ميزانية قدرة الحلقة لحلقات 4-20 mA
تحقّق من الجهد الذي تتركه حلقة 4–20 mA عند الجهاز الإرسالي.
Reads AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3008.1.1:2017 and 2025 (AU). Tables checked 27 Sept 2026.
جرّب مشروعاً 6
تملأ كل مهمة قيماً توضيحية. استبدلها بقيمك.
- Check a 4–20 mA loop's power budgetThe supply, the series resistance and the cable give the voltage left at the transmitter.
- Check a loop with a HART resistorThe voltage left with a 250 Ω HART resistor in the loop.
- Check a loop through a barrierThe voltage left with 300 Ω of barrier in series.
- Check a 2 km loopThe voltage left on 1 mm² cable over 2000 m.
- Check a loop on a 12 V supplyWhether a 12 V supply drives the loop.
- Check a loop at fault currentThe voltage left at 22 mA.
المدخلات
مثال محلول بالمدخلات الافتراضية.
- جهد تغذية الحلقة
- 24 V
- الحد الأدنى لجهد المرسل
- 12 V
- تيار الحلقة
- 20 mA
- مقاومة المدخل
- 250 Ω
- مقاومة HART
- 0 Ω
- مقاومة توالي أخرى
- 0 Ω
- طول الكابل، باتجاه واحد
- 500 m
- مقاومة الموصل
- من حجم الموصل
- حجم الموصل
- 1 mm²
- المعيار
- NZ · AS/NZS 3008.1.2
هامش الجهد
6.48V
- الجهد عند المرسل
- 18.48V
- مقاومة الحلقة
- 275.8Ω
- مقاومة الكابل
- 25.8Ω
- أقصى مقاومة للحلقة
- 600Ω
- أقصى طول للكابل
- 6,782m
هذه النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
خطوات الحساب
- مقاومة الموصل25.8Ω/km
AS/NZS 3008.1.2:2017 Tables 34 to 35
- مقاومة الكابل، للموصلين معًا25.8Ω
- المقاومة المتسلسلة250Ω
- مقاومة الحلقة275.8Ω
- تيار الحلقة20mA
- هبوط الجهد في الحلقة5.52V
- الجهد عند المرسل18.48V
- هامش الجهدالنتيجة6.48V
- أقصى مقاومة للحلقة600Ω
- أقصى طول للكابل6,782m
حول هذه الحاسبة
How the tool checks the loop
A 4–20 mA loop is one series circuit. The loop supply drives the current through the transmitter, the cable and the receiver input. The transmitter needs a minimum voltage at its terminals to work.
- Conductor resistance. The tool reads the resistance of a copper conductor for the size you pick. It can also take the value from the cable data.
- Cable resistance. The current goes out on one conductor and comes back on the other. So the tool doubles the one-way length.
- Loop resistance. It adds the cable resistance to the input resistance, the HART resistor and any other series parts.
- Voltage at the transmitter. It multiplies the loop current by the loop resistance and subtracts that drop from the supply voltage.
- Voltage margin. It subtracts the transmitter minimum voltage. A margin of 0 V or more passes.
- Maximum length. It gives the longest one-way run that keeps the margin at 0 V or more.
Worked loops
Each line opens the tool with its values. Every line uses a 24 V supply, a 12 V transmitter minimum voltage and a 250 Ω receiver input.
- Pressure transmitter, 500 m of 1 mm² at 20 mA. The loop passes with a margin of 6.48 V.
- HART loop, 400 m of 1 mm² at 22 mA. A 250 Ω HART resistor sits in the loop. The loop passes with a margin of 0.55 V.
- HART loop, 500 m of a 36 Ω/km pair at 22 mA. The resistance comes from the cable data. The loop passes with a margin of 0.21 V.
- The same HART loop at 700 m. The loop fails with a margin of −0.11 V. Shorten the run, use a larger conductor or raise the supply.
New Zealand and Australia
The Standard select picks the part of AS/NZS 3008.1 the tool reads for the conductor resistance. Part 1.2 is the New Zealand part, 2017 edition. Part 1.1 is the Australian part. For Australia, the Edition select picks 2025 or the superseded 2017 edition. All three print the same resistance values. The impedance table entry says how AmpSize checked them.
Related checks
- The comms cable selector checks the cable construction and the run length for the interface.
- The DC cable size calculator sizes the 24 V d.c. supply cable to the transmitter panel.
- The segregation checker checks the spacing between the loop cable and power cables.
الأسئلة
النتيجة أداة للتصميم. تحقق منها وفق المعيار الحالي.
ما الذي يحدد المسافة التي يمكن أن تمتدها حلقة 4–20 mA؟
الجهد المزوَّد ناقص الحد الأدنى لجهد المرسل هو الميزانية. ويستنفدها تيار الحلقة عبر كل مقاومة متسلسلة. ويضيف الكابل مقاومة الموصلين معاً، لذلك يستنفد المسار الأطول أو الموصل الأرفع المزيد.
لماذا أفحص عند أكثر من 20 mA؟
يمكن للمرسل أن يقود أكثر من 20 mA، مثل إنذار الحد الأعلى قرب 22 mA. يرتفع هبوط الجهد في الحلقة مع التيار. تحقّق عند أعلى تيار يقوده المرسل.
أين أجد الحد الأدنى لجهد الجهاز الإرسالي؟
تعطيه ورقة بيانات المرسل، غالباً كجهد الإقلاع (lift-off) أو كأدنى جهد طرفين. وبعض أوراق البيانات تعطي خط الحمل بدلاً من ذلك. اقرأ الجهد عند أعلى تيار للحلقة.
الخلفية
البنود والجداول التي تقرأها هذه الأداة
- AS/NZS 3008.1.2:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2025 Table 4.1(A), 4.1(B), 4.5(A), 4.5(B)Reactance at 50 Hz and a.c. resistance at 50 Hz
كل البنود والجداول، مع طريقة التحقق من كل منها
آخر فحص للجداول في 27 Sept 2026.