हार्मोनिक्स, न्यूट्रल करंट और k फ़ैक्टर
स्पेक्ट्रम से THD, न्यूट्रल करंट और k फ़ैक्टर।
Reads AS/NZS 3000:2018, AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3008.1.1:2017 (AU). Tables checked 2 Oct 2026.
कोई प्रोजेक्ट आज़माएँ 4
हर जॉब में उदाहरण मान भरे होते हैं। उन्हें अपने मानों से बदलें।
- Find the harmonic neutral current of an officeThe neutral current of an office floor full of computers, from its spectrum.
- Find the K-factor for a drive transformerThe K-factor of six-pulse drives, for the transformer that feeds them.
- Check an LED lighting circuit for harmonicsWhether a cable for LED drivers is picked on its neutral current.
- Neutral current with some electronic loadThe neutral of a board where electronics are 30 % of the load.
इनपुट
डिफ़ॉल्ट इनपुट के साथ एक कार्य-उदाहरण।
- क्षेत्राधिकार
- NZ · AS/NZS 3008.1.2
- फ़ेज़ धारा, ट्रू RMS
- 100 A
- Third harmonic
- 35 %
- Fifth harmonic
- 20 %
- Seventh harmonic
- 10 %
- Ninth harmonic
- 5 %
- Eleventh harmonic
- 4 %
- Thirteenth harmonic
- 3 %
- Fifteenth harmonic
- 2 %
- फ़ेज़ लोड का वह हिस्सा जो हार्मोनिक्स पैदा करता है
- 100 %
- असंतुलित धारा
- 0 A
ट्रिपलेन न्यूट्रल
97.88A
- धारा का कुल हार्मोनिक विरूपण
- 42.18%
- K-कारक
- 3.59
- Table 2 कमी कारक
- ×0.86
- केबल का चयन किया गया
- फ़ेज़ धारा
- केबल चुनने के लिए धारा
- 116.28A
- Cl 3.5.2(b)(i) न्यूट्रल के लिए न्यूनतम
- 38.86A
यह परिणाम डिज़ाइन में सहायता के लिए है। इसे मौजूदा मानक से सत्यापित करें।
गणना के चरण
- धारा का कुल हार्मोनिक विरूपण42.18%
- मूल धारा92.14A
- ट्रिपलेन हार्मोनिक, √(h3² + h9² + h15²)35.41%
- ट्रिपलेन न्यूट्रलपरिणाम97.88A
- तीसरा हार्मोनिक, फ़ेज़ धारा का प्रतिशत32.25%
AS/NZS 3008.1.2:2017 Table 2
- Table 2 कमी कारक×0.86
AS/NZS 3008.1.2:2017 Table 2
- अकेले तीसरे हार्मोनिक से न्यूट्रल धारा96.75A
AS/NZS 3008.1.2:2017 Cl 3.5.9
- केबल चुनने के लिए धारा116.28A
AS/NZS 3008.1.2:2017 Cl 3.5.9
- एक फ़ेज़ की हार्मोनिक धारा, तीसरी और उससे ऊपर38.86A
- Cl 3.5.2(b)(i) न्यूट्रल के लिए न्यूनतम38.86A
AS/NZS 3000:2018 Cl 3.5.2(b)(i)
- K-कारक3.59
इस कैलकुलेटर के बारे में
How this is calculated
Electronic loads draw current in pulses, not as a smooth wave. A power quality analyser splits that current into the fundamental and its harmonics, each shown as a percent of the fundamental. The tool takes the true rms phase current and that spectrum, from the third to the fifteenth order.
The total harmonic distortion is the rms of all the harmonic percents. The fundamental current is the rms current divided by the square root of one plus the distortion squared.
The third, ninth and fifteenth harmonics are the triplens. In the three phases they are in step, so they add in the neutral instead of cancelling. With equal phases the neutral carries three times one phase's triplen current. That is the tool's main answer.
AS/NZS 3008.1 Table 2 bands the third harmonic as a percent of the phase current. So the tool converts the analyser's percent of the fundamental to a percent of the rms current. It reads the band through the cable size tool's own path, and gives the reduction factor, whether the cable is picked on the phase or the neutral current, and the current to carry to cable size.
AS/NZS 3000 Cl 3.5.2(b)(i) gives a minimum for the neutral of a substantial harmonic load: the out-of-balance current plus one phase's harmonic current. Size the neutral for the larger of it and the triplen figure. AmpSize reads the harmonic current as the rms of the third and higher orders. Note 1 sets what substantial means.
The K-factor weights each harmonic by its order squared, because eddy current loss in a transformer rises with frequency squared. A clean load gives 1.
| Step | Table or clause | What it decides |
|---|---|---|
| Distortion | The rms of the harmonic percents | The THD and the fundamental current |
| Triplen neutral | Three times one phase's triplens | The neutral current of three equal phases |
| Third harmonic band | Table 2 | The reduction factor and the basis the cable is picked on |
| Neutral of the third harmonic | Cl 3.5.9 | The current the cable is picked on above the middle band |
| Clause neutral | Cl 3.5.2(b)(i) | The out-of-balance current plus one phase's harmonic current |
| Substantial load | Cl 3.5.2(b)(i) Note 1 | Whether the clause figure applies |
| K-factor | Each order squared, weighted by its share | The transformer K rating to pick at or above |
Worked examples
- An office floor of 80 A with 40 % third harmonic puts 87.16 A in the neutral, more than a phase. The current has 49.34 % THD and a K-factor of 4.37.
- Six-pulse drives drawing 150 A put only 13.43 A in the neutral, as their harmonics are mostly fifth and seventh. The current has 35.14 % THD and a K-factor of 5.12.
- An LED lighting circuit of 40 A puts 64.28 A in the neutral. The current has 89.16 % THD and a K-factor of 10.01.
- A 60 A board where electronics are 30 % of the load puts 58.73 A of triplens in the neutral if every load had this spectrum. The current has 42.18 % THD and a K-factor of 3.59. Below 40 % the clause figure does not apply.
Limits
The tool assumes three equal phases with the same spectrum. A real board has a mix. Enter the worst phase's readings for a safe answer.
It does not work voltage distortion, resonance with power factor capacitors or filter design. Those need the supply's impedance and a harmonic study.
See also: Neutral current, Cable size and Transformer.
सवाल
परिणाम एक डिज़ाइन सहायता है। मौजूदा मानक से सत्यापित करें।
हार्मोनिक न्यूट्रल करंट की गणना कैसे करें?
तीनों फ़ेज़ की तीसरी, नौवीं और पंद्रहवीं हार्मोनिक एक साथ चलती हैं, इसलिए वे न्यूट्रल में जुड़ती हैं। बराबर फ़ेज़ पर न्यूट्रल एक फ़ेज़ के ट्रिपलेन करंट का तीन गुना ले जाता है। टूल इसे फ़ेज़ करंट और स्पेक्ट्रम से निकालता है।
करंट का THD क्या है?
टोटल हार्मोनिक डिस्टॉर्शन फ़ंडामेंटल पर सारे हार्मोनिक करंट का rms है, प्रतिशत में। एक एनालाइज़र हर ऑर्डर को फ़ंडामेंटल के प्रतिशत के रूप में दिखाता है। टूल वे लेता है और THD और फ़ंडामेंटल करंट देता है।
k फ़ैक्टर क्या है?
यह हर हार्मोनिक को उसके ऑर्डर के वर्ग से भारित करता है, क्योंकि ट्रांसफ़ॉर्मर में एडी करंट लॉस फ़्रीक्वेंसी के वर्ग के साथ बढ़ता है। साफ़ लोड K-1 होता है। आँकड़े के बराबर या उससे ऊपर का ट्रांसफ़ॉर्मर K रेटिंग चुनें। रेटिंग के स्टेप AmpSize के पास मौजूद किसी मानक में नहीं हैं।
केबल आकार कब न्यूट्रल करंट पर जाता है?
AS/NZS 3008.1 Table 2 तीसरे हार्मोनिक को फ़ेज़ करंट के प्रतिशत के बैंड में रखती है। 33 % से ऊपर केबल न्यूट्रल करंट के आधार पर चुनी जाती है। टूल फ़ैक्टर, आधार और वह करंट देता है जिसे केबल आकार टूल में ले जाना है।
AS/NZS 3000 हार्मोनिक लोड से क्या माँगता है?
Cl 3.5.2(b)(i) न्यूट्रल के लिए तीसरी और उससे ऊपर की हार्मोनिक करंट को अनबैलेंस करंट में जोड़ता है, और सबसे ऊँचे फ़ेज़ के हार्मोनिक करंट का 100 % लेता है। Note 1 किसी फ़ेज़ के लोड के 40 % या उससे अधिक हार्मोनिक लोड को काफ़ी कहता है।
वे Clauses और Tables जो यह टूल पढ़ता है
- AS/NZS 3000:2018 Cl 3.5.2(b)Neutral of a multiphase circuit
- AS/NZS 3008.1.2:2017 Cl 3.5.9Third harmonic current in the neutral
- AS/NZS 3000:2018 Cl 3.5.2Neutral conductor of a circuit
- AS/NZS 3008.1.2:2017 Table 2Reduction factors for harmonic currents in 4- and 5‑core cables
- AS/NZS 3008.1.1:2017 Table 2Reduction factors for harmonic currents in 4- and 5‑core cables
हर Clause और Table, और उनकी सत्यापन की विधि
Tables आख़िरी बार 2 Oct 2026 को जाँची गईं।