Fire alarm battery calculator
I-size ang standby battery para sa fire alarm panel.
Reads NZS 4512:2010. Tables checked 26 Sept 2026.
Subukan ang isang job 5
Nilalagyan ng halimbawang value ang bawat job. Palitan ang mga ito ng sarili mong value.
- Size a fire panel batteryThe battery capacity for 0.35 A on standby and 2.5 A in alarm.
- Size a battery for an unmonitored panelThe capacity for 72 hours of standby.
- Size a battery with ageingThe capacity with ageing and temperature factors.
- Size a small panel batteryThe capacity for 0.1 A standby and 0.8 A alarm.
- Size a 24-cell panel batteryThe capacity of a 48 V panel.
Mga input
Worked example gamit ang mga default na input.
- Non-alarm load
- 0.2 A
- Pinakamataas na alarm load
- 2 A
- Nakakonekta sa malayong receiving centre
- Oo
- Panahon ng alarma, minuto
- 30
- Ageing factor
- 1.25
- Temperature factor
- 1
- Mga cell na naka-series
- 12
Kinakailangang kapasidad sa 20 °C
7.25Ah
- Pinakamababang kapasidad bago ang mga factor
- 5.8Ah
- Panahon ng standby
- 24h
- Kapasidad ng standby
- 4.8Ah
- Kapasidad ng alarm sa inilagay na panahon
- 1Ah
- Ageing factor
- ×1.25
- Temperature factor
- ×1.00
- Kapasidad mula sa load at sa mga factor
- 7.25Ah
- Namamahalang halaga
- Kapasidad mula sa load at sa mga factor
- Charger current to restore in 24 h
- 0.5A
- Float voltage
- 26.4V
- Toleransiya ng float voltage
- ± 0.36V
- Pinakamababang boltahe sa buwanang test
- 19.2V
Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.
Mga hakbang ng kalkulasyon
- Panahon ng standby24h
NZS 4512:2010 Cl 213.1
- Kapasidad ng standby4.8Ah
NZS 4512:2010 Cl 213.1
- Inilagay na panahon ng alarma, minuto30
NZS 4512:2010 Cl 213.1
- Alarm period ng clause, minuto30
NZS 4512:2010 Cl 213.1
- Alarm period ng governing, minuto30
NZS 4512:2010 Cl 213.1
- Kapasidad ng alarm sa inilagay na panahon1Ah
NZS 4512:2010 Cl 213.1
- Kapasidad ng alarm sa namamahalang panahon1Ah
NZS 4512:2010 Cl 213.1
- Ageing factor×1.25
- Temperature factor×1.00
- Kapasidad mula sa load at sa mga factor7.25Ah
NZS 4512:2010 Cl 213.1
- Pinakamababang kapasidad bago ang mga factor5.8Ah
NZS 4512:2010 Cl 213.1
- Kinakailangang kapasidad sa 20 °CResulta7.25Ah
NZS 4512:2010 Cl 213.1
- Namamahalang halagaKapasidad mula sa load at sa mga factor
NZS 4512:2010 Cl 213.1
- Charger current to restore in 24 h0.5A
NZS 4512:2010 Cl 212
- Float voltage26.4V
NZS 4512:2010 Cl 212
- Toleransiya ng float voltage0.36V
NZS 4512:2010 Cl 212
- Current limit voltage bawat cell1.85V
NZS 4512:2010 Cl 212
- Tagal ng buwanang test10s
NZS 4512:2010 Cl 602.7
- Buwanang test discharge rate, oras5
NZS 4512:2010 Cl 602.7
- Pinakamababang service life, sa taon5
NZS 4512:2010 Cl 213.5
- Pinakamababang boltahe sa buwanang test19.2V
NZS 4512:2010 Cl 602.7
Tungkol sa calculator na ito
How this is calculated
The tool sizes the standby battery for a fire alarm panel to NZS 4512:2010 Clauses 212 and 213. It sizes the capacity only. It does not pick the battery type.
- Standby capacity. It multiplies the non‑alarm load by the standby period.
- Alarm capacity. It multiplies the alarm load by the alarm period. It compares your period with the period in Cl 213.1 and uses the longer.
- Factors. It adds the standby and alarm capacity. It multiplies by your ageing and temperature factors.
- Minimum. It also reads the minimum capacity before factors. The larger figure governs, and the tool names it.
- Charger. From Cl 212 it gives the charger current to restore the battery in 24 h. It also gives the float voltage and tolerance for your cell count.
- Monthly test. From Cl 602.7 it gives the minimum voltage the battery must hold in the monthly test.
| Step | Table or clause | What it decides |
|---|---|---|
| Capacity | NZS 4512 Cl 213.1 | Standby and alarm capacity, with factors |
| Charger and float | Cl 212 | Charger current and float voltage |
| Monthly test | Cl 602.7 | The minimum voltage in the test |
| Service life | Cl 213.5 | The minimum life of the battery |
Worked example
A panel with a 0.5 A non‑alarm load and a 3 A alarm load. The alarm period is 30 min. The system has 12 cells and is monitored. The tool gives 16.88 Ah at 20 °C. The charger current is 1.2 A. The float voltage is 26.4 V.
Limits
- NZS 4512:2021 supersedes the 2010 edition this tool reads. Check the current edition.
- The tool does not check the battery type or the service life.
- It does not add up the load of each device. You enter the totals.
- It gives the capacity at 20 °C. Enter a temperature factor for a cold or hot room.
See also: Fire alarm cabling, Sounder level and the DC battery sizing tool.
Mga tanong
Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.
Ano ang ginagawa ng Fire Alarm Battery tool?
Dinadagdag ng tool ang ampere hours na kinukuha ng panel sa standby period sa ampere hours na kinukuha nito sa alarm period. Ina-apply nito ang ageing factor at temperature factor, at iniuulat ang capacity sa 20 degree Celsius.
Gaano katagal dapat tumagal ang fire alarm battery?
Gumagamit ang AmpSize ng 24 na oras na standby kapag may monitoring link, at 72 na oras kapag wala. Pagkatapos ay idinadagdag ang 30 minutong alarm load. Galing sa NZS 4512:2010 Clause 213.1 ang tatlong figure na iyon. Pinapalipat ng form option ang pagitan ng dalawang standby period.
Puwede bang bumaba ang resulta sa ibaba ng figure ng clause?
Hindi. Nagbibigay ang Clause 213.1 at Clause 213.2 ng minimum na period. Kinukuha ng AmpSize ang minimum capacity bago ang mga factor, batay sa mas mahabang period sa pagitan ng alarm period ng clause at ng period na ilalagay mo, at hindi nito kailanman iniuulat ang mas mababa sa figure na iyon. Sa halip, may babalang lalabas kapag maikli ang alarm period.
Anong charger at float voltage ang iniuulat nito?
Hinahati ng AmpSize ang capacity sa 24 na oras at idinadagdag ang non‑alarm current. Iyon ang charger current ng Clause 212.1. Pinaparami rin nito ang 2.20 V at 0.03 V sa bilang ng cell mo, para sa float band ng Clause 212.5.
Ano ang monthly test criterion?
Sinusubukan ng Clause 602.7 ang battery sa loob ng 10 segundo sa 5 hour discharge rate o mas mataas. Habang sinusubukan, walang tulong na galing sa ibang source ang battery. Hindi dapat bumaba ang voltage nito sa 80 % ng nominal voltage nito.
Mga clause at table na binabasa ng tool na ito
- NZS 4512:2010 Cl 212Battery charger
- NZS 4512:2010 Cl 213Rechargeable batteries
- NZS 4512:2010 Cl 213.1Standby battery capacity
- NZS 4512:2010 Cl 213.5Battery service life
- Cl 211, 212, 213, 602.7Fire alarm standby battery periods, cell voltages and test criterion
Bawat clause at table, kasama kung paano ito na-verify
Huling na-check ang mga table noong 26 Sept 2026.