Cable fault rating calculator

Cable fault rating calculator para sa New Zealand at Australia. Galing ang k factor sa AS/NZS 3008.1.2:2017, o sa AS/NZS 3008.1.1:2025 na puwedeng piliin ang 2017.

Reads AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3008.1.1:2017 and 2025 (AU). Tables checked 27 Sept 2026.

Mga input

Worked example gamit ang mga default na input.

Prospective fault current
6 kA
Clearing time
0.1 s
Standard
NZ · AS/NZS 3008.1.2
Laki ng conductor
25 mm²
Material
Tanso
Insulation
PVC 75 °C
Insulation class
Mula sa insulation ng cable
Joint sa run
Walang joint

Pinakamaliit na laki ng conductor

17.09mm²

Napiling sukat
25mm²
Kayang tiisin ang fault current
8.78kA
k factor
111
Limitasyon ng temperatura
160°C

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Starting temperature ng conductor75°C

    AS/NZS 3008.1.2:2017 Table 53

  2. Limit ng temperatura sa short-circuit160°C

    AS/NZS 3008.1.2:2017 Table 53

  3. k factor×111.00

    AS/NZS 3008.1.2:2017 Table 52 p.121

  4. Pinakamaliit na laki ng conductorResulta17.09mm²

    AS/NZS 3008.1.2:2017 Cl 5.3

  5. Withstand fault current8.78kA

    AS/NZS 3008.1.2:2017 Cl 5.3

Tungkol sa calculator na ito

How this is calculated

The tool checks that a conductor survives a fault current for the time the protective device takes to clear it. It uses the adiabatic equation, S = √(I²t) / k. It assumes that no heat leaves the conductor during the fault.

  1. Temperatures. It reads the start temperature and the short-circuit temperature limit for the insulation. The insulation class select can name a 110 °C cross-linked type. A joint in the run can set a lower limit than the insulation.
  2. k factor. It reads k from Table 52 for the conductor material and the two temperatures. A larger temperature rise gives a larger k.
  3. Minimum size. S = √(I²t) / k gives the smallest conductor, in mm², that stays within the limit. I is the fault current in amperes and t is the clearing time in seconds.
  4. Withstand. It turns the equation round for the size you pick: I = k × S / √t. That is the largest fault current the conductor survives for that time.
  5. Result. The size you pick passes when it is at or above the minimum.

The Standard select decides which part it reads. It reads AS/NZS 3008.1.2 for New Zealand or AS/NZS 3008.1.1 for Australia. Take the clearing time from the device curve at the fault current. A longer time needs a larger conductor.

StepTable or clauseWhat it decides
TemperaturesTable 53The start temperature and the limit for the insulation
JointTable 55A lower limit where the joint sets it
k factorTable 52The k for the material and the two temperatures
Minimum size and withstandCl 5.3The adiabatic check itself

Tables without a standard named are in the part of AS/NZS 3008.1 you pick.

Common faults, worked with the tool

Each line states its conductor. Every line uses copper and the New Zealand tables, with no joint unless the line names one.

Keep the result

Every input sits in the page address, so the link in your browser reproduces the calculation. The PDF button prints the result with its steps and table references. Saving a calculation to a project needs a free account.

See also: Prospective fault current at a main switchboard, Arc flash incident energy at a 400 V switchboard and Short-circuit withstand and the k factor.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Ano ang ginagawa ng fault rating calculator?

Ina-apply ng tool ang adiabatic check sa conductor. Mula sa prospective fault current at sa clearing time, kinakalkula nito ang minimum size. Iniuulat din nito ang fault current na kayang tiisin ng inilagay na laki sa oras na iyon. Pumapasa ang check kapag hindi mas mababa sa minimum ang naka-install na laki.

Saan galing ang k factor?

Galing ang k factor sa AS/NZS 3008.1.2:2017 Table 52. Nakadepende ito sa conductor material at sa uri ng insulation. Ang bumagsak na check ay tumutukoy sa AS/NZS 3008.1.2:2017 Clause 5.3, na nagbibigay ng adiabatic equation na I²t = K²S². Kapag binago ang material o insulation, nagbabago rin ang k factor.

Ano ang nagtatakda ng minimum cable size para sa fault?

Itinutulak ng prospective fault current at ng clearing time ang minimum size. Dapat tumugma ang clearing time sa device na nag-aalis ng fault, hindi sa downstream device. Itinatakda ng material at insulation ang k factor. Ang mga cable na parallel ay itinuturing na isang conductor na may pinagsamang cross section.

Ano ang hindi sakop ng check na ito?

Hindi nito tinitingnan ang current rating, voltage drop o loop impedance. Gamitin ang cable size tool para sa mga check na iyon. Ipinapalagay din ng adiabatic method na walang init na lumalabas sa conductor habang may fault. Nasa page address ang mga input, kaya inuulit ng link ang parehong check.

Binabago ba ng laki ng conductor o ng joint ang k factor?

Oo. Ibinababa ng AS/NZS 3008.1.2:2017 Table 53 ang thermoplastic limit mula 160 patungong 140 degrees kapag higit sa 300 square millimetres. Nililimitahan ng Table 55 ang soldered joint sa 160 degrees. Binabasa ng tool ang dalawa, pagkatapos ay kinukuha ang k factor para sa start at limit pair na iyon mula sa Table 52.

Mga worked example

Lahat ng 7 na guide para sa calculator na ito

Background

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 27 Sept 2026.