A mechanical schedule gives a chiller as 75 kVA. The electrical estimate needs amps. This page converts the one figure into the current that sizes the submain and the protective device.

The inputs

  • Phases: 3
  • Voltage: 400 V
  • Rating kind: kVA
  • Rating: 75
  • Power factor: 0.9
  • Efficiency: 1

The rating is apparent power, so the tool does not apply efficiency to it. Efficiency stays at 1. Efficiency only raises the current when the rating is a shaft or output figure in kilowatts.

Enter the line to line voltage, not the phase to neutral voltage. A 400 V board gives 400 here.

The clause and the table

AS/NZS 3000:2018 Cl 2.2.2 covers maximum demand for the installation. Table C2 group D covers appliances of this kind on a commercial installation. The current from this page becomes the group D line in the demand assessment.

The conversion itself cites no table. Apparent power divided by the line voltage and by the square root of three gives the line current.

The steps

The tool takes the 75 kVA rating as the apparent power. It applies the power factor of 0.9 to get the real power. It then divides the apparent power by 400 V and by the square root of three.

  • Real power: 67.5 kW
  • Apparent power: 75 kVA
  • Full load current: 108.25 A

The result

The full load current is 108.25 A per phase.

Two figures leave this page with different jobs. The 108.25 A goes into the cable size tool as the design current. It also goes into the demand assessment as a group D item. The 67.5 kW goes on the tender as the connected load in kilowatts. That is the figure a mechanical consultant usually asks for.

An estimator can price from 108.25 A directly. The device rating is the next standard frame above that current. The cable behind it still needs the derating and voltage drop checks. A chiller submain on a tray in a plant room often carries a grouping factor.

The nameplate kVA is the worst case draw at full compressor load. A chiller with a variable speed drive spends most of its life well below that. Size the cable and the device for the nameplate. Use the duty figure for energy estimates only.

If the schedule gives kilowatts instead of kVA, change the rating kind on the tool and enter the efficiency. The current will be higher than a direct kW to A conversion suggests. The power factor and the efficiency both raise the apparent power.

Power factor moves the real power line, not the current. Change the power factor to 0.8 and the current stays at 108.25 A. Only the 67.5 kW figure moves. A kVA rating already carries the phase angle, so the rating and the voltage fix the current.

That catches estimators out. A schedule that lists both kVA and kW sometimes disagrees with itself. Price the current from the kVA figure. Use the kW figure for the energy estimate and for generator sizing.

A chiller also has a starting characteristic. A direct on line compressor draws several times the full load current for a short period. That does not change the cable size. It does affect the device curve and the upstream grading.

This page is a design aid. Verify every value against the current edition of the standard.

See also: Commercial kitchen kW to amps full load current, Three‑phase power: kVA to amps at 400 V and Motor circuits and starting.

Thử với các đầu vào này

Hiệu suất
1
Đơn vị định mức
kVA
Hệ số công suất
0.9
Các pha
Ba pha
Định mức
75
Điện áp
400 V
Mở công cụ tính với các dữ liệu nhập này

Tiếp theo

Các khái niệm đứng sau nó

Thêm ví dụ tính toán

AmpSize là công cụ hỗ trợ thiết kế. Hãy đối chiếu kết quả với tiêu chuẩn hiện hành.

Thông tin này có hữu ích không?

Có câu hỏi, hoặc giá trị có vẻ sai? Liên hệ chúng tôi.