कॉम्स केबल सिलेक्टर
एक कॉम्स केबल चुनें और रन की लंबाई जाँचें।
Reads AS/NZS 3000:2018 and Industrial communications sources 2019-2024. Tables checked 26 Sept 2026.
कोई प्रोजेक्ट आज़माएँ 8
हर जॉब में उदाहरण मान भरे होते हैं। उन्हें अपने मानों से बदलें।
- Add an instrument loopA cable for the signal over a 150 m route.
- Select a comms cableA PROFINET cable for a 60 m run through a drag chain.
- Check an RS-485 runWhether 400 m at 115.2 kbps is in the limit.
- Check a long Modbus trunkWhether 1200 m at 9.6 kbps is in the limit.
- Check an Ethernet run past 90 mWhether a 110 m Ethernet run is in the limit.
- Pick a 24 V field supply cableA cable for a 24 V d.c. supply over 80 m.
- Pick a screened cable beside a driveA screened signal cable for a noisy area.
- Pick an outdoor Ethernet cableAn Ethernet cable for an outdoor run.
इनपुट
डिफ़ॉल्ट इनपुट के साथ एक कार्य-उदाहरण।
- इंटरफ़ेस
- RS-485
- परिवेश
- फ़िक्स्ड इंस्टॉलेशन
- रन की लंबाई
- 100 m
- शीथ सामग्री
- PVC
- केबल स्क्रीन्ड है
- हाँ
- ट्रांसमिशन गति
- 187.5 kbps
- बस केबल परिवार
- मानक, मज़बूत, FRNC, खाद्य, भूमिगत या समुद्री
रन की लंबाई
सीमा के भीतर
- लंबाई सीमा
- 1,000m
- केबल की बनावट
- 1 pair or more, 2 cores, larger than 0.34 mm2, required screen
- स्क्रीन
- आवश्यक
- स्क्रीन जाँच
- पास
- हर सिरे पर टर्मिनेशन
- 120Ω
- प्रति लाइन इकाई लोड
- 32
- पर्यावरण जाँच
- पास
- श्रेणी जाँच
- लागू नहीं
- नोट
- A PROFIBUS DP segment at 187.5 kbps on standard bus cable may run 1000 m, from a cable maker network manual. The held table falls from 1000 m at 9.6 kbps to 100 m from 3 Mbps up. TIA-485 itself sets no maximum line length, and a separate report gives a nominal 1.2 km on 24 AWG cable.
यह परिणाम डिज़ाइन में सहायता के लिए है। इसे मौजूदा मानक से सत्यापित करें।
गणना के चरण
- इंटरफ़ेसRS-485
Industrial communications sources 2019-2024
- रन की लंबाई100m
- लंबाई सीमा1,000m
Industrial communications sources 2019-2024
- लंबाई जाँचपास
- निर्माण1 pair or more, 2 cores, larger than 0.34 mm2, required screen
Industrial communications sources 2019-2024
- स्क्रीन आवश्यकrequired
Industrial communications sources 2019-2024
- स्क्रीन जाँचपास
- वातावरणस्थिर इंस्टॉलेशन
Industrial communications sources 2019-2024
- वातावरण की जाँचपास
- श्रेणी जाँचलागू नहीं
- ट्रांसमिशन गति187.5 kbps
- छपी गई गति पंक्ति187.5 kbps
Industrial communications sources 2019-2024
- बस केबल परिवारमानक बस केबल
Industrial communications sources 2019-2024
- हर सिरे पर टर्मिनेशन120Ω
Industrial communications sources 2019-2024
- प्रति लाइन यूनिट लोड32
Industrial communications sources 2019-2024
- प्रति सेगमेंट बस अटैचमेंट32
Industrial communications sources 2019-2024
इस कैलकुलेटर के बारे में
How this is calculated
The tool picks the cable construction for a control or data link. It checks your run length against the limit for the interface. No AmpSize figure here comes from a printed Standard. The figures come from maker data and course notes, which the tool labels as secondary sources.
- Interface. You pick 24 V d.c., 4–20 mA, RS-485, Ethernet or PROFINET. For RS-485 you also pick the data rate and the bus cable family.
- Length limit. The tool reads the longest run for that interface. For RS-485 the limit falls as the data rate rises.
- Length check. It compares your run with the limit. It reports the run as inside or over the limit.
- Construction. It gives the pairs, the cores and the smallest core size. It says whether a screen is required, and checks the screen you enter.
- Environment. It checks the sheath and the bend radius for a fixed or a flexing installation. For Ethernet it checks the category.
- Termination. For RS-485 it gives the termination at each end and the unit loads per line.
| Step | Source | What it decides |
|---|---|---|
| Length limit | Industrial communications sources 2019 to 2024 | The longest run for the interface |
| Construction and screen | Industrial communications sources 2019 to 2024 | The cable build |
| Termination | Industrial communications sources 2019 to 2024 | The resistor at each end |
Worked example
- RS-485 at 187.5 kbps over 1200 m. The limit is 1,000 m, so the run is over the limit. The screen and environment checks pass. Add a repeater or shorten the run.
Limits
- The figures are secondary source and maker data. They are not a Standard. Confirm each one with the device maker.
- The tool does not size power conductors. Use the DC cable size calculator for a 24 V supply.
- The tool does not check segregation from power cables. Use the segregation checker.
- The termination value suits typical cable. Match it to the cable you use.
- The 32 unit loads on an RS-485 line are not a device count.
See also: Control panels and PLC wiring, 24 V DC instrument loop voltage drop and Loop power.
सवाल
परिणाम एक डिज़ाइन सहायता है। मौजूदा मानक से सत्यापित करें।
कॉम्स केबल सिलेक्टर क्या करता है?
यह 24 V DC, 4–20 mA, RS-485, Ethernet या PROFINET लिंक के लिए केबल बनावट बताता है, और यह भी कि रन की लंबाई उस इंटरफ़ेस की सीमा के भीतर है या नहीं। यह वातावरण के मुकाबले शीथ, स्क्रीन और बेंडिंग रेडियस भी जाँचता है।
RS-485 सेगमेंट कितना लंबा हो सकता है?
टूल केबल निर्माता की मैनुअल से PROFIBUS DP सेगमेंट की लंबाई दिखाता है: स्टैंडर्ड बस केबल पर 187.5 kbps तक 1000 m, 500 kbps पर 400 m, 1.5 Mbps पर 200 m, और 3 Mbps से ऊपर 100 m। फ़्लेक्सिबल और टॉर्शन केबल के रन छोटे होते हैं।
RS-485 की 32 की सीमा किसे गिनती है?
यूनिट लोड, डिवाइस नहीं। एक यूनिट लोड 12 V के कॉमन-मोड स्ट्रेस पर 1 mA खींचता है। 12 किलोओम से ऊपर इनपुट रेज़िस्टेंस वाला रिसीवर उसका केवल एक हिस्सा दिखाता है, इसलिए एक लाइन 32 से ज़्यादा रिसीवर ले जा सकती है।
RS-485 को कौन सा टर्मिनेशन चाहिए?
टर्मिनेशन रेज़िस्टेंस लाइन के कैरेक्टरिस्टिक इम्पीडेंस के बराबर है। होल्ड किया गया सोर्स हर सिरे पर 120 ओम पर काम करता है, इसलिए उसे अपने केबल से मिलाएँ। इतनी छोटी लाइन जिसे लम्प्ड-पैरामीटर माना जा सके, उसे टर्मिनेशन की ज़रूरत नहीं।
24 V DC और 4–20 mA के लिए कौन सी लंबाई सीमा लागू होती है?
इनमें से किसी के लिए प्रकाशित लंबाई नहीं है। 24 V DC रन वोल्ट ड्रॉप से सीमित होता है, इसलिए 24 V पर AmpSize वोल्टेज ड्रॉप टूल इस्तेमाल करें। 4–20 mA लूप लूप बर्डन और ट्रांसमीटर सप्लाई वोल्टेज से सीमित होता है।
बैकग्राउंड
वे Clauses और Tables जो यह टूल पढ़ता है
- AS/NZS 3000:2018 Table 3.3Nominal minimum cross-sectional area of conductors
- Industrial communications sources, interface limitsLength, screen and construction limits for five industrial interfaces
हर Clause और Table, और उनकी सत्यापन की विधि
Tables आख़िरी बार 26 Sept 2026 को जाँची गईं।
संबंधित टूल
- 4-20 mA लूप के लिए लूप पावर बजटCheck the voltage a 4–20 mA loop leaves the transmitter.AS/NZS 3008.1.2AS/NZS 3008.1.1
- वोल्टेज ड्रॉप कैलकुलेटरCalculate voltage drop on a cable run and check the limit.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- केबल स्क्रीन अर्थिंग सिलेक्टरFind where to earth a screen, drain wire or armour.AS/NZS 3000