Lumaktaw sa nilalaman
AmpSize

Switchboard circuit chart

Gumawa ng board circuit chart at ang mga label na kailangan nito.

Reads AS/NZS 3000:2018. Tables checked 1 Oct 2026.

Mga input

Worked example gamit ang mga default na input.

Pangalan ng board
Hindi nakasaad
Board
Main switchboard
Single domestic installation
Oo
Mga main switch
1
Alternatibong supply
Wala
Mga final subcircuit, ayon sa pagkakasunod sa board
6 row

Mga circuit sa chart

6

Mga ways na ginamit
6
Label ng main switch
MAIN SWITCH

Design aid lang ang resultang ito. I-verify ito laban sa kasalukuyang standard.

Mga hakbang ng kalkulasyon

  1. Way 1Mga ilaw

    AS/NZS 3000:2018 Cl 2.10.5.2

  2. Way 2Lounge and bedroom sockets

    AS/NZS 3000:2018 Cl 2.10.5.2

  3. Way 3Mga socket sa kusina

    AS/NZS 3000:2018 Cl 2.10.5.2

  4. Way 4Laundry and bathroom

    AS/NZS 3000:2018 Cl 2.10.5.2

  5. Way 5Oven

    AS/NZS 3000:2018 Cl 2.10.5.2

  6. Way 6Hot water

    AS/NZS 3000:2018 Cl 2.10.5.2

  7. Label ng main switchMAIN SWITCH

    AS/NZS 3000:2018 Cl 2.3.3.5(a)

  8. Label ng boardHindi kailangan sa iisang domestic installation

    AS/NZS 3000:2018 Cl 2.10.2.4 Exception 1

  9. LabelMAIN SWITCH

    AS/NZS 3000:2018 Cl 2.3.3.5(a)

  10. Mga ways na ginamitResulta6

Tungkol sa calculator na ito

How this is calculated

You list the final subcircuits of one board in the order they sit: what each supplies, its device and rating, its active conductor, single or three phase, its RCD, and any neutral it shares. It is the same list the test schedule reads, so a link carries the circuits from one tool to the other.

The tool numbers the ways in order. A single‑phase circuit takes one way and a three‑phase circuit three. Each row of the chart gives the way, what the circuit supplies, its device, its RCD and its active conductor. That is how the wiring rules want a board marked: each switch, circuit-breaker, fuse and RCD tied to the part of the installation it supplies, on or beside the board. A circuit with no name fails, because nobody can tell from the chart what it feeds.

Then the board's own labels. Each main switch says MAIN SWITCH, and where a board has more than one, each names the part it controls. A main switchboard says MAIN SWITCHBOARD, except in a single domestic installation. A solar, generator or battery supply has its main switch labelled with its energy source, and a notice shows where it is isolated. A sub‑board's isolating switch names the circuits it isolates. A shared neutral is marked with the actives it serves, and the chart names their ways.

The clauses ask for marking in English, legible and indelible. They set no letter height or colour, so the tool states none. The chart prints as a PDF for the board door.

StepTable or clauseWhat it decides
Chart of the circuitsCl 2.10.5.2Each device tied to what it supplies
Main switchCl 2.3.3.5MAIN SWITCH, its part and its energy source
Main switchboardCl 2.10.2.4MAIN SWITCHBOARD, and the single home exception
Isolating switchCl 2.3.4.4The circuits a sub‑board switch isolates
Shared neutralCl 2.10.5.5The actives a shared neutral serves
MarkingCl 2.10.5.1English, legible and indelible

Worked examples

  • A New Zealand house board. The chart holds 6 circuits on 6 ways, and the main switch is labelled MAIN SWITCH. The board needs no MAIN SWITCHBOARD label in a single home.
  • A shop board with solar. The chart holds 6 circuits on 6 ways, with MAIN SWITCH, MAIN SWITCHBOARD and MAIN SWITCH SOLAR labels.
  • A workshop sub‑board. The chart holds 4 circuits on 8 ways: the two three‑phase circuits take ways 3-5 and 6-8. The isolating switch names the circuits it isolates.

Limits

The chart is as good as the list: it does not check the devices, cables or RCD arrangement. Use the circuit check, RCD arrangement and test schedule tools for those. It does not draw the board, and it does not set a form of separation or an enclosure. It covers the labels the wiring rules name; a network company or a building owner may ask for more.

See also: Switchboard labels and circuit charts, A circuit chart for a house board with solar and Circuit Check.

Mga tanong

Design aid ang resulta. I-verify ito laban sa kasalukuyang standard.

Kailangan ba ng switchboard ng circuit chart?

Hinihingi ng AS/NZS 3000 Cl 2.10.5.2 na markahan ang bawat switch, circuit-breaker, fuse at RCD ng bahagi ng installation na sinusuplayan nito, sa board o sa tabi nito. Karaniwang ginagawa ito sa pamamagitan ng circuit chart sa pinto.

Anong label ang kailangan ng main switchboard?

MAIN SWITCH sa bawat main switch, at MAIN SWITCHBOARD sa board, maliban sa iisang domestic installation. Kapag may higit sa isang main switch, binabanggit ng bawat isa ang bahaging kinokontrol nito. Binabanggit ng solar o generator main switch ang energy source nito.

Gaano kalaki dapat ang mga label?

Walang itinatakdang taas ng letra o kulay ang wiring rules. Hinihingi nila na nasa English ang marking, malinaw basahin, at hindi mabubura. Dapat ding mamukod ang main switch sa iba pang switchgear sa pamamagitan ng grouping, contrasting na kulay o katulad nito.

Paano minamarkahan ang shared neutral?

Ang neutral na ginagamit ng dalawa o higit pang circuit ay minarkahan ng mga active na sinusuplayan nito, ayon sa Cl 2.10.5.5. Bigyan ang mga circuit na iyon ng parehong shared neutral number at pangalanan ng chart ang kanilang daan.

Puwede ko bang gamitin ang parehong circuit list para sa test sheet?

Oo. Parehong circuit list ang binabasa ng circuit chart at ng test schedule, kaya dinadala ng link ang mga circuit mo mula sa isang tool papunta sa isa pa.

Mga worked example

Background

Mga clause at table na binabasa ng tool na ito

Bawat clause at table, kasama kung paano ito na-verify

Huling na-check ang mga table noong 1 Oct 2026.

Nakatulong ba ito?