى تحتاج السلسلة إلى مصهر؟
عندما تعمل السلاسل على التوازي، يمكن للسلاسل الأخرى أن تغذي عطلًا في سلسلة واحدة. تضيف الأداة ذلك التيار إلى التغذية العكسية وتقارنه بأقصى مصهر على التوالي للوحدة. وعندما يكون أعلى، يكون المصهر فوق 1.2 مرة من أقصى تيار للسلسلة وعند القيمة الاسمية للوحدة أو أقل منها.
هل تم التحقق من أرقام AS/NZS 5033؟
نعم. قُرئ Table 4.1 والجهد والتيار وحدود الكابل مقابل الصفحات المطبوعة من AS/NZS 5033:2021. تحقّق من كل رقم مقابل المعيار الحالي قبل أن تعتمد عليه.
أمثلة محلولة
- DC isolator rating for a 10 kW solar arrayRate the d.c. isolator and size the frame earth for a four-string domestic array. Check one data sheet that passes and one that fails per pole.
- Solar string sizing for a 600 V inverterHow many 49.5 V modules fit a string on a 600 V inverter at −5 °C? Work cold Voc, hot Vmp, the string current, fuses and the d.c. isolator by AS/NZS 5033.
الخلفية
- PV array isolators and earthingHow parallel strings feed a fault, what Ithe, Ie and make and break mean for a d.c. isolator, and how AS/NZS 5033 earths and alarms a PV array.
- PV string voltage and temperatureWhy a PV string's voltage rises in the cold and falls in the heat, how AS/NZS 5033 limits it, and how the string current, fuses and isolator follow.
البنود والجداول التي تقرأها هذه الأداة
- AS/NZS 5033:2021 Cl 3.1Maximum voltage of PV d.c. circuits
- AS/NZS 5033:2021 Cl 3.3.3.1Maximum string current
- AS/NZS 5033:2021 Cl 3.3.3.2Fault current from parallel strings
- AS/NZS 5033:2021 Cl 3.3.4.1When strings take overcurrent protection
- AS/NZS 5033:2021 Cl 4.2.1.2PV module maximum voltage
- AS/NZS 5033:2021 Cl 4.2.1.3.1String voltage limit
- AS/NZS 5033:2021 Cl 4.4.2.2PV cable temperature
- AS/NZS 5033:2021 Cl 4.4.2.3Smallest PV conductor
كل البنود والجداول، مع طريقة التحقق من كل منها
آخر فحص للجداول في 2 Oct 2026.