Lumaktaw sa nilalaman
AmpSize

Cable tray at ladder fill

Lapad ng tray o ladder, mga tier, kg/m at ang grouping factor.

AS/NZS 3008.1

Reads AS/NZS 3000:2018, Nexans Olex The Handbook:2017, AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3008.1.1:2017 (AU). Tables checked 1 Oct 2026.

Mga input

Worked example gamit ang mga default na input.

Standard
AS/NZS 3008.1.2 (New Zealand)
Suporta
Perforated tray
Lapad sa loob
300 mm
Lapad na iniiwang bakante
25 %
Mga cable
Multicore (tatlong core at earth)
Espasyo
Magkadikit
Mga cable sa tray
2 row

Kinakailangang baitang

1

Lapad na nasasakupan ng mga cable
125.3mm
Punô ng pinakapunong baitang
41.8%
Cable mass sa pinakamabigat na tier
4.31kg/m
Grouping factor na dadalhin sa laki ng cable
0.73

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. 4 × 16 mm² multicore, tig-19.7 mm78.8mm
  2. 3 × 6 mm² multicore, tig-15.5 mm46.5mm
  3. Lapad na nasasakupan ng mga cable125.3mm
  4. Magagamit na lapad pagkatapos ng 25 % reserve225mm
  5. Kinakailangang baitangResulta1

    AS/NZS 3008.1.2:2017 Table 24 Note 5

  6. Hanay 1: 7 cable, 125.3 mm4.31kg/m

    Olex Handbook

  7. Punô ng pinakapunong baitang41.8%
  8. Grouping factor na dadalhin sa laki ng cable×0.73

    AS/NZS 3008.1.2:2017 Table 24 p.82

Tungkol sa calculator na ito

How this is calculated

A cable tray or ladder holds cables side by side. AS/NZS 3008.1 rates cables on trays and ladders with grouping factors that hold for one layer of cables on each tier. So the question for a tray is how wide the cables are, laid in one layer, and how many tiers that takes. This tool lays them out and reads the factor.

You pick the cable family and list the sizes and counts. The overall diameters are the cable maker's figures that the conduit fill tool also uses. A multicore cable takes one diameter of width. A single‑core three‑phase circuit takes two diameters in trefoil and three laid flat. Touching cables sit side by side. Spaced cables have one diameter between them, as Tables 23 and 24 draw, and where sizes differ the tool uses the largest.

The standard sets no fill percentage for a tray, so the width kept free for later cables is yours to choose. The tool places each cable or circuit, in the order you list them, on the first tier with room. A run that does not fit one tier takes another, and stacked tiers are at least 300 mm apart for the factors to hold.

It then reads the grouping factor for the support, the spacing, the tiers used and the most cables or circuits on one tier. A count between two printed columns reads the next column up. Past the printed counts no factor is given. The mass per metre on each tier is the maker's catalogue figure.

StepTable or clauseWhat it decides
Cable diametersOlex and Prysmian catalogue diametersThe width each cable or circuit takes
SpacingAS/NZS 3008.1 Tables 23 and 24 Note 1One diameter between spaced cables or circuits
One layer per tierAS/NZS 3008.1 Tables 23 and 24 Note 5The tiers the run needs
Tier spacingAS/NZS 3008.1 Tables 23 and 24 Note 6The gap between stacked tiers
Grouping factorAS/NZS 3008.1 Table 23 or Table 24The factor to carry to the cable size
MassOlex Handbook mass per metreThe kg/m on each tier

Worked examples

Limits

The tool lays one cable family at a time: multicore three core and earth cables, or single‑core three‑phase circuits. It does not mix the two, model cables in more than one layer, or check segregation between services on the same tray. Use the segregation tool for that.

Single‑core widths use the diameter of unsheathed V‑90 single cores, the conduit fill figures. A sheathed or XLPE single core is wider, so allow for it. The mass is the cable alone. Check the tray or ladder against its maker's load and span tables, with the fixings and any future cables.

See also: Cable size, Correction factors and Conduit fill.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

May maximum fill ba para sa cable tray?

Walang fill percentage na itinakda ang AS/NZS 3008.1 para sa tray o ladder. Ang grouping factors nito ay ipinapalagay na isang layer ng cable sa bawat tier. Isang layer ang inilalatag ng tool at pinananatili ang reserve na pipiliin mo para sa mga susunod na cable.

Ano ang ibig sabihin ng spaced sa tray?

Ang cable na may espasyo ay may isang diameter ng cable ang pagitan, gaya ng ipinapakita ng AS/NZS 3008.1 Tables 23 at 24. Kapag magkakaiba ang laki, ginagamit ng tool ang pinakamalaking diameter. Pinapataas ng espasyo ang grouping factor at mas maraming lapad ang kinukuha.

Gaano kalawak ang trefoil circuit?

Ang tatlong single‑core cable na nasa trefoil ay umuukupa ng dalawang diameter ang lapad sa tray. Kapag nakahiga nang patag, tatlong diameter ang kukunin nila. Ginagamit ng tool ang overall diameter mula sa catalogue ng cable maker.

Anong grouping factor ang ginagamit ko para sa cable size?

Binabasa ng tool ang AS/NZS 3008.1 Table 23 para sa single‑core circuit o Table 24 para sa multicore cable, sa mga tier na ginamit nito at sa pinakamaraming cable sa isang tier. Dalhin ang factor na iyon sa cable size tool.

Tinitingnan ba nito kung kayang dalhin ng tray ang bigat?

Hindi. Ibinibigay nito ang kg/m ng cable sa bawat tier mula sa catalogue ng maker. Tingnan iyon laban sa load at span table ng tray maker.

Mga worked example

Background

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 1 Oct 2026.

Nakatulong ba ito?

May tanong, o may value na mukhang mali? Makipag-ugnayan sa amin.