المدخلات

مثال محلول بالمدخلات الافتراضية.

جدول الطلب
Table C1 · منزلي
التركيب
منزل واحد أو وحدة سكنية واحدة
الأطوار
طور واحد
جهد الطور
230 V
مجموعات الأحمال
4 صفوف

الطلب الأقصى

50.43A

لكل طور
50.43A
A(i) · Lighting
5A
B(i) · Socket-outlets and permanently connected equipment up to 10 A
15A
C · Ranges, cooking appliances and laundry equipment
17.39A
F · Storage water heaters
13.04A

هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.

خطوات الحساب

  1. جدول الطلبC1 · single domestic

    AS/NZS 3000:2018 Table C1

  2. A(i) · Lighting5A

    AS/NZS 3000:2018 Table C1

  3. B(i) · Socket‑outlets and permanently connected equipment up to 10 A15A

    AS/NZS 3000:2018 Table C1

  4. C · Ranges, cooking appliances and laundry equipment17.39A

    AS/NZS 3000:2018 Table C1

  5. F · Storage water heaters13.04A

    AS/NZS 3000:2018 Table C1

  6. الطلب الأقصى50.43A

    AS/NZS 3000:2018 Table C1

  7. الحمل الأقصى لكل طورالنتيجة50.43A

    AS/NZS 3000:2018 Table C1

حول هذه الحاسبة

How this is calculated

The tool works out the maximum demand of an installation from its loads. It follows the load group method of AS/NZS 3000 Appendix C.

  1. Table. Table C1 covers domestic installations: one house or living unit, or a block of living units. Table C2 covers other installations. For Table C2 you pick the occupancy.
  2. Load groups. You enter each load in its group, such as lighting points, socket‑outlet points or kW of cooking. The tool lists only the groups the table assesses for your choice.
  3. Group demand. Each group has its own rule for its load. The tool applies that rule and gives the group demand in amperes. It converts each kW load at the phase voltage you enter.
  4. Living units per phase. A block of living units can take more than one phase. The tool then divides the units by the number of phases and rounds up. It reads the column for that number of units per phase.
  5. Total. The maximum demand is the sum of the group demands.
  6. Per phase. On three phases, the tool divides the total by three. That assumes you spread the load evenly over the phases. Where you cannot, allocate the loads per phase and check the heaviest phase.
StepTable or clauseWhat it decides
Domestic loadsAS/NZS 3000 Table C1The rule for each load group in a house or a block of living units
Other loadsAS/NZS 3000 Table C2The rule for each load group, by occupancy
Living units per phaseTable C1 Note 2The column a block of living units reads on more than one phase
Total and per phaseTable C1 or Table C2The sum of the groups and the share on each phase

Phase voltage

Enter the phase voltage, line to neutral, such as 230 V. The tool converts every kW load at that voltage. The 400 V between lines would read every kW group 42 % low. On a three‑phase supply the tool refuses a line voltage and asks for the phase voltage.

Common installations, worked with the tool

Each line states its loads. Every line uses a phase voltage of 230 V.

  • House on one phase. It uses Table C1 for one house. The loads are 30 lighting points, 25 socket‑outlet points, 8 kW of cooking and a 3 kW storage water heater. The maximum demand is 50.43 A.
  • The same house on three phases. The maximum demand is 16.81 A per phase and 50.43 A over all phases.
  • Block of 12 living units on three phases. Table C1 for blocks of living units, with the same load rows. The tool reads 4 units per phase. The maximum demand is 75 A per phase and 225 A over all phases.
  • Office on three phases. It uses Table C2 for factories, shops and offices. The loads are 10 kW of lighting, 20 socket‑outlets and motors of 15 A, 10 A and 5 A. The maximum demand is 44.93 A per phase and 134.78 A over all phases.

New Zealand and Australia

AS/NZS 3000 Appendix C applies in both countries, so the tool has no country select.

Keep the result

Every input sits in the page address, so the link in your browser reproduces the calculation. The PDF button prints the result with its steps and table references. Saving a calculation to a project needs a free account.

See also: Commercial maximum demand with Table C2, Domestic maximum demand with Table C1 and Maximum demand and diversity.

الأسئلة

النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.

ماذا تفعل حاسبة الطلب الأقصى؟

تطبّق الأداة قاعدة الطلب على كل مجموعة أحمال تضيفها. تسرد الطلب لكل مجموعة بوحدة A، ثم تعرض إجمالي الطلب والطلب لكل طور. يُظهر كل سطر الجدول والعمود اللذين أنتجاه.

ما جداول AS/NZS 3000 التي تستخدمها حاسبة الطلب الأقصى؟

تستخدم الأداة AS/NZS 3000:2018 Table C1 لتركيب منزلي واحد أو لمبنى من الوحدات السكنية. وتستخدم Table C2 للتركيبات الأخرى، مع عمود سكني أو تجاري. اختر الجدول والوضع أولاً، لأنهما يغيّران القاعدة التي تتبعها كل مجموعة أحمال.

ما الذي يحدد قاعدة الطلب لكل مجموعة حمل؟

يحدد الجدول والوضع القاعدة لكل مجموعة. ويحوّل جهد التغذية المجموعات المعطاة بالكيلوواط إلى أمبير. ويقسم عدد الأطوار الإجمالي. وفي وضع الوحدات السكنية، يحدد عدد الوحدات في كل طور النتيجة. أدخل إجمالي عدد الوحدات وعدد الأطوار.

كيف تُحصى الوحدات السكنية على ثلاثة أطوار؟

تقسم الأداة عدد الوحدات على 3، كما تشترط الملاحظة b في Table C1. تأخذ بعض المجموعات قائمة بالبنود الفردية، لا كمية واحدة. وبعض المجموعات تُحدَّد وفق التقييم ولا تضيف شيئاً. تظهر ملاحظة فوق حدود اللائحة 59.

هل يمكنني مشاركة حساب الطلب أو حفظه؟

نعم. يُحفظ الجدول والوضع والجهد والأطوار وكل صف حمل في عنوان الصفحة. انسخ الرابط لإرسال تقييم الطلب نفسه إلى شخص آخر. ويحتاج حفظه باسم مشروع إلى حساب. وشروط نيوزيلندا هي الافتراضية.

أمثلة محلولة

كل الأدلة الـ8 لهذه الحاسبة

الخلفية

البنود والجداول التي تقرأها هذه الأداة

كل البنود والجداول، مع طريقة التحقق من كل منها

آخر فحص للجداول في 19 Sept 2026.

هل كان هذا مفيداً؟

سؤال، أو قيمة تبدو خاطئة؟ اتصل بنا.