Transformer size mula sa demand

I-size ang transformer mula sa demand, kasama ang paglaki at losses.

Walang standard

Mga input

Worked example gamit ang mga default na input.

Maximum demand
220
Demand sa
kVA
Power factor
0.9
Allowance para sa paglaki
20 %
Karamihan ng loading sa design load
100 %
Mga phase
Three phase
Primary voltage
11,000 V
Secondary voltage
400 V
Impedance
4.5 %
X/R ratio
4
No-load loss, ng rating
0.2 %
Load loss sa full load, ng rating
1.1 %

Laki ng transformer

300kVA

Design load na may paglago
264kVA
Loading sa kasalukuyan
73.3%
Loading na may paglago
88%
Voltage regulation na may paglago
2.59%
Mga pagkawala na may paglago
3.16kW
Secondary full load current
433.01A
Secondary fault current
9,622.5A

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Design load na may 20 % na paglaki264kVA
  2. Pinakamaliit na karaniwang laki sa 100 % na loading300 kVA
  3. Loading sa kasalukuyan73.3%
  4. Loading na may paglago88%
  5. Resistance, ng rating1.09%
  6. Reactance, ng rating4.37%
  7. Voltage regulation na may paglago2.59%
  8. Secondary voltage sa design load389.7V
  9. Mga pagkawala na may paglago3.16kW
  10. Efficiency kasama ang paglaki98.69%
  11. Secondary full load current433.01A
  12. Secondary fault current9,622.5A

Tungkol sa calculator na ito

How this is calculated

A transformer is sized from the maximum demand it will carry, with room for the load to grow. Too small and it runs hot and drops too much voltage; too large and it costs more and wastes energy in its core every hour of the year. This tool finds the size and shows what it does at the load.

You enter the maximum demand, in kVA or in kW with a power factor, and a growth allowance. The design load is the demand plus that growth. The tool picks the smallest rating from a list of typical sizes that carries the design load within the loading limit you set. The list is common distribution and site ratings, not a standard's list.

At that size it works the loading today and with growth, then the voltage regulation: the drop through the transformer's own resistance and reactance at the design load and power factor. The impedance on the rating plate splits into the two by the X/R ratio. The losses are the core loss, which is there whenever the transformer is energised, plus the winding loss, which rises with the square of the loading. The full load and fault currents at the size come from the transformer tool.

The impedance, X/R ratio and losses are maker's data. The defaults are typical figures, and the result names them as assumptions.

StepTable or clauseWhat it decides
Design loadDemand plus the growth allowanceThe load the size must carry
SizeSmallest typical rating within the loading limitThe transformer rating
Resistance and reactanceImpedance split by the X/R ratioThe two parts of the drop
Voltage regulationLoading times the drop at the power factorThe voltage lost through the transformer
LossesCore loss plus winding loss times loading squaredThe heat and the running cost
CurrentsThe transformer toolThe full load and fault current at the size

Worked examples

Limits

The regulation is the drop through the transformer alone. The network upstream and the cables downstream add their own drop; the total voltage drop tool adds the cable parts. A tap changer or off-load taps can raise the secondary voltage to make up for it.

The tool does not cover transformers in parallel, harmonic loads, the temperature rise of the windings or the network company's own sizing rules for a supply transformer.

See also: Transformer, Maximum demand and Fault level at a board.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Paano ko i-size ang transformer?

Magsimula sa maximum demand, magdagdag ng allowance para sa paglaki ng load, at piliin ang pinakamaliit na standard rating na kayang dalhin ang resulta. Pagkatapos, i-check ang voltage drop ng transformer sa load na iyon at kung gaano karami ang nawawala bilang init.

Gaano karaming growth ang dapat kong isama?

Depende ito sa site. Karaniwan ang 20 hanggang 30 % kung saan malamang dadami ang load. Tumatagal ng dekada ang transformer, at mas magastos palitan ito mamaya kaysa kumuha ng isang size na mas malaki ngayon.

Ano ang transformer voltage regulation?

Ang pagbaba ng secondary voltage mula no load hanggang load, bilang porsyento. Galing ito sa resistance at reactance ng transformer, at mas malaki ito sa mababang power factor.

Bakit hindi na lang pumili ng mas malaking transformer?

Mas mahal ang mas malaking unit at tumatakbo ang core loss nito buong araw, araw-araw, kahit magaan ang load. Kapag i-size malapit sa load, tumatakbo ang transformer sa punto kung saan pinakamababa ang losses nito para sa enerhiyang inihahatid nito.

Saan galing ang impedance at losses?

Nasa rating plate ang impedance. Nasa test report ng maker ang losses at ang X/R ratio. Karaniwang figure ang default ng tool hanggang sa makuha mo ang totoong mga figure.

Nakatulong ba ito?

May tanong, o may value na mukhang mali? Makipag-ugnayan sa amin.