कुल वोल्टेज ड्रॉप कैलकुलेटर
मेन्स, सबमेन और फ़ाइनल का ड्रॉप जोड़ें, और उसे 5 % के मुकाबले जाँचें।
Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 1 Oct 2026.
कोई प्रोजेक्ट आज़माएँ 4
हर जॉब में उदाहरण मान भरे होते हैं। उन्हें अपने मानों से बदलें।
- Check the total voltage drop to a shedThe mains, the shed submain and a final subcircuit added against 5 %.
- Find the drop left for a new circuitWhat 25 m of mains and a 40 m submain leave for a final subcircuit.
- Add a three phase submain to a finalThree phase mains and submain with a single phase final, added by percent.
- Use the 7 % substation limitA factory fed from its own transformer, checked against 7 %.
इनपुट
डिफ़ॉल्ट इनपुट के साथ एक कार्य-उदाहरण।
- सप्लाई का पॉइंट
- नेटवर्क आपूर्ति (5 % सीमा)
- मानक
- NZ · AS/NZS 3008.1.2
- पावर फ़ैक्टर
- 0.9
- रन के हिस्से, आपूर्ति के बिंदु से
- 3 पंक्तियाँ
कुल वोल्टेज ड्रॉप
4.25%
- वोल्टेज ड्रॉप सीमा
- 5%
- मेन और सबमेन
- 1.98%
- अंतिम उप-सर्किट के लिए छोड़ा गया
- 3.02%
- उपयोग के स्थान पर छोड़ा गया
- 0.75%
यह परिणाम डिज़ाइन में सहायता के लिए है। इसे मौजूदा मानक से सत्यापित करें।
गणना के चरण
- भाग 1उपभोक्ता मेन
- भाग 1 mV/A·m2.6mV/A·m
AS/NZS 3008.1.2:2017 Cl 4.5
- भाग 1 वोल्टेज ड्रॉप2.6V
- भाग 1 वोल्टेज ड्रॉप, 230 V का प्रतिशत1.13%
AS/NZS 3000:2018 App C Para C4.1
- भाग 1 के बाद चालू कुल1.13%
AS/NZS 3000:2018 App C Para C4.1
- भाग 2सबमेन
- भाग 2 mV/A·m4.09mV/A·m
AS/NZS 3008.1.2:2017 Cl 4.5
- भाग 2 वोल्टेज ड्रॉप1.96V
- भाग 2 वोल्टेज ड्रॉप, 230 V का प्रतिशत0.85%
AS/NZS 3000:2018 App C Para C4.1
- भाग 2 के बाद चालू कुल1.98%
AS/NZS 3000:2018 App C Para C4.1
- भाग 3अंतिम सबसर्किट
- भाग 3 mV/A·m16.31mV/A·m
AS/NZS 3008.1.2:2017 Cl 4.5
- भाग 3 वोल्टेज ड्रॉप5.22V
- भाग 3 वोल्टेज ड्रॉप, 230 V का प्रतिशत2.27%
AS/NZS 3000:2018 App C Para C4.1
- भाग 3 के बाद चालू कुल4.25%
AS/NZS 3000:2018 App C Para C4.1
- वोल्टेज ड्रॉप सीमा5%
AS/NZS 3000:2018 Cl 3.6.2
- कुल वोल्टेज ड्रॉपपरिणाम4.25%
AS/NZS 3000:2018 Cl 3.6.2
- मेन और सबमेन1.98%
- अंतिम उप-सर्किट के लिए छोड़ा गया3.02%
AS/NZS 3000:2018 Cl 3.6.2
- उपयोग के स्थान पर छोड़ा गया0.75%
इस कैलकुलेटर के बारे में
How this is calculated
AS/NZS 3000 limits the voltage drop from the point of supply to any point in the installation. It is one limit for the whole run, not one per circuit. So the drop in the consumer mains, every submain and the final subcircuit must add up to no more than the limit. This tool adds them.
You enter each part of the run in order from the point of supply: the consumer mains, up to three submains and the final subcircuit. For each part you give the phases, the current, the route length and the cable. The tool works each part with the same calculation as the voltage drop tool. It reads the cable's resistance and reactance from AS/NZS 3008.1, finds the mV/A·m at the power factor, and gives the drop in volts.
Each drop is then taken as a percent of that part's own circuit voltage: 230 V for single phase and 400 V for three phase. Appendix C of AS/NZS 3000 adds the percents directly, so a three‑phase submain adds to a single‑phase final subcircuit with no conversion. The running total is the drop at the end of each part.
The limit is 5 % of the nominal voltage. Where the point of supply is the low voltage terminals of a substation on the premises, which supplies only this installation, it is 7 %. The clause sets no split between the parts. The tool shows what the mains and submains take, and what that leaves for a final subcircuit from the last board.
| Step | Table or clause | What it decides |
|---|---|---|
| Resistance and reactance of each part | AS/NZS 3008.1 Tables 34 and 35 | The impedance of the cable |
| Drop of each part | AS/NZS 3008.1 Cl 4.5 | The mV/A·m and the drop in volts |
| Percent of each part | AS/NZS 3000 App C Para C4.1 | The drop as a percent of its circuit voltage, added part by part |
| The limit | AS/NZS 3000 Cl 3.6.2 | The most the total may be from the point of supply |
| A substation on the premises | AS/NZS 3000 Cl 3.6.2 Exception 3 | The higher limit where it applies |
| A load spread along a final subcircuit | AS/NZS 3000 Cl 3.6.2 Exception 1 | The current you may use for that part |
Worked examples
- A house: mains, a garage submain and a socket‑outlet circuit. The total voltage drop is 4.25 %. The mains and submain take 1.98 %, which leaves 3.02 % for a final subcircuit.
- A shed 30 m from the house. The total voltage drop is 4.83 %, inside the 5 % limit but close to it. The upstream parts take 3.13 %, which leaves 1.87 % for a final subcircuit.
- A factory on its own substation. The total voltage drop is 6.27 % against the 7 % limit. The mains and submain take 4.38 %, which leaves 2.62 % for a final subcircuit.
- A farm workshop 60 m from the house. The total voltage drop is 10.82 %, so the run fails. The mains and submain take 8.55 % on their own, which leaves −3.55 % for a final subcircuit. A larger submain is the fix.
Limits
The tool works a.c. runs at 230 V and 400 V nominal. It does not check extra-low voltage circuits, which Cl 3.6.2 leaves out, or a stand-alone system, which Exception 4 judges on the utilisation voltage. Single‑core parts use the highest reactance the table gives for the formation. Use the voltage drop tool for one run with a known formation or an unbalanced neutral.
Motor starting and other short transient drops are not part of the limit. Check those against the equipment.
See also: Voltage drop, The 5 % voltage drop limit from supply to load and Total voltage drop: mains, submain and final.
सवाल
परिणाम एक डिज़ाइन सहायता है। मौजूदा मानक से सत्यापित करें।
क्या 5 % वोल्टेज ड्रॉप हर सर्किट के लिए है या पूरे इंस्टॉलेशन के लिए?
पूरा इंस्टॉलेशन। AS/NZS 3000 Cl 3.6.2 सप्लाई के बिंदु से किसी भी बिंदु तक ड्रॉप को सीमित करता है। उपभोक्ता मेन्स, सबमेन और फ़ाइनल सबसर्किट एक 5 % साझा करते हैं, इसलिए यह टूल उन्हें जोड़ता है।
क्या मेन्स और फ़ाइनल सबसर्किट के बीच 2 % और 3 % का बँटवारा है?
AS/NZS 3000 में नहीं। Cl 3.6.2 एक सीमा तय करता है, कोई बँटवारा नहीं। डिज़ाइनर अक्सर बँटवारा प्लान करते हैं, पर Clause केवल इतना माँगता है कि कुल सीमा के भीतर रहे। टूल दिखाता है कि मेन्स और सबमेन क्या लेते हैं और क्या बचता है।
सिंगल-फ़ेज़ फ़ाइनल सबसर्किट में थ्री-फ़ेज़ सबमेन कैसे जोड़ूँ?
प्रतिशत के अनुसार। हर भाग को उसके अपने सर्किट वोल्टेज के प्रतिशत के रूप में निकाला जाता है: थ्री-फ़ेज़ के लिए 400 V और सिंगल-फ़ेज़ के लिए 230 V। AS/NZS 3000 का Appendix C उन प्रतिशतों को सीधे जोड़ता है।
सीमा 7 % कब होती है?
जब सप्लाई का बिंदु उसी परिसर पर सबस्टेशन के लो वोल्टेज टर्मिनल हों जो सिर्फ़ इसी इंस्टॉलेशन को सप्लाई करता है। अपना सबस्टेशन चुनें, तो टूल 7 % इस्तेमाल करता है।
हर पार्ट के लिए मुझे कौन सा करंट इस्तेमाल करना चाहिए?
हर पार्ट की अधिकतम मांग, उसका कनेक्टेड लोड, या उसकी प्रोटेक्टिव डिवाइस रेटिंग, जो भी आपको पता हो। जिस फ़ाइनल सबसर्किट पर लोड उसके साथ फैला हो, वह डिवाइस रेटिंग का आधा इस्तेमाल कर सकता है।
हल किए गए उदाहरण
बैकग्राउंड
वे Clauses और Tables जो यह टूल पढ़ता है
- AS/NZS 3000:2018 App C Para C4.1Adding voltage drop by percent
- AS/NZS 3000:2018 Cl 3.6.2Voltage drop limit
- AS/NZS 3000:2018 Cl 3.6.2Voltage drop limit from the point of supply, and how the parts of an installation add
- AS/NZS 3008.1.2:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2025 Table 4.1(A), 4.1(B), 4.5(A), 4.5(B)Reactance at 50 Hz and a.c. resistance at 50 Hz
हर Clause और Table, और उनकी सत्यापन की विधि
Tables आख़िरी बार 1 Oct 2026 को जाँची गईं।
संबंधित टूल
- केबल आकार कैलकुलेटरFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- वोल्टेज ड्रॉप कैलकुलेटरCalculate voltage drop on a cable run and check the limit.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- अधिकतम सर्किट लंबाई कैलकुलेटरLongest run that voltage drop and the fault loop allow.AS/NZS 3000AS/NZS 3008.1.2