AS/NZS 3000 Cl 7.9: EV charging in NZ

Công cụ tính tiết diện cáp

+5 references

Worked to AS/NZS 3000:2018 and AS/NZS 3008.1.2:2017 (NZ). Tables checked 27 Sept 2026.

A pedestal EV charger beside a townhouse driveway, with a car parked next to it.

An EV charger is a long duration load on a domestic switchboard. Clause 7.9 of AS/NZS 3000:2018 is the part of the standard written for it.

The question

A 32 A charger goes on a garage wall, 25 m of cable from the switchboard. What conductor size carries it, and which clauses set the surrounding requirements?

The inputs

  • 230 V, single phase, 32 A design current
  • Power factor 1.0
  • Run length 25 m
  • Installation method: partly in insulation
  • Wiring enclosure: none
  • Ambient temperature 35 °C, one circuit on the route
  • Copper, PVC, multicore, one cable
  • Voltage drop limit 5 %
  • Device: curve C, 32 A, with an external loop impedance of 0.35 Ω

The clauses

Cl 7.9.2 covers the supply arrangement for electric vehicle charging equipment. A charger draws close to its rated current for hours. The clause therefore treats a charger as its own circuit, not as an addition to a socket‑outlet circuit.

Cl 7.9.3 covers residual current protection for the charging circuit. Charger electronics can pass d.c. residual current, and the RCD type has to suit what the equipment produces. The cable size tool does not choose an RCD product for this circuit. The RCD selection tool reports the requirement and the trip limits. It also reports the type where the clause names one.

Cl 7.9.4 covers a charging circuit outside a domestic installation. It sets that circuit's own Type B device. Cl 7.9.3.3(e) sets the isolating switch instead.

Demand is a separate question. Table C1 of AS/NZS 3000:2018 places electric vehicle charging in group J(iv) for a domestic installation. Table C2 places it in group C(ii) for other installations. The maximum demand tool applies whichever group the chosen table gives.

Amendment 1 revised Clause 7.9. Check the amendment status of the copy in front of you before citing a subclause.

The steps

The cable size tool sizes against the derated capacity first.

At 35 °C the ambient factor is 0.94. One circuit gives a grouping factor of 1, so the total derating factor is 0.94.

Dividing 32 A by 0.94 gives a required tabulated current of 34.04 A. The tool then walks the standard sizes in AS/NZS 3008.1.2:2017 Table 13 and takes the first that passes every check.

6 mm² carries 31.96 A after derating, which falls under the 32 A design current. It fails on capacity.

10 mm² carries 44.18 A after derating. Voltage drop over 25 m comes to 1.55 %, inside the 5 % limit. The 32 A curve C device sits correctly against both the load and the cable. Loop impedance reaches 0.55 Ω, and the earth conductor for that active is 4 mm².

A 32 A circuit over 25 m on 10 mm²Supply230 VDevice32 A25 m10 mm² CuLoad32 A
A 32 A circuit over 25 m on 10 mm²

The result

The circuit needs 10 mm² copper. A 32 A number suggests 6 mm² on paper. That cable falls one size short here, because the insulation contact and the 35 °C ambient take the rating down.

Two inputs move this answer most. The installation method sets the base rating. A charger cable that leaves a wall cavity and crosses a ceiling changes method partway. The ambient temperature matters for the same reason, since a roof space in summer runs hotter than 35 °C.

The cable is one part of the design. Cl 7.9.3 still governs the residual current device, and Cl 7.9.3.3(e) still governs the isolating switch. This tool outputs neither.

This page is a design aid. Verify every value against the current edition of the standard.

See also: 22 kW EV charger amps at 400 V three‑phase, EV charger cable size for a 7 kW 32 A circuit and Current-carrying capacity and derating.

Thử với các đầu vào này

Nhiệt độ môi trường
35 °C
Lõi dây
Nhiều lõi
Đường đặc tính của thiết bị
Đường đặc tính C
Kiểm tra thiết bị bảo vệ
Có
Các mạch đi chung nhóm
1
Cách điện
PVC 75 °C
Chiều dài đoạn dây
25 m
Dòng thiết kế
32 A
Vật liệu
Đồng
Phương pháp lắp đặt
Partly in insulation
Cáp song song
1
Hệ số công suất
1
Các pha
Một pha
Định mức thiết bị
32 A
Giới hạn sụt áp
5 %
Điện áp
230 V
Vỏ bao che đi dây
Không có vỏ bọc đi dây
Tổng trở ngoài Ze
0.35 Ω
Mở công cụ tính với các dữ liệu nhập này

Tiếp theo

Các khái niệm đứng sau nó

Thêm ví dụ tính toán

AmpSize là công cụ hỗ trợ thiết kế. Hãy đối chiếu kết quả với tiêu chuẩn hiện hành.