स्विचबोर्ड के लिए टेस्ट शेड्यूल
हर टेस्ट की सीमा के साथ बोर्ड टेस्ट शीट प्रिंट करें।
Reads Electricity (Safety) Regulations 2010, AS/NZS 3000:2018 and AS/NZS 3017:2022. Tables checked 1 Oct 2026.
कोई प्रोजेक्ट आज़माएँ 4
हर जॉब में उदाहरण मान भरे होते हैं। उन्हें अपने मानों से बदलें।
- Print the test sheet for a house boardSix circuits with their tests in order and the pass limits.
- Test a workshop board with three‑phase socketsAdds the phase sequence test to the three‑phase socket circuit.
- Make an Australian test sheetA house board where each RCD must operate, with no trip time.
- Mark a circuit for the reduced test voltageA data rack circuit tested at the lower insulation voltage.
इनपुट
डिफ़ॉल्ट इनपुट के साथ एक कार्य-उदाहरण।
- देश
- न्यूज़ीलैंड
- बोर्ड का नाम
- नहीं बताया गया
- अंतिम सबसर्किट
- 6 पंक्तियाँ
शीट पर सर्किट
6
- क्रम में परीक्षण
- 7
- मुख्य अर्थ और बॉन्डिंग, अधिकतम
- 0.5Ω
- Table 8.1 में पंक्ति न होने वाले सर्किट
- 0
- टेस्ट का क्रम
- De-energized, earth continuity, insulation, polarity, phase sequence, Zs, RCD
यह परिणाम डिज़ाइन में सहायता के लिए है। इसे मौजूदा मानक से सत्यापित करें।
गणना के चरण
- परीक्षण 1ऊर्जा-रहित होने की जांच
AS/NZS 3017:2022 Cl 4.3
- परीक्षण 2अर्थ निरंतरता
AS/NZS 3017:2022 Cl 4.4
- परीक्षण 3इन्सुलेशन रेज़िस्टेंस
AS/NZS 3017:2022 Cl 4.5
- परीक्षण 4ध्रुवता और सही सर्किट कनेक्शन
AS/NZS 3017:2022 Cl 4.6
- परीक्षण 4बहु-फेज़ सॉकेट-आउटलेट का फेज़ क्रम
AS/NZS 3017:2022 Cl 4.7
- परीक्षण 5अर्थ फॉल्ट-लूप इम्पीडेंस
AS/NZS 3017:2022 Cl 4.8
- परीक्षण 6RCD संचालन
AS/NZS 3017:2022 Cl 4.9
- परीक्षण 7असफल परीक्षण और उससे पहले के वे परीक्षण दोबारा करें जिन्हें उसने प्रभावित किया हो सकता है
AS/NZS 3017:2022 Cl 4.2.2
- सर्किट 1 इंसुलेशन रेज़िस्टेंस, न्यूनतम1MΩ
AS/NZS 3000:2018 Cl 8.3.6
- सर्किट 1 अर्थ कंटिन्यूटी Re, अधिकतम1Ω
AS/NZS 3000:2018 Table 8.2
- सर्किट 1 अर्थ फ़ॉल्ट-लूप इम्पीडेंस, अधिकतम3.1Ω
AS/NZS 3000:2018 Table 8.1
- सर्किट 1 Rphe, अधिकतम2Ω
AS/NZS 3000:2018 Table 8.2
- सर्किट 1 RCD ट्रिप समय, 30 mA पर, अधिकतम300ms
Electricity (Safety) Regulations 2010 reg 24
- सर्किट 2 इंसुलेशन रेज़िस्टेंस, न्यूनतम1MΩ
AS/NZS 3000:2018 Cl 8.3.6
- सर्किट 2 अर्थ कंटिन्यूटी Re, अधिकतम0.5Ω
AS/NZS 3000:2018 Table 8.2
- सर्किट 2 अर्थ फ़ॉल्ट-लूप इम्पीडेंस, अधिकतम1.5Ω
AS/NZS 3000:2018 Table 8.1
- सर्किट 2 Rphe, अधिकतम1Ω
AS/NZS 3000:2018 Table 8.2
- सर्किट 2 RCD ट्रिप समय, 30 mA पर, अधिकतम300ms
Electricity (Safety) Regulations 2010 reg 24
- सर्किट 3 इंसुलेशन रेज़िस्टेंस, न्यूनतम1MΩ
AS/NZS 3000:2018 Cl 8.3.6
- सर्किट 3 अर्थ कंटिन्यूटी Re, अधिकतम0.5Ω
AS/NZS 3000:2018 Table 8.2
- सर्किट 3 अर्थ फ़ॉल्ट-लूप इम्पीडेंस, अधिकतम1.5Ω
AS/NZS 3000:2018 Table 8.1
- सर्किट 3 Rphe, अधिकतम1Ω
AS/NZS 3000:2018 Table 8.2
- सर्किट 3 RCD ट्रिप समय, 30 mA पर, अधिकतम300ms
Electricity (Safety) Regulations 2010 reg 24
- सर्किट 4 इंसुलेशन रेज़िस्टेंस, न्यूनतम1MΩ
AS/NZS 3000:2018 Cl 8.3.6
- सर्किट 4 अर्थ कंटिन्यूटी Re, अधिकतम0.5Ω
AS/NZS 3000:2018 Table 8.2
- सर्किट 4 अर्थ फ़ॉल्ट-लूप इम्पीडेंस, अधिकतम1.5Ω
AS/NZS 3000:2018 Table 8.1
- सर्किट 4 Rphe, अधिकतम1Ω
AS/NZS 3000:2018 Table 8.2
- सर्किट 4 RCD ट्रिप समय, 30 mA पर, अधिकतम300ms
Electricity (Safety) Regulations 2010 reg 24
- सर्किट 5 इंसुलेशन रेज़िस्टेंस, न्यूनतम1MΩ
AS/NZS 3000:2018 Cl 8.3.6
- सर्किट 5 अर्थ कंटिन्यूटी Re, अधिकतम0.5Ω
AS/NZS 3000:2018 Cl 8.3.5
- सर्किट 5 अर्थ फ़ॉल्ट-लूप इम्पीडेंस, अधिकतम1Ω
AS/NZS 3000:2018 Table 8.1
- सर्किट 6 इंसुलेशन रेज़िस्टेंस, न्यूनतम1MΩ
AS/NZS 3000:2018 Cl 8.3.6
- सर्किट 6 अर्थ कंटिन्यूटी Re, अधिकतम0.5Ω
AS/NZS 3000:2018 Table 8.2
- सर्किट 6 अर्थ फ़ॉल्ट-लूप इम्पीडेंस, अधिकतम1.5Ω
AS/NZS 3000:2018 Table 8.1
- सर्किट 6 Rphe, अधिकतम1Ω
AS/NZS 3000:2018 Table 8.2
- मुख्य अर्थ और बॉन्डिंग, अधिकतम0.5Ω
AS/NZS 3000:2018 Cl 8.3.5
इस कैलकुलेटर के बारे में
How this is calculated
You list the final subcircuits of one board: what each supplies, its protective device and rating, its active conductor, single or three phase, and its RCD. The tool turns the list into the sheet you test from.
The tests follow the preferred order of the verification standard's sequence figure. First prove the circuit de-energized. Then test earth continuity, insulation resistance, and polarity with the correct connection of each circuit. A circuit with three‑phase socket‑outlets also takes the phase sequence test, so every outlet of a type turns a motor the same way. Then the earth fault-loop impedance, and last the operation of each RCD. If a test fails, fix the fault and repeat that test and any earlier one it may have upset.
Each circuit carries the limits its readings are judged against. They come from the wiring rules, through the same code the test results tool uses: the insulation resistance and its test voltage, the earth continuity Re and the Rphe from the subcircuit resistance table, and the earth fault-loop impedance from the loop impedance table, at a 0.4 s disconnection time. Where the resistance table has no row, Re falls back to the main earth figure, and the tool says so.
An RCD must operate at about its rated residual current and disconnect the circuit. In New Zealand the sheet also holds it to the regulations' trip time at that current. In Australia the sheet states no time, since the verification standard prints none.
| Step | Table or clause | What it decides |
|---|---|---|
| Order of tests | AS/NZS 3017 Figure 4.1 | The sequence on the sheet |
| Repeat after a fix | AS/NZS 3017 Cl 4.2.2 | Which tests to run again |
| Insulation resistance | Cl 8.3.6 | The least resistance and the test voltage |
| Earth continuity and Rphe | Table 8.2 | The most each conductor may read |
| Earth fault-loop impedance | Table 8.1 | The most Zs may read |
| Phase sequence | AS/NZS 3017 Cl 4.7 | Which circuits take it |
| RCD | AS/NZS 3017 Cl 4.9.4 and reg 24 | What the RCD must do, and the NZ trip time |
Worked examples
- A New Zealand house board. The sheet holds 6 circuits. The 10 A lighting circuit reads Zs at most 3.1 Ω, and each 30 mA RCD trips within 300 ms.
- An Australian house board. The same 6 circuits, and each RCD must operate at about 30 mA; the sheet states no trip time.
- A workshop board. The sheet holds 4 circuits. The three‑phase socket circuit takes the phase sequence test, and the D20 compressor reads Zs at most 0.9 Ω.
Limits
The sheet sets out the tests and the limits; it does not judge a reading. Put a reading into the test results tool to check it, or use it for a fuse circuit at a 5 s disconnection time. The sheet covers final subcircuits: test the main earthing conductor and the bonding against their own limit, shown on the sheet. It does not replace the visual inspection the standard asks for first.
See also: The order of verification tests, A test sheet for a house board and Test Results.
सवाल
परिणाम एक डिज़ाइन सहायता है। मौजूदा मानक से सत्यापित करें।
नई इंस्टॉलेशन की टेस्टिंग किस क्रम में करनी चाहिए?
AS/NZS 3017 Figure 4.1 एक पसंदीदा क्रम तय करता है: पहले उसका डी-एनर्जाइज़्ड होना साबित करें, फिर अर्थ कंटिन्युइटी, इंसुलेशन रेज़िस्टेंस, पोलैरिटी और कनेक्शन, अर्थ फ़ॉल्ट-लूप इम्पीडेंस, और आख़िर में RCD। बाद में मिला फ़ॉल्ट पहले के टेस्ट को बिगाड़ सकता है, इसलिए सुधार के बाद उन्हें दोहराएँ।
पास सीमाएँ कहाँ से आती हैं?
AS/NZS 3000 से: Cl 8.3.6 के अनुसार इंसुलेशन रेज़िस्टेंस, Table 8.2 के अनुसार अर्थ कंटिन्युइटी Re और Rphe, और Table 8.1 के अनुसार अर्थ फ़ॉल्ट-लूप इम्पीडेंस। ये वही सीमाएँ हैं जिनके मुकाबले टेस्ट परिणाम टूल कोई रीडिंग जाँचता है।
RCD को कौन सा ट्रिप टाइम चाहिए?
न्यूज़ीलैंड में शीट 30 mA RCD को उसके रेटेड रेज़िडुअल करंट पर Electricity (Safety) Regulations की सीमा तक रखती है। AS/NZS 3017 माँगता है कि हर RCD लगभग अपने रेटेड करंट पर ट्रिप करे और सर्किट डिस्कनेक्ट करे, और कोई समय नहीं छापता, इसलिए ऑस्ट्रेलियाई शीट कोई समय नहीं बताती।
किन सर्किटों में फ़ेज़ सीक्वेंस टेस्ट चाहिए?
मल्टी-फ़ेज़ सॉकेट-आउटलेट वाला सर्किट, ताकि एक ही प्रकार के हर आउटलेट का फ़ेज़ सीक्वेंस एक जैसा हो (AS/NZS 3017 Cl 4.7)। उस सर्किट पर थ्री-फ़ेज़ सॉकेट-आउटलेट वाला बॉक्स टिक करें।
क्या मैं शीट प्रिंट कर सकता हूँ?
हाँ। PDF हर सर्किट को उसकी सीमाओं और इंसुलेशन, Re, Zs, पोलैरिटी और RCD रीडिंग के खाली बॉक्स के साथ छापता है, जिन्हें साइट पर भरना है।
हल किए गए उदाहरण
- A circuit chart for a house board with solarThe circuit chart and labels for a six-circuit house board with a solar inverter: ways, devices, RCDs, MAIN SWITCH, MAIN SWITCH SOLAR and a shared neutral.
- A test sheet for a house boardA test sheet for a six-circuit New Zealand house board, with the tests in the AS/NZS 3017 order and the limit for each reading, then the Australian sheet.
बैकग्राउंड
वे Clauses और Tables जो यह टूल पढ़ता है
- AS/NZS 3000:2018 Cl 8.3.5Earth continuity test
- AS/NZS 3000:2018 Cl 8.3.6Insulation resistance test
- AS/NZS 3017:2022 Cl 4.2.2Order of tests
- AS/NZS 3017:2022 Cl 4.3Test for de-energized
- AS/NZS 3017:2022 Cl 4.4Earth continuity test method
- AS/NZS 3017:2022 Cl 4.5Insulation resistance test method
- AS/NZS 3017:2022 Cl 4.6Polarity and circuit connections test method
- AS/NZS 3017:2022 Cl 4.7Phase sequence test method
हर Clause और Table, और उनकी सत्यापन की विधि
Tables आख़िरी बार 1 Oct 2026 को जाँची गईं।
संबंधित टूल
- इलेक्ट्रिकल सर्टिफ़िकेशन मार्गFind the paperwork for a job in NZ or Australia.Electricity (Safety) Regulations 2010
- टेस्ट परिणाम चेकरCheck measured test results against Section 8 limits.AS/NZS 3000AS/NZS 3017Electricity (Safety) Regulations 2010
- स्विचबोर्ड सर्किट चार्टMake a board circuit chart and the labels it needs.AS/NZS 3000