Công cụ tính mức ngắn mạch
Dòng ngắn mạch dự kiến tại một tủ điện, tính từ nguồn cấp của tủ đó.
Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.
Thử một công việc 8
Mỗi công việc điền sẵn giá trị ví dụ. Hãy thay bằng giá trị của bạn.
- Find the fault level at a sub‑boardThe fault current at a board 45 m from a 300 kVA transformer, against 6 kA breakers.
- Check breakers beside a 1000 kVA transformerWhether 25 kA breakers suit a main board 20 m from a 1000 kVA transformer.
- Find the fault level at a house boardThe fault current at the end of 20 m of 16 mm² mains.
- Find the fault level at a shedThe fault current 60 m down a 16 mm² submain.
- Find the fault level at an MCCThe fault current 30 m from a 500 kVA transformer.
- Check 6 kA breakers at a tenancy boardWhether 6 kA devices suit the fault level at the board.
- Find the fault level on parallel feedersThe fault current with two cables per phase.
- Find fault level from a 10 kA serviceThe fault current at a board in Australia.
Dữ liệu nhập
Ví dụ tính toán với dữ liệu nhập mặc định.
- Nguồn
- Máy biến áp
- Định mức máy biến áp
- 500 kVA
- Trở kháng máy biến áp
- 4.5 %
- Điện áp đường dây
- 400 V
- Tiêu chuẩn
- NZ · AS/NZS 3008.1.2
- Chiều dài cáp tổng nhánh
- 30 m
- Kích thước ruột dẫn
- 35 mm²
- Vật liệu
- Đồng
- Cách điện
- PVC 75 °C
- Lõi dây
- Nhiều lõi
- Cáp song song
- 1
- Dung lượng cắt của aptomat
- 15 kA
Dòng sự cố ba pha tại tủ điện
10.01kA
- Dòng điện sự cố pha–đất, cực đại
- 3.18kA
- Dòng điện sự cố pha–đất, cáp đang có điện
- 2.63kA
- Trở kháng nguồn mỗi pha
- 14.4mΩ
- Khả năng cắt
- 15kA
Kết quả này là công cụ hỗ trợ thiết kế. Hãy kiểm tra theo tiêu chuẩn hiện hành.
Các bước tính toán
- Trở kháng biến áp mỗi pha, U² ÷ S × Z%0.01Ω
- Dòng sự cố tại nguồn16.04kA
- Điện trở pha của nhánh phụ tại nhiệt độ vận hành0.02Ω
AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103
- Điện trở pha của nhánh phụ tại 20 °C0.02Ω
AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103
- Điện kháng pha của nhánh phụ0Ω
AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103
- Tiết diện dây dẫn bảo vệ10mm²
AS/NZS 3000:2018 Table 5.1
- Điện trở dây dẫn bảo vệ ở 20 °C0.06Ω
AS/NZS 3008.1.2:2017 Table 30 (Xc), Tables 34–35 (Rc) p.98, p.102–103
- Dòng ngắn mạch ba pha tại bảng, U0 ÷ |Z|Kết quả10.01kA
- Dòng sự cố pha-đất tại bảng, tối đa3.18kA
- Dòng sự cố pha-đất, cáp ở nhiệt độ vận hành2.63kA
- Khả năng cắt của cầu dao15kA
Giới thiệu công cụ tính này
How this is calculated
The tool finds the fault current at a board. The source is a transformer or a stated supply fault level. A submain then adds impedance. The tool compares the result with the breaking capacity of your device.
- Source impedance. For a transformer, the tool works Z = U² ÷ S × Z% per phase. It takes the source as all reactance. That gives the highest current for the size.
- Source current. It gives the fault current at the transformer terminals.
- Submain impedance. It reads the resistance and reactance of the submain for your size, length and material. The tables are Table 30 for reactance and Tables 34 and 35 for resistance. It scales the resistance to 20 °C for the maximum figure.
- Protective conductor. It reads the earth conductor size from Table 5.1 of AS/NZS 3000:2018. It adds that resistance to the earth loop.
- Fault currents. It gives the three‑phase current as U0 ÷ |Z|. It also gives the phase-earth current, maximum and with the cable hot.
- Breaking capacity. It compares the three‑phase current with the rating you enter.
| Step | Table or clause | What it decides |
|---|---|---|
| Submain reactance | AS/NZS 3008.1.2 Table 30 | The reactance of the submain |
| Submain resistance | AS/NZS 3008.1.2 Tables 34 and 35 | The resistance of the submain |
| Earth conductor | AS/NZS 3000 Table 5.1 | The size of the protective conductor |
Worked example
- 500 kVA transformer with a 30 m 35 mm² submain. The transformer has 4.5 % impedance. The three‑phase fault current at the board is 10.01 kA. The maximum phase-earth current is 3.18 kA. A 15 kA device passes.
Limits
- The tool works at nominal voltage. It does not apply the IEC 60909 voltage factors.
- It takes the network above the transformer as infinite. A real network lowers the current a little.
- It takes the phase-earth loop at the transformer as its phase impedance, as for a Dyn transformer.
- It does not add motor contribution. It does not grade devices. Use the IDMT tool for grading.
- The result is an estimate for sizing. Ask the network company for the supply fault level at the point of supply.
See also: Prospective fault current at a board, Fault level at a sub‑board on a 300 kVA transformer and Fault rating.
Câu hỏi
Kết quả chỉ là công cụ hỗ trợ thiết kế. Đối chiếu với tiêu chuẩn hiện hành.
Công cụ mức ngắn mạch tính dòng như thế nào?
Công cụ cộng tổng trở theo từng pha. Máy biến áp cho U² ÷ S × Z%, còn nguồn cấp cho điện áp pha chia cho mức ngắn mạch của nó. Cáp cấp tủ phụ cộng điện trở và điện kháng từ bảng tổng trở của AS/NZS 3008.1. Điện áp pha chia cho tổng là dòng ngắn mạch ba pha tại tủ điện.
Vì sao có hai số liệu pha-đất?
Các bảng cho điện trở ở nhiệt độ vận hành của dây dẫn. Cáp nguội cho dòng điện cao nhất, nên giá trị tối đa được quy đổi điện trở về 20 °C. Số liệu ở trạng thái nóng thấp hơn, dùng cho kiểm tra thời gian cắt trong công cụ Tổng trở mạch vòng.
Công cụ giả định gì về nguồn cấp?
Công cụ coi nguồn là toàn điện kháng và lưới phía trên máy biến áp là vô hạn. Cả hai cách đều cho dòng lớn nhất với các số liệu bạn nhập. Công cụ dùng điện áp danh định, không có hệ số điện áp của IEC 60909. Với nguồn cấp, các giá trị pha-đất cần Ze tại điểm gốc.
Tôi làm gì với kết quả?
So sánh với khả năng cắt của các aptomat tại tủ điện. Sau đó chuyển kết quả sang công cụ khả năng chịu ngắn mạch, để kiểm tra cáp có chịu được dòng sự cố trong thời gian cắt không.
Các ví dụ tính sẵn
- Starting a loaded conveyorA 22 kW conveyor that needs 120 % torque to break away. Why star-delta and a soft starter will not start it, and what a drive or autotransformer does.
- Fault level at a sub‑board, 300 kVA transformerWork the prospective fault current at a sub‑board 45 m from a 300 kVA transformer, three‑phase and phase-earth, and check 6 kA and 10 kA breakers against it.
Nền
Các điều khoản và bảng mà công cụ này đọc
- AS/NZS 3000:2018 Table 5.1Minimum earthing conductor size by active conductor size
- AS/NZS 3008.1.2:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2025 Table 4.1(A), 4.1(B), 4.5(A), 4.5(B)Reactance at 50 Hz and a.c. resistance at 50 Hz
Mọi điều khoản và bảng, kèm cách mỗi mục đã được kiểm chứng
Các bảng được kiểm tra lần cuối ngày 27 Sept 2026.
Công cụ liên quan
- Công cụ tính khả năng chịu ngắn mạch của cápCheck that a conductor can withstand the fault current.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Công cụ tính tiết diện cápFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Công cụ tính máy biến ápCalculate transformer full load current and impedance.Không có tiêu chuẩn
Thông tin này có hữu ích không?
Có câu hỏi, hoặc giá trị có vẻ sai? Liên hệ chúng tôi.