Downlight clearance check

IC, CA90 o Non‑IC: puwede bang dumikit ang insulation sa ilaw?

Reads AS/NZS 3000:2018. Tables checked 1 Oct 2026.

Mga input

Worked example gamit ang mga default na input.

Bansa
New Zealand
Installation
Residential
Marking sa luminaire
IC-4
Rating ng lamp
10 W
Insulation ng kisame
Insulation sa ibabaw
Sa maa-access na roof space
Oo

Ang luminaire na ito

Pinapayagan

Maaaring dumikit dito ang insulation
Oo
Maaaring takpan ito ng insulation
Oo
Limitasyon sa gilid at tuktok na ibabaw
90°C
Warning sign para sa roof space
Hindi kailangan

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. KlaseIC-4

    AS/NZS 3000:2018 Table 4.3

  2. Pinapayagan sa installation na itoOo

    AS/NZS 3000:2018 Cl 4.5.2.3.5(b)(i)

  3. Maaaring dumikit dito ang insulationOo

    AS/NZS 3000:2018 Table 4.3

  4. Maaaring takpan ito ng insulationOo

    AS/NZS 3000:2018 Table 4.3

  5. Limitasyon sa gilid at tuktok na ibabaw90°C

    AS/NZS 3000:2018 Table 4.3

  6. Warning sign sa roof spaceHindi kailangan

    AS/NZS 3000:2018 Cl 4.5.2.3.2

Tungkol sa calculator na ito

How this is calculated

A recessed luminaire, usually a downlight, sits in the ceiling with its body in the roof space. Its heat has to go somewhere, so AS/NZS 3000 sets which classes may go where and how close insulation may come. The class is the symbol on the luminaire or its box.

The tool first reads the marking. A luminaire marked to the 2001 standard is read as its current class: an IC-F as IC-4, a CA 80 as CA90. Then it checks the class against the list for your country and installation. A New Zealand home may take CA90, CA135, IC and IC-4. An Australian home may take Do-not-cover, CA90, IC and IC-4. Other buildings add Non‑IC and Do-not-cover, and New Zealand adds CA135.

Next it checks the insulation you plan against the class. IC and IC-4 may be covered. CA90 and CA135 may have insulation against their sides but not over the top. Do-not-cover may be near insulation but not touch it. Non‑IC is not tested with insulation, so the tool warns when insulation is present even kept clear.

Where insulation is kept clear and the maker gives no distance, the tool gives the default clearances of the standard for a lamp up to 100 W, for the dimensions its drawing shows for the class. Above 100 W there are no defaults: use the maker's distances or a luminaire certified for the condition. Last, it says whether the roof space needs the warning sign.

StepTable or clauseWhat it decides
A 2001 markingCl 4.5.2.3.5 ExceptionThe class an old marking is read as
The class for this installationCl 4.5.2.3.5Whether the class may go in this home or building
Insulation against or over the luminaireTable 4.3Whether insulation may abut or cover the class
Default clearancesFigure 4.9The distances where the clearance method is used
A lamp over 100 WCl 4.5.2.3.3(a)(viii)Which methods remain
The roof space signCl 4.5.2.3.2Whether the warning sign is needed

Worked examples

Limits

The tool reads the class and the clauses. It does not test a luminaire or check the maker's instructions, which take the place of the defaults. It does not size the lighting circuit or check its cable in the insulation; use the correction factors tool for a cable run in insulation. Spotlights that heat the surface they light follow Table 4.2, which the tool does not check.

See also: Downlights and insulation: IC-4, CA90 and Non‑IC, Downlights in an insulated ceiling and Lighting lumen method.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Puwede bang takpan ng insulation ang downlight?

Ang IC o IC-4 downlight lang. Sinubukan ang mga ito para ma-cover ng building insulation. Ang CA90 o CA135 ay maaaring may insulation sa gilid nito, pero hindi sa ibabaw. Ang ibang class ay kailangang may insulation na nakalayo.

Anong clearance ang kailangan ng downlight mula sa insulation?

Kapag walang ibinibigay ang maker, itinatakda ng AS/NZS 3000 Figure 4.9 ang mga default para sa lampara hanggang 100 W: 100 mm sa insulation, 100 mm sa building elements, 100 mm sa itaas, at 50 mm sa control gear. Nakadepende sa class kung alin ang nalalapat.

Anong downlight ang puwede sa bahay sa New Zealand?

CA90, CA135, IC at IC-4. Hindi puwede sa New Zealand residential installation ang Non‑IC at Do-not-cover. Sa Australia, puwedeng gamitin sa bahay ang Do-not-cover, CA90, IC at IC-4, at walang CA135.

Ang downlight ko ay may markang IC-F. Ano ito?

Marking mula sa 2001 standard. Pinapayagan ng AS/NZS 3000 na ituring na IC-4 ang IC-F downlight, at CA90 ang CA 80. Binabasa ito ng tool sa ganitong paraan para sa lumang marking.

Kailan kailangan ng warning sign ang roof space?

Kapag nasa accessible roof space ang recessed luminaire, maliban kung lahat sila ay IC o IC-4. Nakalagay ang sign sa access point, kung saan ito makikita ng taong papasok.

Mga worked example

Background

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 1 Oct 2026.