AS/NZS 3008.1.2:2017
Table 8
Current ratings, single‑core cable, three cables per circuit, cross-linked 90 °C
The cable size tool reads the printed rating here for single‑core cross-linked cable on a three‑phase circuit, in copper or aluminium, for each installation method.
Đã xác minh: đối chiếu với tiêu chuẩn in, trang 47–49. Đã kiểm tra 24 Sept 2026.
Đơn vị: Rating A
Đây là các giá trị mà AmpSize mã hóa. Không sao chép nội dung tiêu chuẩn. Hãy đối chiếu với tiêu chuẩn hiện hành.
20 hàng
| Size | Cu spaced apart | Cu spaced from surface | Cu touching | Cu sun | Cu enclosed air | Cu insulation partial | Cu insulation complete | Cu buried direct | Cu underground one enclosure | Cu underground separate enclosures | Al spaced apart | Al spaced from surface | Al touching | Al sun | Al enclosed air | Al insulation partial | Al insulation complete | Al buried direct | Al underground one enclosure | Al underground separate enclosures |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 1 | 21 | 18 | 18 | 13 | 17 | 13 | 9 | 19 | 19 | 24 | — | — | — | — | — | — | — | — | — | — |
| 1.5 | 28 | 23 | 22 | 17 | 20 | 17 | 11 | 24 | 24 | 29 | — | — | — | — | — | — | — | — | — | — |
| 2.5 | 39 | 33 | 31 | 23 | 28 | 22 | 15 | 33 | 33 | 41 | — | — | — | — | — | — | — | — | — | — |
| 4 | 51 | 44 | 41 | 31 | 36 | 29 | 21 | 43 | 43 | 52 | — | — | — | — | — | — | — | — | — | — |
| 6 | 65 | 55 | 52 | 40 | 46 | 37 | 26 | 54 | 54 | 64 | — | — | — | — | — | — | — | — | — | — |
| 10 | 89 | 76 | 72 | 53 | 62 | 50 | 35 | 72 | 72 | 85 | — | — | — | — | — | — | — | — | — | — |
| 16 | 119 | 101 | 95 | 70 | 79 | 64 | 47 | 125 | 92 | 108 | 92 | 78 | 74 | 55 | 62 | 50 | 36 | 97 | 71 | 85 |
| 25 | 161 | 138 | 129 | 95 | 107 | 85 | 64 | 162 | 121 | 141 | 124 | 107 | 100 | 73 | 83 | 66 | 50 | 125 | 93 | 110 |
| 35 | 198 | 169 | 158 | 116 | 132 | 106 | 79 | 193 | 147 | 169 | 154 | 131 | 122 | 89 | 102 | 83 | 62 | 150 | 113 | 131 |
| 50 | 243 | 207 | 194 | 140 | 157 | 125 | — | 229 | 174 | 203 | 188 | 161 | 150 | 109 | 122 | 98 | — | 178 | 135 | 157 |
| 70 | 310 | 264 | 246 | 176 | 201 | 161 | — | 280 | 217 | 248 | 241 | 205 | 191 | 136 | 156 | 125 | — | 217 | 169 | 193 |
| 95 | 385 | 328 | 306 | 217 | 242 | 194 | — | 335 | 261 | 295 | 298 | 255 | 238 | 168 | 188 | 151 | — | 260 | 203 | 229 |
| 120 | 451 | 384 | 358 | 252 | 287 | 230 | — | 381 | 304 | 342 | 350 | 298 | 278 | 196 | 223 | 178 | — | 296 | 236 | 265 |
| 150 | 519 | 443 | 413 | 288 | 325 | 260 | — | 428 | 342 | 383 | 403 | 344 | 320 | 223 | 252 | 201 | — | 332 | 266 | 296 |
| 185 | 616 | 515 | 479 | 332 | 369 | 295 | — | 484 | 388 | 442 | 470 | 402 | 373 | 259 | 287 | 230 | — | 377 | 303 | 343 |
| 240 | 726 | 616 | 573 | 394 | 439 | 352 | — | 560 | 456 | 510 | 564 | 482 | 448 | 308 | 343 | 275 | — | 438 | 356 | 397 |
| 300 | 843 | 713 | 662 | 451 | 516 | 413 | — | 630 | 525 | 591 | 656 | 559 | 519 | 354 | 405 | 323 | — | 495 | 412 | 460 |
| 400 | 989 | 832 | 772 | 521 | 587 | 470 | — | 715 | 596 | 670 | 776 | 659 | 613 | 414 | 466 | 373 | — | 567 | 473 | 525 |
| 500 | 1156 | 961 | 893 | 598 | 696 | 557 | — | 805 | 693 | 756 | 912 | 773 | 717 | 481 | 560 | 448 | — | 646 | 556 | 598 |
| 630 | 1353 | 1111 | 1032 | 683 | 785 | 628 | — | 902 | 778 | 877 | 1076 | 906 | 842 | 558 | 641 | 513 | — | 736 | 635 | 700 |
Các công cụ đọc nó (2)
Hướng dẫn và trang học tập trích dẫn nó (9)
- Hot water cylinder cable size for a 3 kW element
- Cable size for a 20 A heat pump circuit in summer
- AmpSize vs jCalc vs free cable sizing tools
- EV charger cable size for a 7 kW 32 A circuit
- AS/NZS 3008.1.2 Tables 4 to 21: current ratings
- AS/NZS 3008 vs BS 7671: cable sizing compared
- Motor full load current: 11 kW 400 V DOL
- Cable size for a 32 A single‑phase 25 m run
- Current-carrying capacity and derating