Electricity (Safety) Regulations 2010
reg 24
Rated residual current and trip time limits for RCDs
The RCD selection tool reads the maximum rated residual current and the two trip time limits for the protection duty of the device. A measured trip time is compared with those limits.
تم التحقق: مقروء مقابل المعيار المطبوع، الصفحات 36–37. تم التحقق في 26 Sept 2026.
الوحدات: Max rated ma mA, Trip at rated ms ms, Trip at five ms ms, No trip at fraction x
هذه هي القيم التي ترمّزها AmpSize. لا يُعاد إنتاج أي نص من المعيار. تحقق من المعيار الحالي.
العودة إلى بطاقته في صفحة Electricity (Safety) Regulations 2010
4 صفوف
| Duty | Max rated ma (mA) | Trip at rated ms | Trip at five ms | No trip at fraction (x) |
|---|---|---|---|---|
| shock | 30 | 300 | 40 | 0.5 |
| property | 300 | 500 | 150 | — |
| patient | 10 | 40 | 40 | 0.45 |
| children | 10 | 300 | 40 | 0.5 |