करेक्शन फ़ैक्टर कैलकुलेटर
हर करेक्शन फ़ैक्टर और केबल के लिए ज़रूरी रेटिंग पढ़ें।
Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.
कोई प्रोजेक्ट आज़माएँ 7
हर जॉब में उदाहरण मान भरे होते हैं। उन्हें अपने मानों से बदलें।
- Find the correction factors in a hot ceilingThe factor for four circuits in a 50 °C ceiling space, and the rating the cable needs.
- Find the correction factors for a buried cableThe soil, depth and grouping factors for two buried three‑phase circuits.
- Find the factor for nine circuitsThe grouping factor for nine circuits on a tray.
- Find the factor on a 50 °C roofThe ambient factor at 50 °C.
- Find the factors in poor soilThe soil and depth factors at 2.5 K·m/W and 1 m.
- Find the factor for a harmonic loadThe factor for 40 % third harmonic in a four‑core cable.
- Compare the factors in AustraliaThe factors for 45 °C and four grouped circuits on the Australian tables.
इनपुट
डिफ़ॉल्ट इनपुट के साथ एक कार्य-उदाहरण।
- मानक
- NZ · AS/NZS 3008.1.2
- इंस्टॉलेशन विधि
- हवा में एनक्लोज़्ड
- परिवेश का तापमान
- 40 °C
- समूहित सर्किट
- 3
- फ़ेज़
- सिंगल-फ़ेज़
- डिज़ाइन करंट
- 32 A
- केबल आकार
- 6 mm²
- सामग्री
- तांबा
- इंसुलेशन
- PVC 75 °C
- कोर
- मल्टीकोर
- समानांतर केबल
- 1
संयुक्त सुधार गुणांक
0.62x
- आवश्यक सारणीबद्ध धारा
- 51.95A
- 6 mm² की सारणीबद्ध रेटिंग
- 38A
- सुधारी गई रेटिंग Iz
- 23.41A
- परिवेश सुधार फ़ैक्टर
- ×0.88
- समूहन सुधार गुणांक
- ×0.70
यह परिणाम डिज़ाइन में सहायता के लिए है। इसे मौजूदा मानक से सत्यापित करें।
गणना के चरण
- परिवेश सुधार फ़ैक्टर×0.88
AS/NZS 3008.1.2:2017 Table 27(1) p.88
- समूहन सुधार गुणांक×0.70
AS/NZS 3008.1.2:2017 Tables 22, 25(1), 25(2) p.79, p.84–85
- संयुक्त सुधार गुणांकपरिणाम×0.62
- आवश्यक सारणीबद्ध धारा51.95A
AS/NZS 3000:2018 Cl 3.4
- 6 mm² की सारणीबद्ध रेटिंग38A
AS/NZS 3008.1.2:2017 Table 13 p.62–64
- सुधारी गई रेटिंग Iz23.41A
AS/NZS 3000:2018 Cl 3.4
इस कैलकुलेटर के बारे में
How this is calculated
The tool reads every factor that lowers or raises the current a cable can carry on your route. It is the same code the cable size calculator runs before it tests each size.
- Ambient. It reads the factor for the air temperature, or the soil temperature on a buried route. AS/NZS 3008.1.2 rates New Zealand cables for 30 °C air and 15 °C soil. AS/NZS 3008.1.1 rates Australian cables for 40 °C air and 25 °C soil, so a cooler route gives a factor above 1.
- Grouping. It reads the factor for the circuits that share the route, by how they sit. On a tray, ladder, rack or cleats, pick the cable support. Each parallel cable set counts as a circuit.
- Buried cable. For a buried route it reads the soil thermal resistivity factor and the burial depth factor. Cable buried direct reads its depth factor by conductor size.
- Harmonics. On three phases with third harmonic current, it reads the reduction factor. Above 33 %, it sizes on the neutral current.
- Product. It multiplies the factors into one correction factor (derating factor in 2017). It divides the design current by that factor to give the tabulated current the cable needs.
- One size. It reads the tabulated rating of the size you pick and multiplies it by the factor. The result is Iz, which it checks against the design current.
| Step | Table or clause | What it decides |
|---|---|---|
| Ambient | Tables 27(1) and 27(2) | The factor for the air or soil temperature |
| Grouping | Tables 22, 25(1) and 25(2) | The factor for circuits run together |
| Cable support | Tables 23 and 24 | The factor on a tray, ladder, rack or cleats |
| Buried cable | Table 29, Tables 28(1) and 28(2) | The factors for soil resistivity and depth |
| Harmonics | Table 2 and Cl 3.5.9 | The reduction for third harmonic current in the neutral |
| Required current | AS/NZS 3000 Cl 3.4 | The current the cable must carry in the table |
| Current rating | Table 13 or 14 for multicore, Tables 4, 5, 7 and 8 for single core | The tabulated rating of the size you pick |
Tables without a standard named are in the part of AS/NZS 3008.1 you pick. AS/NZS 3008.1.1:2025 numbers them by section, such as Table 3.44 for Table 27(1).
Common routes, worked with the tool
Each line states its route. Every line uses multicore copper cable with PVC insulation, except where a line names single‑core cable.
- Three circuits enclosed in 40 °C air, 32 A on 6 mm². The factors multiply to 0.62 x. The cable needs a tabulated 51.95 A, and 6 mm² carries only 23.41 A on this route.
- The same route on 16 mm². The factors still multiply to 0.62 x, and the cable needs a tabulated 51.95 A. 16 mm² carries 40.66 A, above the 32 A design current.
- Buried direct in Australia, 100 A on 35 mm² single‑core. Soil at 20 °C with a resistivity of 2 K·m/W, 1 m deep. The factors multiply to 0.8 x, and the cable needs a tabulated 125.31 A.
- Four three‑phase circuits touching, 80 A with 40 % third harmonic on 50 mm². The neutral carries 96 A, so the tool sizes on it. The factors multiply to 0.56 x, and the cable needs a tabulated 171.74 A.
New Zealand and Australia
The Standard select picks the part of AS/NZS 3008.1 the tool reads. For Australia, the Edition select picks 2025 or the superseded 2017 edition. The 2025 edition changed several ambient and grouping factors, so run both when you check an older design.
To size the cable from these factors, use the cable size calculator. To check a cable that is already installed, use the circuit check.
सवाल
परिणाम एक डिज़ाइन सहायता है। मौजूदा मानक से सत्यापित करें।
क्या करेक्शन फ़ैक्टर डीरेटिंग फ़ैक्टर के समान है?
हाँ। AS/NZS 3008.1.1:2025 इन्हें करेक्शन फ़ैक्टर कहता है। 2017 के भाग इन्हें डीरेटिंग फ़ैक्टर कहते हैं। दोनों सारणीबद्ध रेटिंग से गुणा होकर वह करंट देते हैं जो केबल आपके रूट पर ले जाता है।
फ़ैक्टर कैसे मिलाऊँ?
इन्हें गुणा करें। परिवेश, ग्रुपिंग, मिट्टी की रेज़िस्टिविटी, दबाने की गहराई और हार्मोनिक फ़ैक्टर, हर एक रेटिंग पर लागू होता है। डिज़ाइन करंट को इस गुणनफल से भाग दें, ताकि केबल को चाहिए सारणीबद्ध करंट मिले।
30 °C पर ऑस्ट्रेलियाई केबल को 1 से ऊपर फ़ैक्टर क्यों मिलता है?
AS/NZS 3008.1.1 केबल को 40 °C हवा और 25 °C मिट्टी के लिए रेट करता है। ठंडा रूट केबल को ज़्यादा ले जाने देता है। AS/NZS 3008.1.2 न्यूज़ीलैंड की केबल को 30 °C हवा और 15 °C मिट्टी के लिए रेट करता है।
क्या समानांतर केबल को ग्रुपेड सर्किट गिना जाता है?
हाँ। पैरेलल सर्किट का हर केबल सेट ग्रुप में एक सर्किट गिना जाता है। दो पैरेलल सेट वाले तीन सर्किट छह सर्किट का फ़ैक्टर पढ़ते हैं।
बड़े केबल के लिए डेप्थ फ़ैक्टर अलग क्यों है?
सीधे दबी केबल के लिए, गहराई टेबल कंडक्टर आकार के अनुसार फ़ैक्टर को बैंड में बाँटती है: 50 mm² तक, 50 से ऊपर 300 mm² तक, और 300 mm² से ऊपर। टूल आपके चुने आकार का बैंड पढ़ता है।
हल किए गए उदाहरण
- Cable tray fill for a plant room: a second tierLay ten multicore cables on a 300 mm perforated tray in one layer, see when it takes a second tier, and carry the grouping factor into the cable size.
- Downlights in an insulated ceilingRe-insulate a NZ ceiling with downlights in it. Check which may be covered, which only abutted, which must come out, and the clearances and roof space sign.
- Three circuits in a hot ceiling: correction factorThree 32 A circuits in conduit across a 40 °C and a 50 °C ceiling space, worked with the NZ 2017 tables and again with AS/NZS 3008.1.1:2025.
बैकग्राउंड
- Downlights and insulation: IC-4, CA90 and Non‑ICThe six recessed luminaire classes, what insulation may do around each, which a NZ or AU home may have, the default clearances, and the roof space warning sign.
- Cable tray fill: one layer, tiers and groupingHow cables lie on a tray or ladder for AS/NZS 3008.1, touching or spaced, when a run needs another tier, and why there is no fill percentage to work to.
- Correction factors in the 2017 and 2025 editionsWhat each AS/NZS 3008 correction factor does, how the factors multiply, and which values changed when AS/NZS 3008.1.1:2025 replaced the 2017 tables.
वे Clauses और Tables जो यह टूल पढ़ता है
- AS/NZS 3000:2018 Cl 3.4Current-carrying capacity
- AS/NZS 3008.1.2:2017 Cl 3.5.9Third harmonic current in the neutral
- AS/NZS 3008.1.2:2017 Table 2Reduction factors for harmonic currents in 4- and 5‑core cables
- AS/NZS 3008.1.2:2017 Table 13Current ratings, multicore cable with three or four cores, thermoplastic 75 °C
- AS/NZS 3008.1.2:2017 Table 22, 25(1), 25(2)Grouping factors for bunched circuits, buried circuits and underground wiring enclosures
- AS/NZS 3008.1.2:2017 Table 23Grouping factors for single‑core circuits on trays, ladder supports, racks and cleats in air
- AS/NZS 3008.1.2:2017 Table 24Grouping factors for multicore cables on trays, ladder supports, racks and cleats in air
- AS/NZS 3008.1.2:2017 Table 27(1), 27(2)Rating factors for air and soil ambient temperature
हर Clause और Table, और उनकी सत्यापन की विधि
Tables आख़िरी बार 27 Sept 2026 को जाँची गईं।
संबंधित टूल
- केबल आकार कैलकुलेटरFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- वोल्टेज ड्रॉप कैलकुलेटरCalculate voltage drop on a cable run and check the limit.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- केबल ट्रे और लैडर फ़िलTray or ladder width, tiers, kg/m and the grouping factor.AS/NZS 3008.1
क्या यह उपयोगी था?
कोई सवाल, या कोई मान गलत लगता है? हमसे संपर्क करें।