Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.
جرّب مشروعاً 7
تملأ كل مهمة قيماً توضيحية. استبدلها بقيمك.
- Find the correction factors in a hot ceilingThe factor for four circuits in a 50 °C ceiling space, and the rating the cable needs.
- Find the correction factors for a buried cableThe soil, depth and grouping factors for two buried three‑phase circuits.
- Find the factor for nine circuitsThe grouping factor for nine circuits on a tray.
- Find the factor on a 50 °C roofThe ambient factor at 50 °C.
- Find the factors in poor soilThe soil and depth factors at 2.5 K·m/W and 1 m.
- Find the factor for a harmonic loadThe factor for 40 % third harmonic in a four‑core cable.
- Compare the factors in AustraliaThe factors for 45 °C and four grouped circuits on the Australian tables.
المدخلات
مثال محلول بالمدخلات الافتراضية.
- المعيار
- NZ · AS/NZS 3008.1.2
- طريقة التركيب
- داخل حاوية في الهواء
- درجة الحرارة المحيطة
- 40 °C
- الدوائر المجمّعة
- 3
- الأطوار
- طور واحد
- تيار التصميم
- 32 A
- مقاس الكابل
- 6 mm²
- المادة
- النحاس
- العزل
- PVC 75 °C
- الأسلاك الداخلية
- متعدد القلوب
- الكابلات المتوازية
- 1
معامل التصحيح المجمّع
0.62x
- التيار الجدولي المطلوب
- 51.95A
- السعة المجدولة لـ 6 mm²
- 38A
- التصنيف المصحح Iz
- 23.41A
- معامل تصحيح المحيط
- ×0.88
- معامل تصحيح التجميع
- ×0.70
هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
خطوات الحساب
- معامل تصحيح المحيط×0.88
AS/NZS 3008.1.2:2017 Table 27(1) p.88
- معامل تصحيح التجميع×0.70
AS/NZS 3008.1.2:2017 Tables 22, 25(1), 25(2) p.79, p.84–85
- معامل التصحيح المجمّعالنتيجة×0.62
- التيار الجدولي المطلوب51.95A
AS/NZS 3000:2018 Cl 3.4
- التقنين الجدولي لـ 6 mm²38A
AS/NZS 3008.1.2:2017 Table 13 p.62–64
- التصنيف المصحح Iz23.41A
AS/NZS 3000:2018 Cl 3.4
حول هذه الحاسبة
How this is calculated
The tool reads every factor that lowers or raises the current a cable can carry on your route. It is the same code the cable size calculator runs before it tests each size.
- Ambient. It reads the factor for the air temperature, or the soil temperature on a buried route. AS/NZS 3008.1.2 rates New Zealand cables for 30 °C air and 15 °C soil. AS/NZS 3008.1.1 rates Australian cables for 40 °C air and 25 °C soil, so a cooler route gives a factor above 1.
- Grouping. It reads the factor for the circuits that share the route, by how they sit. On a tray, ladder, rack or cleats, pick the cable support. Each parallel cable set counts as a circuit.
- Buried cable. For a buried route it reads the soil thermal resistivity factor and the burial depth factor. Cable buried direct reads its depth factor by conductor size.
- Harmonics. On three phases with third harmonic current, it reads the reduction factor. Above 33 %, it sizes on the neutral current.
- Product. It multiplies the factors into one correction factor (derating factor in 2017). It divides the design current by that factor to give the tabulated current the cable needs.
- One size. It reads the tabulated rating of the size you pick and multiplies it by the factor. The result is Iz, which it checks against the design current.
| Step | Table or clause | What it decides |
|---|---|---|
| Ambient | Tables 27(1) and 27(2) | The factor for the air or soil temperature |
| Grouping | Tables 22, 25(1) and 25(2) | The factor for circuits run together |
| Cable support | Tables 23 and 24 | The factor on a tray, ladder, rack or cleats |
| Buried cable | Table 29, Tables 28(1) and 28(2) | The factors for soil resistivity and depth |
| Harmonics | Table 2 and Cl 3.5.9 | The reduction for third harmonic current in the neutral |
| Required current | AS/NZS 3000 Cl 3.4 | The current the cable must carry in the table |
| Current rating | Table 13 or 14 for multicore, Tables 4, 5, 7 and 8 for single core | The tabulated rating of the size you pick |
Tables without a standard named are in the part of AS/NZS 3008.1 you pick. AS/NZS 3008.1.1:2025 numbers them by section, such as Table 3.44 for Table 27(1).
Common routes, worked with the tool
Each line states its route. Every line uses multicore copper cable with PVC insulation, except where a line names single‑core cable.
- Three circuits enclosed in 40 °C air, 32 A on 6 mm². The factors multiply to 0.62 x. The cable needs a tabulated 51.95 A, and 6 mm² carries only 23.41 A on this route.
- The same route on 16 mm². The factors still multiply to 0.62 x, and the cable needs a tabulated 51.95 A. 16 mm² carries 40.66 A, above the 32 A design current.
- Buried direct in Australia, 100 A on 35 mm² single‑core. Soil at 20 °C with a resistivity of 2 K·m/W, 1 m deep. The factors multiply to 0.8 x, and the cable needs a tabulated 125.31 A.
- Four three‑phase circuits touching, 80 A with 40 % third harmonic on 50 mm². The neutral carries 96 A, so the tool sizes on it. The factors multiply to 0.56 x, and the cable needs a tabulated 171.74 A.
New Zealand and Australia
The Standard select picks the part of AS/NZS 3008.1 the tool reads. For Australia, the Edition select picks 2025 or the superseded 2017 edition. The 2025 edition changed several ambient and grouping factors, so run both when you check an older design.
To size the cable from these factors, use the cable size calculator. To check a cable that is already installed, use the circuit check.
الأسئلة
النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
هل معامل التصحيح هو نفسه معامل التخفيض؟
نعم. يسمّيها AS/NZS 3008.1.1:2025 معاملات التصحيح، وتسمّيها أجزاء 2017 معاملات التخفيض. وكلاهما يضرب القيمة الجدولية لإعطاء التيار الذي يحمله الكابل على مسارك.
كيف أجمع المعاملات؟
اضربها معًا. تنطبق درجة الحرارة المحيطة والتجميع ومقاومة التربة النوعية وعمق الدفن وعامل التوافقيات كلٌّ على القيمة الاسمية. اقسم تيار التصميم على الناتج للحصول على التيار الجدولي الذي يحتاجه الكابل.
لماذا يحصل كابل أسترالي عند 30 °C على معامل أكبر من 1؟
تحدد AS/NZS 3008.1.1 قيم الكابلات عند هواء 40 °C وتربة 25 °C. يسمح المسار الأبرد للكابل بحمل تيار أكبر. تحدد AS/NZS 3008.1.2 قيم كابلات نيوزيلندا عند هواء 30 °C وتربة 15 °C.
هل تُحتسب الكابلات المتوازية كدوائر متجمعة؟
نعم. تُحسب كل مجموعة كابلات في دائرة متوازية كدائرة واحدة في المجموعة. وثلاث دوائر من مجموعتين متوازيتين تقرأ معامل الدوائر الست.
لماذا يختلف معامل العمق لكابل أكبر؟
بالنسبة للكابل المدفون مباشرة، يصنّف جدول العمق المعامل حسب مقاس الموصل: حتى 50 mm²، وفوق 50 حتى 300 mm²، وفوق 300 mm². تقرأ الأداة نطاق المقاس الذي تختاره.
أمثلة محلولة
- Cable tray fill for a plant room: a second tierLay ten multicore cables on a 300 mm perforated tray in one layer, see when it takes a second tier, and carry the grouping factor into the cable size.
- Downlights in an insulated ceilingRe-insulate a NZ ceiling with downlights in it. Check which may be covered, which only abutted, which must come out, and the clearances and roof space sign.
- Three circuits in a hot ceiling: correction factorThree 32 A circuits in conduit across a 40 °C and a 50 °C ceiling space, worked with the NZ 2017 tables and again with AS/NZS 3008.1.1:2025.
الخلفية
- Downlights and insulation: IC-4, CA90 and Non‑ICThe six recessed luminaire classes, what insulation may do around each, which a NZ or AU home may have, the default clearances, and the roof space warning sign.
- Cable tray fill: one layer, tiers and groupingHow cables lie on a tray or ladder for AS/NZS 3008.1, touching or spaced, when a run needs another tier, and why there is no fill percentage to work to.
- Correction factors in the 2017 and 2025 editionsWhat each AS/NZS 3008 correction factor does, how the factors multiply, and which values changed when AS/NZS 3008.1.1:2025 replaced the 2017 tables.
البنود والجداول التي تقرأها هذه الأداة
- AS/NZS 3000:2018 Cl 3.4Current-carrying capacity
- AS/NZS 3008.1.2:2017 Cl 3.5.9Third harmonic current in the neutral
- AS/NZS 3008.1.2:2017 Table 2Reduction factors for harmonic currents in 4- and 5‑core cables
- AS/NZS 3008.1.2:2017 Table 13Current ratings, multicore cable with three or four cores, thermoplastic 75 °C
- AS/NZS 3008.1.2:2017 Table 22, 25(1), 25(2)Grouping factors for bunched circuits, buried circuits and underground wiring enclosures
- AS/NZS 3008.1.2:2017 Table 23Grouping factors for single‑core circuits on trays, ladder supports, racks and cleats in air
- AS/NZS 3008.1.2:2017 Table 24Grouping factors for multicore cables on trays, ladder supports, racks and cleats in air
- AS/NZS 3008.1.2:2017 Table 27(1), 27(2)Rating factors for air and soil ambient temperature
كل البنود والجداول، مع طريقة التحقق من كل منها
آخر فحص للجداول في 27 Sept 2026.
أدوات ذات صلة
- حاسبة مقاس الكابلFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- حاسبة هبوط الجهدCalculate voltage drop on a cable run and check the limit.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- امتلاء حامل الكابلات والسلّمTray or ladder width, tiers, kg/m and the grouping factor.AS/NZS 3008.1
هل كان هذا مفيداً؟
سؤال، أو قيمة تبدو خاطئة؟ اتصل بنا.