ट्रांसफ़ॉर्मर इनरश और उसका ब्रेकर
ट्रांसफ़ॉर्मर के स्विच-ऑन इनरश को उसके ब्रेकर से मिलाकर जाँचें।
Reads AS/NZS 3000:2018. Tables checked 2 Oct 2026.
कोई प्रोजेक्ट आज़माएँ 4
हर जॉब में उदाहरण मान भरे होते हैं। उन्हें अपने मानों से बदलें।
- Stop a transformer tripping its breakerWhy an isolation transformer trips a Type B breaker at switch-on, and what holds.
- Pick a breaker for a site transformerThe breaker and cable for a portable site transformer.
- Check a control transformer breakerWhether a small control transformer on an extra-low voltage secondary holds its breaker.
- Size the breaker for a step-down transformerThe smallest breaker of each type for a single‑phase step-down transformer.
इनपुट
डिफ़ॉल्ट इनपुट के साथ एक कार्य-उदाहरण।
- रेटिंग
- 15 kVA
- फ़ेज़
- थ्री-फ़ेज़
- प्राइमरी वोल्टेज
- 400 V
- द्वितीयक वोल्टेज
- 400 V
- द्वितीयक पर सर्किट
- एक, जिसकी अपनी कोई सुरक्षा नहीं
- इनरश, × पूर्ण लोड धारा
- 12
- इनरश कितनी देर रहता है
- 0.1 s
- ब्रेकर का प्रकार
- कर्व C
- रेटिंग
- 32 A
चालू करते समय ब्रेकर
ट्रिप हो सकता है
- इनरश करंट
- 259.8A
- प्राथमिक पूर्ण लोड धारा
- 21.65A
- सबसे छोटा Type B जो समाए
- 100 A
- सबसे छोटा Type C जो समाए
- 63 A
- सबसे छोटा Type D जो समाए
- 32 A
- द्वितीयक कंडक्टर, कम से कम
- 21.7A
यह परिणाम डिज़ाइन में सहायता के लिए है। इसे मौजूदा मानक से सत्यापित करें।
गणना के चरण
- प्राथमिक पूर्ण लोड धारा21.65A
- इनरश, 0.1 s के लिए 12 × पूर्ण लोड धारा259.8A
- प्रकार C 32 A, विशिष्ट तात्कालिक बैंड से160A
- प्रकार C 32 A, विशिष्ट तात्कालिक बैंड तक320A
- चालू करते समय ब्रेकरपरिणामट्रिप हो सकता है
- सबसे छोटा Type B जो समाए100 A
- सबसे छोटा Type C जो समाए63 A
- सबसे छोटा Type D जो समाए32 A
- द्वितीयक कंडक्टर, कम से कम21.7A
AS/NZS 3000:2018 Cl 4.14.2.2
इस कैलकुलेटर के बारे में
How this is calculated
When a transformer is switched on, its core can draw a large current for a few cycles while the magnetic flux settles. This inrush can be ten or more times the full load current. It lasts about a tenth of a second, and it is often enough to trip the breaker on the primary. This tool checks whether it does, and finds a breaker that rides through it.
The tool takes the primary full load current from the transformer tool, then multiplies it by the inrush multiple you enter, for the time you enter. No standard on hand prints these two figures, so they are your assumptions. Take them from the maker's data sheet. The multiple is a peak, and the tool compares it with the breaker's band, which is given in RMS multiples of the rating, as if it were RMS: that errs towards a trip.
It then places that current on the trip band of the breaker, the same band the MCB trip curve tool draws. The breaker holds when the band's earliest trip is no sooner than the inrush lasts. It trips when the latest trip is sooner, and it may trip in between. For each type, B, C and D, the tool finds the smallest rating that carries the full load current and holds.
With one circuit on the secondary and no protection there, AS/NZS 3000 lets the secondary cable go without its own breaker if it carries the primary current scaled by the voltage ratio. The tool gives that current.
| Step | Table or clause | What it decides |
|---|---|---|
| Full load current | The transformer tool | The current the inrush multiplies |
| Inrush | The multiple and time you enter | The current and time the breaker sees |
| The breaker's band | AS/NZS 3000 Cl 2.5.3.1 and Table 8.1, and a typical band | Holds, may trip or trips |
| The secondary cable | AS/NZS 3000 Cl 4.14.2.2 Exception | The least capacity of an unprotected secondary cable |
| An extra-low voltage transformer | AS/NZS 3000 Cl 4.14.1 Exception 2 | Whether Cl 4.14 applies at all |
Worked examples
- A 15 kVA three‑phase isolation transformer on a C32 draws 259.8 A of inrush, inside the C32's typical instant band, so the breaker may trip at switch-on. A 32 A Type D holds.
- The same transformer on a D32 holds the 259.8 A and passes. The 32 A Type D is also the smallest D that carries the 21.65 A load.
- The same transformer on a B32 fails: the inrush is past the top of the typical instant band and the breaker trips. A 32 A Type D would hold.
- A 3 kVA 230/110 V site transformer on a C16 may trip on its 156.5 A inrush. A 16 A Type D holds, and the 110 V cable needs at least 27.3 A.
- A 10 kVA 400/230 V transformer, 10 × inrush, on a D32 holds and passes. A 32 A Type D is the smallest D that holds.
Limits
The inrush depends on where on the wave the transformer is switched and on the flux left in the core, so it differs from one switch-on to the next. The tool uses one figure for the peak and one for the time. A toroidal transformer can draw much more than a laminated one. A soft-start or inrush limiter changes the figures; enter what the maker gives.
The breaker's band is typical of its type, not a maker's curve. The tool does not check a fuse or a moulded-case breaker.
See also: MCB trip curve, Transformer and Cable size.
सवाल
परिणाम एक डिज़ाइन सहायता है। मौजूदा मानक से सत्यापित करें।
ट्रांसफ़ॉर्मर चालू करने पर अपना ब्रेकर क्यों ट्रिप करता है?
कोर कुछ साइकल के लिए, जब तक उसका फ़्लक्स स्थिर होता है, एक बड़ा मैग्नेटाइज़िंग करंट खींचता है। इनरश फ़ुल लोड करंट का दस गुना या उससे ज़्यादा हो सकता है। अगर वह ब्रेकर के इंस्टेंट बैंड तक पहुँचता है, तो ब्रेकर ट्रिप हो सकता है।
ट्रांसफ़ॉर्मर इनरश करंट कितना बड़ा होता है?
यह डिज़ाइन पर और इस पर निर्भर करता है कि वेव पर कहाँ स्विच किया गया है। लगभग 0.1 s के लिए फ़ुल लोड करंट का 10 से 12 गुना एक आम पहला अनुमान है। टोरॉइडल ट्रांसफ़ॉर्मर इससे ज़्यादा खींच सकता है। असली आँकड़ा निर्माता की डेटा शीट देती है।
कौन सा ब्रेकर कर्व ट्रांसफ़ॉर्मर के लिए ठीक बैठता है?
अक्सर टाइप D, जिसका सामान्य इंस्टेंट बैंड उसकी रेटिंग के 10 गुना से शुरू होता है। टाइप C को उसी इनरश के लिए बड़ी रेटिंग चाहिए, और टाइप B को और भी बड़ी। टूल हर एक का सबसे छोटा ऐसा आकार खोजता है जो टिके।
क्या सेकेंडरी केबल को अपना ब्रेकर चाहिए?
AS/NZS 3000 Cl 4.14.2.2 एक असुरक्षित सेकेंडरी सर्किट को बिना प्रोटेक्शन के छोड़ने देता है, यदि उसकी केबल प्राइमरी रेटेड करंट को प्राइमरी से सेकेंडरी वोल्टेज अनुपात से गुणा करके ले जा सके। अधिक सर्किट हों तो हर एक को प्रोटेक्ट करें।
क्या ब्रेकर बैंड निर्माता का कर्व है?
नहीं। यह इस प्रकार के लिए एक सामान्य बैंड है, वही जो MCB ट्रिप कर्व टूल खींचता है। जहाँ नतीजा ट्रिप हो सकता है, वहाँ निर्माता का कर्व जाँचें या अगली ऊँची रेटिंग चुनें।
वे Clauses और Tables जो यह टूल पढ़ता है
- AS/NZS 3000:2018 Cl 4.14.1Transformers outside Cl 4.14
- AS/NZS 3000:2018 Cl 4.14.2.2Transformer secondary circuits
- AS/NZS 3000:2018 Cl 2.5.3.1Operating points of circuit-breakers and fuses
- AS/NZS 3000:2018 Cl 4.14Transformer secondary circuits
- AS/NZS 3000:2018 Table 8.1Maximum earth fault loop impedance multipliers by MCB curve
हर Clause और Table, और उनकी सत्यापन की विधि
Tables आख़िरी बार 2 Oct 2026 को जाँची गईं।
संबंधित टूल
- ट्रांसफ़ॉर्मर कैलकुलेटरCalculate transformer full load current and impedance.कोई मानक नहीं
- MCB ट्रिप कर्व और केबल सीमाPlot an MCB trip band against the cable it protects.AS/NZS 3000AS/NZS 3008.1.2AS/NZS 3008.1.1
- मांग से ट्रांसफ़ॉर्मर का आकारSize a transformer from the demand, with growth and losses.कोई मानक नहीं