Outbuilding earthing

I-earth ang shed: earth kasama ang submain, o sarili nitong MEN.

Reads AS/NZS 3000:2018. Tables checked 1 Oct 2026.

Mga input

Worked example gamit ang mga default na input.

Bansa
New Zealand
Outbuilding
Indibidwal: isang istruktura na may sariling board
Earthing arrangement
Earth na kasama ng submain
Mga phase ng submain
Single phase
Aktibong sukat ng submain
6 mm²
Conductor
Tanso
Mga metal service sa pagitan ng mga gusali
Hindi

Protective earthing conductor

2.5mm²

Pinapayagan para sa outbuilding na ito
Earth kasama ng submain, o hiwalay na MEN

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. OutbuildingIndibidwal

    AS/NZS 3000:2018 Cl 1.4.88

  2. Earthing arrangementEarth run kasama ang submain

    AS/NZS 3000:2018 Cl 5.5.3.1(a)(i)

  3. Pinapayagan ditoOo

    AS/NZS 3000:2018 Cl 5.5.3.1(a)(i)

  4. Protective earthing conductorResulta2.5mm²

    AS/NZS 3000:2018 Table 5.1

Tungkol sa calculator na ito

How this is calculated

A shed, garage, sleep-out or workshop with its own board, fed by a submain, is an outbuilding. AS/NZS 3000 gives it two ways to be earthed. The tool asks which outbuilding it is and which way you plan, then checks the plan and gives the sizes.

An individual outbuilding is one structure, separated by land from the building whose board supplies it. It may take a protective earthing conductor run with the submain, connected at the main switchboard. Or it may be a separate MEN installation: the submain neutral becomes a PEN, the outbuilding board has its own MEN link, and an electrode is driven at the outbuilding. Combined outbuildings share a foundation, a metal roof or a metal frame. They take the earth with the submain only, so a separate MEN for them fails.

The sizes come from the same table as the earthing tool. With an earth in the submain, it is the protective earthing conductor for the submain's active size. With a separate MEN, the lead from the outbuilding board to its electrode is a main earthing conductor, sized from the submain. The PEN must be at least the neutral the submain needs and at least that earthing conductor, so the tool gives the larger. The electrode is one of the types the electrode table accepts, driven to the depth or laid to the length and cover for your country.

StepTable or clauseWhat it decides
Individual or combinedCl 1.4.88 and Cl 1.4.89Which arrangements the outbuilding may take
Earth with the submainCl 5.5.3.1(a)(i) and Cl 5.5.2.1Where the earth connects
Separate MENCl 5.5.3.1(a)(ii) and (c)The MEN link, the board and the main earthing conductor
Combined outbuildingCl 5.5.3.1(b)No separate MEN
Earthing conductor sizesTable 5.1The protective and main earthing conductors
PEN sizeCl 3.5.2(c)The least PEN of the submain
ElectrodeTable 5.2 and Cl 5.3.6.3The electrode, and its depth, length and cover

Worked examples

Limits

The tool does not size the submain itself; use the cable size or total voltage drop tools for that. It does not check the earth fault-loop impedance at the outbuilding, which the loop impedance tool does. It does not decide whether a structure is an outbuilding: that is the definition and your site. Bonding of water pipes and other services follows the earthing tool.

See also: Earthing an outbuilding: earth or its own MEN, Shed earthing on a 16 mm² submain and Earthing and bonding.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Kailangan ba ng shed ng sarili nitong earth stake?

Hindi palagi. Pinapayagan ng AS/NZS 3000 Cl 5.5.3.1 na ang isang hiwalay na outbuilding ay kumuha ng earth run kasama ang submain, nang walang electrode. Maaari rin itong maging hiwalay na MEN installation, at kung gayon, kailangan nito ng sarili nitong electrode at MEN link.

Ano ang pagkakaiba ng isang individual at combined na outbuilding?

Ang individual na outbuilding ay isang istruktura na may sarili nitong board, at hiwalay sa lupa mula sa gusaling nagsusuplay dito. Ang combined outbuildings ay nagbabahagi ng foundation, metal na bubong o metal na frame. Ang combined outbuildings ay may earth sa pamamagitan ng submain lang.

Anong laki ang PEN papunta sa hiwalay na MEN shed?

Hindi bababa sa neutral na kailangan ng submain, na active size para sa single‑phase submain, at hindi bababa sa earthing conductor mula sa Table 5.1. Ibinibigay ng tool ang mas malaki.

Gaano kalalim ang earth electrode?

Hindi bababa sa 1.8 m ang driven rod sa New Zealand at 1.2 m sa Australia. Ang strip sa trench ay may hindi bababa sa 0.5 m na cover at hindi bababa sa 7.5 m ang haba sa New Zealand o 3 m sa Australia.

Bakit mahalaga ang mga metal na pipe sa pagitan ng mga gusali?

Kapag may hiwalay na MEN, ang neutral ng submain ay siya ring earth. Ang metal na water pipe o walkway sa pagitan ng mga gusali ay maaaring magdala ng bahagi ng neutral current nang parallel. Nagbababala ang tool, at naiiwasan ito ng earth na kasama ng submain.

Mga worked example

Background

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 1 Oct 2026.