सामग्री पर जाएँ
AmpSize

अधिकतम मांग कैलकुलेटर

घरेलू या गैर-घरेलू लोड के लिए अधिकतम मांग का आकलन करें।

Reads AS/NZS 3000:2018 and Electricity (Safety) Regulations 2010. Tables checked 19 Sept 2026.

इनपुट

डिफ़ॉल्ट इनपुट के साथ एक कार्य-उदाहरण।

माँग तालिका
Table C1 · घरेलू
इंस्टॉलेशन
एकल घरेलू या एक आवासीय यूनिट
फ़ेज़
सिंगल-फ़ेज़
फ़ेज़ वोल्टेज
230 V
लोड समूह
4 पंक्तियाँ

अधिकतम मांग

50.43A

प्रति फ़ेज़
50.43A
A(i) · Lighting
5A
B(i) · Socket-outlets and permanently connected equipment up to 10 A
15A
C · Ranges, cooking appliances and laundry equipment
17.39A
F · Storage water heaters
13.04A

यह परिणाम डिज़ाइन में सहायता के लिए है। इसे मौजूदा मानक से सत्यापित करें।

गणना के चरण

  1. मांग तालिकाC1 · single domestic

    AS/NZS 3000:2018 Table C1

  2. A(i) · Lighting5A

    AS/NZS 3000:2018 Table C1

  3. B(i) · Socket‑outlets and permanently connected equipment up to 10 A15A

    AS/NZS 3000:2018 Table C1

  4. C · Ranges, cooking appliances and laundry equipment17.39A

    AS/NZS 3000:2018 Table C1

  5. F · Storage water heaters13.04A

    AS/NZS 3000:2018 Table C1

  6. अधिकतम मांग50.43A

    AS/NZS 3000:2018 Table C1

  7. प्रति फ़ेज़ अधिकतम मांगपरिणाम50.43A

    AS/NZS 3000:2018 Table C1

इस कैलकुलेटर के बारे में

How this is calculated

The tool works out the maximum demand of an installation from its loads. It follows the load group method of AS/NZS 3000 Appendix C.

  1. Table. Table C1 covers domestic installations: one house or living unit, or a block of living units. Table C2 covers other installations. For Table C2 you pick the occupancy.
  2. Load groups. You enter each load in its group, such as lighting points, socket‑outlet points or kW of cooking. The tool lists only the groups the table assesses for your choice.
  3. Group demand. Each group has its own rule for its load. The tool applies that rule and gives the group demand in amperes. It converts each kW load at the phase voltage you enter.
  4. Living units per phase. A block of living units can take more than one phase. The tool then divides the units by the number of phases and rounds up. It reads the column for that number of units per phase.
  5. Total. The maximum demand is the sum of the group demands.
  6. Per phase. On three phases, the tool divides the total by three. That assumes you spread the load evenly over the phases. Where you cannot, allocate the loads per phase and check the heaviest phase.
StepTable or clauseWhat it decides
Domestic loadsAS/NZS 3000 Table C1The rule for each load group in a house or a block of living units
Other loadsAS/NZS 3000 Table C2The rule for each load group, by occupancy
Living units per phaseTable C1 Note 2The column a block of living units reads on more than one phase
Total and per phaseTable C1 or Table C2The sum of the groups and the share on each phase

Phase voltage

Enter the phase voltage, line to neutral, such as 230 V. The tool converts every kW load at that voltage. The 400 V between lines would read every kW group 42 % low. On a three‑phase supply the tool refuses a line voltage and asks for the phase voltage.

Common installations, worked with the tool

Each line states its loads. Every line uses a phase voltage of 230 V.

  • House on one phase. It uses Table C1 for one house. The loads are 30 lighting points, 25 socket‑outlet points, 8 kW of cooking and a 3 kW storage water heater. The maximum demand is 50.43 A.
  • The same house on three phases. The maximum demand is 16.81 A per phase and 50.43 A over all phases.
  • Block of 12 living units on three phases. Table C1 for blocks of living units, with the same load rows. The tool reads 4 units per phase. The maximum demand is 75 A per phase and 225 A over all phases.
  • Office on three phases. It uses Table C2 for factories, shops and offices. The loads are 10 kW of lighting, 20 socket‑outlets and motors of 15 A, 10 A and 5 A. The maximum demand is 44.93 A per phase and 134.78 A over all phases.

New Zealand and Australia

AS/NZS 3000 Appendix C applies in both countries, so the tool has no country select.

Keep the result

Every input sits in the page address, so the link in your browser reproduces the calculation. The PDF button prints the result with its steps and table references. Saving a calculation to a project needs a free account.

See also: Commercial maximum demand with Table C2, Domestic maximum demand with Table C1 and Maximum demand and diversity.

सवाल

परिणाम एक डिज़ाइन सहायता है। मौजूदा मानक से सत्यापित करें।

अधिकतम मांग कैलकुलेटर क्या करता है?

टूल हर जोड़े गए लोड ग्रुप पर मांग नियम लागू करता है। यह हर ग्रुप के लिए एम्पियर में मांग सूचीबद्ध करता है, फिर कुल मांग और हर फ़ेज़ की मांग दिखाता है। हर पंक्ति वह टेबल और कॉलम दिखाती है जिससे वह आया।

अधिकतम मांग कैलकुलेटर कौन सी AS/NZS 3000 टेबल इस्तेमाल करता है?

यह एक घरेलू इंस्टॉलेशन या रहने की इकाइयों के एक ब्लॉक के लिए AS/NZS 3000:2018 Table C1 इस्तेमाल करता है। अन्य इंस्टॉलेशन के लिए यह Table C2 इस्तेमाल करता है, जिसमें रेज़िडेंशियल या कमर्शियल कॉलम होता है। पहले टेबल और मोड चुनें, क्योंकि ये बदलते हैं कि हर लोड ग्रुप कौन-सा नियम मानता है।

हर लोड ग्रुप के लिए मांग नियम क्या तय करता है?

टेबल और मोड हर ग्रुप के लिए नियम तय करते हैं। सप्लाई वोल्टेज किलोवॉट में दिए गए ग्रुपों को एम्पियर में बदलता है। फ़ेज़ की संख्या कुल को बाँटती है। लिविंग यूनिट मोड में, हर फ़ेज़ पर यूनिट की गिनती परिणाम तय करती है। कुल यूनिट गिनती और फ़ेज़ की संख्या दर्ज करें।

थ्री-फ़ेज़ पर रहने की इकाइयाँ कैसे गिनी जाती हैं?

टूल यूनिट की गिनती को तीन से भाग देता है, जैसा Table C1 Note b माँगता है। कुछ ग्रुप व्यक्तिगत आइटम की सूची लेते हैं, किसी एक मात्रा की नहीं। कुछ ग्रुप मूल्यांकन के आधार पर होते हैं और कुछ नहीं जोड़ते। regulation 59 की सीमाओं से ऊपर होने पर एक नोट दिखता है।

क्या मैं मांग की गणना साझा कर सकता हूँ या सहेज सकता हूँ?

हाँ। टेबल, मोड, वोल्टेज, फ़ेज़ और हर लोड पंक्ति पेज के एड्रेस में रहते हैं। वही मांग आकलन किसी और को भेजने के लिए लिंक कॉपी करें। इसे किसी प्रोजेक्ट नाम से सेव करने के लिए अकाउंट चाहिए। न्यूज़ीलैंड की शर्तें डिफ़ॉल्ट हैं।

हल किए गए उदाहरण

इस कैलकुलेटर के सभी 8 गाइड

बैकग्राउंड

वे Clauses और Tables जो यह टूल पढ़ता है

हर Clause और Table, और उनकी सत्यापन की विधि

Tables आख़िरी बार 19 Sept 2026 को जाँची गईं।

क्या यह उपयोगी था?

कोई सवाल, या कोई मान गलत लगता है? हमसे संपर्क करें।