Fire alarm cabling lookup
Hanapin ang cable at circuit rules para sa fire alarm systems.
Reads NZS 4512:2010. Tables checked 26 Sept 2026.
Subukan ang isang job 4
Nilalagyan ng halimbawang value ang bawat job. Palitan ang mga ito ng sarili mong value.
- Choose the cable for a sounder circuitThe minimum conductor size for a fire alarm alerting device circuit.
- Choose the cable for a detector circuitThe minimum conductor for a four‑core detector circuit.
- Choose the cable for a transmission pathThe fire rating a transmission path needs.
- Choose the cable for staged evacuationThe cable for a staged evacuation circuit.
Mga input
Worked example gamit ang mga default na input.
- Uri ng circuit
- Circuit ng detector o manual call point
- Mga core sa cable
- 2
Pinakamaliit na laki ng conductor
0.75mm²
- Kailangan ng stranded conductor
- Oo
- Insulation resistance na lampas sa
- 5MΩ
- Fire rating
- Hindi itinatakda ng clause na ito
- Clause
- 402.1
Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.
Mga hakbang ng kalkulasyon
- Clause na nalalapat402.1
NZS 4512:2010 Cl 402.2
- Mga core sa cable2
NZS 4512:2010 Cl 402.1
- Pinakamaliit na laki ng conductorResulta0.75mm²
NZS 4512:2010 Cl 402.1
- Kinakailangan ang stranded conductorOo
NZS 4512:2010 Cl 402.1
- Nalalapat ang stranding sa ilalim ng1mm²
NZS 4512:2010 Cl 402.1
- Insulation resistance na higit sa5MΩ
NZS 4512:2010 Cl 402.2
- Fire ratingHindi itinatakda ng clause na ito
NZS 4512:2010 Cl 402.2
Tungkol sa calculator na ito
How this is calculated
The tool looks up what a fire alarm circuit needs from NZS 4512:2010 Clauses 402.1 and 402.2. It gives the conductor size, the stranding, the insulation resistance and the fire rating.
- Circuit. You pick the circuit: detector, alerting device, transmission, staged evacuation, data link or mains supply.
- Clause. The tool picks the clause. Cl 402.1 covers detector and alerting device circuits. Cl 402.2 covers the rest.
- Cores. You enter the number of cores in the cable. The size rule in Cl 402.1 reads it.
- Conductor size. The tool gives the minimum conductor size and says whether it must be stranded.
- Insulation resistance. From Cl 402.2 it gives the minimum insulation resistance.
- Fire rating. It gives the fire rating, or says that this clause does not set one.
| Step | Table or clause | What it decides |
|---|---|---|
| Conductor size and stranding | NZS 4512 Cl 402.1 | The smallest conductor and its construction |
| Insulation resistance | Cl 402.2 | The minimum test result |
| Fire rating | Cl 402.2 | The rating, where the clause sets one |
Worked example
A detector circuit in 2‑core cable. The minimum conductor size is 0.75 mm². The conductor must be stranded. The insulation resistance must be above 5 MΩ. This clause sets no fire rating.
Limits
- The tool reads Cl 402.1 and 402.2 only. Check the cable specification and the mechanical protection in Cl 402.1.
- Clause 402.2(g) is the other size driver. Read it in full.
- Check the earthing rules for zone circuit wiring in Cl 402.2(i).
- Check the separation and identification rules in Cl 402.2(k).
- The tool does not check voltage drop on the circuit.
- NZS 4512:2021 supersedes the 2010 edition this tool reads.
See also: Fire alarm battery, Detector spacing and the segregation checker.
Mga tanong
Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.
Anong laki ng cable ang kailangan ng fire alarm circuit?
Nagbibigay ang NZS 4512:2010 Clause 402.1 ng 0.75 mm² kada conductor para sa two‑core cable, at 0.5 mm² kada conductor kapag higit sa dalawang core ang cable. Iniuulat din ng AmpSize ang 1 mm² stranding threshold ng parehong clause. Basahin ang Clause 402.1 para sa mga uri ng cable at sa proteksyong tinatanggap nito.
Aling fire alarm circuit ang nangangailangan ng fire-rated cable?
Dalawang kaso ang iniuulat ng AmpSize. Binibigyan ng Clause 402.2(m) ng 15 min integrity ang AS/NZS 3013 Classification WS11 para sa transmission circuit. Binibigyan ng Clause 402.2(r) ng WS51W ang staged evacuation cabling. Basahin nang buo ang dalawang clause, dahil may kondisyon ang bawat isa na hindi tinitingnan ng tool na ito.
Kailangan ba ng fire alarm ng sarili nitong supply circuit?
Oo. Hinihingi ng Clause 402.2(f) ang hiwalay na subcircuit at permanent na label. Inililimbag ng AmpSize ang label text na ibinibigay ng clause, FIRE ALARM. Basahin ang Clause 402.2(f) para malaman kung saan nagsisimula ang subcircuit at kung saan dapat ilagay ang label.
Anong insulation resistance ang inaasahan?
Itinatakda ng Clause 402.2(j) ang criterion na higit sa 5 MΩ, at iniuulat ng AmpSize ang figure na iyon. Nasa Clause 402.2(i) at Clause 402.2(k) ang earthing at separation rules para sa parehong wiring. Basahin ang tatlo bago mo itala ang test result.
Kinukumpirma ba ng tool na ito na sumusunod ang isang installation?
Hindi. Iniuulat ng AmpSize ang mga figure ng NZS 4512:2010 Clauses 402.1 at 402.2 para sa circuit na pipiliin mo. Gabay ito, hindi desisyon. Sinusuri ang fire alarm installation laban sa buong standard at sa wiring rules.
Mga clause at table na binabasa ng tool na ito
- NZS 4512:2010 Cl 402.1Fire alarm cable
- NZS 4512:2010 Cl 402.2Fire alarm cable installation
- Cl 402Fire alarm cable and circuit requirements
Bawat clause at table, kasama kung paano ito na-verify
Huling na-check ang mga table noong 26 Sept 2026.