Worked to AS/NZS 3000:2018 and Electricity (Safety) Regulations 2010. Tables checked 19 Sept 2026.

A living room on a frosty morning, with a heat pump and a panel heater.

A house gains fixed heating. Ducted units, panel heaters and heat pump indoor heads all land in one place in a demand assessment. The owner wants to know whether the existing consumer mains still carry the house. This page adds 7.5 kW of fixed heating to a single phase house. It reports what the mains then see.

The inputs

  • Table: C1, single domestic installation
  • Supply: 230 V, single phase
  • Group A(i): 22 lighting points
  • Group B(i): 26 socket outlets and connected equipment up to 10 A
  • Group C: 9 kW of range, cooking and laundry equipment
  • Group D: 7.5 kW of fixed space heating and air conditioning
  • Group F: 3 kW of storage water heating

Group D takes the connected rating of the fixed heating, in kilowatts. A plug-in heater is not fixed heating and belongs in group B(i) with the socket outlets that feed it.

The clause and the table

AS/NZS 3000:2018 Cl 2.2.2 sets the assessment of maximum demand. AS/NZS 3000:2018 Table C1 gives the rule for each load group in a single domestic installation. Each group carries its own rule, so the assessment is not a sum of connected loads.

The steps

The tool applies the Table C1 rule to each group and reports the group in amperes.

  • A(i), lighting: 5 A
  • B(i), socket outlets and equipment up to 10 A: 15 A
  • C, ranges, cooking and laundry: 19.57 A
  • D, fixed space heating, air conditioning and saunas: 24.46 A
  • F, storage water heaters: 13.04 A

Group D entered as 7.5 kW and left as 24.46 A. The Table C1 rule for that group is the whole difference. The same 7.5 kW entered in a group with a different rule would produce a different figure.

The result

  • Maximum demand: 77.07 A
  • Demand per phase: 77.07 A

Group D alone is 24.46 A, close to a third of the whole assessment. Fixed heating is often the largest single group in a New Zealand house. The Table C1 rule discounts it less than it discounts the socket outlet group.

Remove group D from the same house and the assessment falls to 52.61 A. That gap of 24.46 A is what a heating retrofit costs the mains.

The reg 59 line

The tool holds a threshold of 80 A per phase for Electricity (Safety) Regulations 2010 reg 59(1). 77.07 A sits under it. No note appears on this result.

Push the fixed heating from 7.5 kW to 12 kW and the assessment becomes 91.74 A. The tool then raises a note. The note states that the demand is above the reg 59(1) threshold of 80 A per phase. It states that reg 59(2) then allows either a Part 2 route or a certified Part 1 design. It names the route. It does not say who may take it.

That threshold is the reason a heating upgrade turns into a mains conversation. A house assessed at 77.07 A sits just under it. One more heating circuit crosses it.

Before you commit

Check the consumer mains against 77.07 A in the cable size tool, with the real length and the real installation method. Check the main switch rating and the service fuse as well. A demand figure under 80 A does not mean the existing mains carry it. The cable can fail on voltage drop or on derating long before its rating runs out.

This page is a design aid. Verify every value against the current edition of the standard.

See also: AS/NZS 3000 Tables C1 and C2: demand groups, Office maximum demand per phase with Table C2 and Maximum demand and diversity.

इन इनपुट के साथ आज़माएँ

लोड समूह
[{"group":"A(i)","quantity":22},{"group":"B(i…
इंस्टॉलेशन
एकल घरेलू या एक आवासीय यूनिट
फ़ेज़
सिंगल-फ़ेज़
माँग तालिका
Table C1 · घरेलू
फ़ेज़ वोल्टेज
230 V
इन इनपुट के साथ कैलकुलेटर खोलें

आगे कहाँ जाएँ

इसके पीछे के विचार

और उदाहरण

AmpSize एक डिज़ाइन सहायक है। परिणामों को वर्तमान मानक से जाँचें।

क्या यह उपयोगी था?

कोई सवाल, या कोई मान गलत लगता है? हमसे संपर्क करें।