असंतुलित लोड का न्यूट्रल करंट
एक अनबैलेंस्ड थ्री-फ़ेज़ लोड का न्यूट्रल करंट।
Reads AS/NZS 3000:2018. Tables checked 2 Oct 2026.
कोई प्रोजेक्ट आज़माएँ 4
हर जॉब में उदाहरण मान भरे होते हैं। उन्हें अपने मानों से बदलें।
- Find the neutral current of a shop boardThe neutral current of a board with 45, 30 and 25 A on its phases.
- Neutral current with heaters and a motorHeaters on one phase and a motor on another: the neutral with two power factors.
- Neutral current of a farm on one phaseMost of the load on one phase: how close the neutral comes to that phase.
- Check the neutral of a mostly three‑phase loadThe out-of-balance current a reduced neutral must still carry.
इनपुट
डिफ़ॉल्ट इनपुट के साथ एक कार्य-उदाहरण।
- लाइन वोल्टेज
- 400 V
- फ़ेज़ A धारा
- 32 A
- फ़ेज़ B धारा
- 20 A
- फ़ेज़ C धारा
- 10 A
- फ़ेज़ A पावर फ़ैक्टर
- 1
- फ़ेज़ B पावर फ़ैक्टर
- 1
- फ़ेज़ C पावर फ़ैक्टर
- 1
न्यूट्रल धारा
19.08A
- सबसे बड़े फेज़ के हिस्से के रूप में न्यूट्रल
- 59.6%
- सबसे बड़ी फेज़ धारा
- 32A
- वास्तविक शक्ति, तीन फेज़
- 14.32kW
यह परिणाम डिज़ाइन में सहायता के लिए है। इसे मौजूदा मानक से सत्यापित करें।
गणना के चरण
- फ़ेज़ A धारा, फ़ेज़ A वोल्ट से 0° पर32A
- फ़ेज़ B धारा, फ़ेज़ A वोल्ट से −120° पर20A
- फ़ेज़ C धारा, फ़ेज़ A वोल्ट से 120° पर10A
- सूत्र: एक पावर फ़ैक्टर, इसलिए
I_N = √(Ia² + Ib² + Ic² − Ia·Ib − Ib·Ic − Ic·Ia)
19.08 A - न्यूट्रल धारापरिणाम19.08A
AS/NZS 3000:2018 Cl 3.5.2(b)(ii)
- फेज़ A से न्यूट्रल धारा का कोण−27
- सबसे बड़े फेज़ के हिस्से के रूप में न्यूट्रल59.6%
- वास्तविक शक्ति, तीन फेज़14.32kW
इस कैलकुलेटर के बारे में
How this is calculated
In a star load each phase current returns through the neutral. The three phase voltages are 120° apart, so the three currents are too. When the currents are equal and at one power factor, they cancel and the neutral carries nothing. When they are not equal, the neutral carries what is left over.
The tool works that left-over current as a phasor sum. It sets phase A at 0°, phase B at −120° and phase C at +120°. It then turns each current back by its own power factor angle, because a lagging load draws its current after its voltage. The three currents are added as vectors, and the size of the sum is the neutral current. The tool also gives the angle of the sum from the phase A voltage.
When all three power factors are the same, the angles cancel out of the sum. The tool then shows the short formula: the square root of the sum of the three squares, less the three products of pairs.
The neutral can carry more than the largest phase. That happens when the power factors differ a lot, so two currents line up. The tool warns when it does.
The answer is the current at the supply frequency only. Third harmonic currents from electronic loads add in the neutral, not cancel. The harmonics tool works those.
| Step | Table or clause | What it decides |
|---|---|---|
| Phasor of each phase | The phase angle less the power factor angle | Where each current points |
| Neutral current | The phasor sum of the three | The current the neutral carries |
| One power factor | I_N = √(Ia² + Ib² + Ic² − Ia·Ib − Ib·Ic − Ic·Ia) | The short form of the sum |
| Neutral size | Cl 3.5.2(b)(ii) | A neutral at least the size of the largest active |
| A smaller neutral | Cl 3.5.2 Exception 3 | Allowed for a mostly multiphase load that still carries the out-of-balance current |
| Harmonics | Cl 3.5.2(b)(i) | Third harmonic currents add to the out-of-balance current |
Worked examples
- A shop board with 45, 30 and 25 A on its phases has 18.03 A in the neutral, 40.1 % of the largest phase.
- A farm supply with 40 A on one phase and 5 A on the others has 35 A in the neutral, 87.5 % of the largest phase. Nearly all of the load comes back on it.
- Heaters on phase A and a motor on phase B at 0.8 power factor give 19.69 A in the neutral, 65.6 % of the largest phase.
- A mostly three‑phase load of 60, 55 and 50 A at 0.85 power factor leaves 8.66 A in the neutral, 14.4 % of the largest phase.
Limits
The tool takes three phase currents and their power factors, all lagging. It does not take a leading load, such as a capacitor bank, or a load connected between two phases.
It gives the current, not the conductor size. Take the larger of the neutral current and the largest phase current to the cable size tool.
See also: Three phase power, Max demand by phase and Cable size.
सवाल
परिणाम एक डिज़ाइन सहायता है। मौजूदा मानक से सत्यापित करें।
थ्री-फ़ेज़ लोड का न्यूट्रल करंट कैसे निकालें?
तीन फ़ेज़ करंट को फ़ेज़र के रूप में जोड़ें, 120° के अंतर पर, हर एक अपने पावर फ़ैक्टर कोण से घुमाकर। योग का आकार न्यूट्रल करंट है। सभी फ़ेज़ पर एक ही पावर फ़ैक्टर हो तो यह √(Ia² + Ib² + Ic² − Ia·Ib − Ib·Ic − Ic·Ia) है।
न्यूट्रल करंट फ़ेज़ों के बीच का अंतर क्यों नहीं है?
फ़ेज़ करंट 120° के अंतर पर हैं, इसलिए वे सीधी रेखा में जुड़ते या घटते नहीं। 32 A, 20 A और 10 A न्यूट्रल में 19.08 A देते हैं, न कि 22 A या 12 A।
क्या न्यूट्रल किसी फ़ेज़ से ज़्यादा करंट ले जा सकता है?
हाँ। बहुत अलग पावर फ़ैक्टर पर फ़ेज़र एक लाइन में आ सकते हैं, और न्यूट्रल सबसे बड़े फ़ेज़ से ज़्यादा ले जा सकता है। इलेक्ट्रॉनिक लोड से तीसरे हार्मोनिक करंट भी न्यूट्रल में जुड़ते हैं। जब योग सबसे बड़े फ़ेज़ से ज़्यादा हो, तो टूल चेतावनी देता है।
थ्री-फ़ेज़ सर्किट का न्यूट्रल कितना बड़ा होना चाहिए?
AS/NZS 3000 Cl 3.5.2(b)(ii) माँगता है कि न्यूट्रल सबसे बड़े एक्टिव जितना कम से कम बड़ा हो। Exception 3 छोटे न्यूट्रल की अनुमति देता है, जहाँ ज़्यादातर लोड मल्टी-फ़ेज़ हो और न्यूट्रल फिर भी अपने हार्मोनिक्स के साथ अनबैलेंस करंट ले जाए।
क्या संतुलित लोड को न्यूट्रल चाहिए?
एक ही पावर फ़ैक्टर पर तीन बराबर करंट एक-दूसरे को काटते हैं, इसलिए फ़ंडामेंटल पर न्यूट्रल में कोई करंट नहीं होता। सिंगल-फ़ेज़ आइटम वाला स्टार लोड फिर भी उसे चाहता है, क्योंकि लोड बंद होने पर बैलेंस बदलता है।
वे Clauses और Tables जो यह टूल पढ़ता है
- AS/NZS 3000:2018 Cl 3.5.2(b)Neutral of a multiphase circuit
- AS/NZS 3000:2018 Cl 3.5.2Neutral conductor of a circuit
हर Clause और Table, और उनकी सत्यापन की विधि
Tables आख़िरी बार 2 Oct 2026 को जाँची गईं।
संबंधित टूल
- केबल आकार कैलकुलेटरFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- सप्लाई का वोल्टेज अनबैलेंसVoltage or current unbalance from three line readings.कोई मानक नहीं
- हार्मोनिक्स, न्यूट्रल करंट और k फ़ैक्टरTHD, neutral current and K-factor from a spectrum.AS/NZS 3008.1AS/NZS 3000