मौजूदा सर्किट जाँच
लगे हुए सर्किट की जाँच करें: केबल, डिवाइस, ड्रॉप और Zs।
Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.
कोई प्रोजेक्ट आज़माएँ 7
हर जॉब में उदाहरण मान भरे होते हैं। उन्हें अपने मानों से बदलें।
- Check the breaker on a 4 mm² circuitWhether a 32 A breaker suits 4 mm² cable, and the largest breaker the cable allows.
- Check an existing three‑phase submainWhether 16 mm² on a 63 A breaker over 80 m passes the cable, drop and Zs checks.
- Check a 20 A breaker on 2.5 mm²Whether a 20 A breaker suits a 2.5 mm² circuit.
- Check a 32 A breaker on 6 mm²Whether a 32 A breaker suits a 6 mm² circuit.
- Check a 16 A breaker on 1.5 mm²Whether a 16 A breaker suits a 1.5 mm² circuit.
- Check a 63 A breaker on 16 mm²Whether a 63 A breaker suits 16 mm² mains.
- Check a 10 A breaker on 1 mm²Whether a 10 A breaker suits a 1 mm² lighting circuit.
इनपुट
डिफ़ॉल्ट इनपुट के साथ एक कार्य-उदाहरण।
- फ़ेज़
- सिंगल-फ़ेज़
- वोल्टेज
- 230 V
- डिज़ाइन करंट
- 20 A
- पावर फ़ैक्टर
- 0.9
- मानक
- NZ · AS/NZS 3008.1.2
- रन की लंबाई
- 30 m
- इंस्टॉलेशन विधि
- हवा में एनक्लोज़्ड
- परिवेश का तापमान
- 30 °C
- समूहित सर्किट
- 1
- लगाया गया केबल आकार
- 2.5 mm²
- सामग्री
- तांबा
- इंसुलेशन
- PVC 75 °C
- कोर
- मल्टीकोर
- समानांतर केबल
- 1
- वोल्टेज ड्रॉप सीमा
- 5 %
- बाहरी इम्पीडेंस Ze
- 0.35 Ω
- संभावित फ़ॉल्ट करंट
- 0 kA
- उपकरण कर्व
- कर्व C
- डिवाइस रेटिंग
- 20 A
2.5 mm² पर सर्किट
पास
- सुधारी गई रेटिंग Iz
- 23A
- वोल्टेज ड्रॉप
- 4.25%
- अर्थ फ़ॉल्ट लूप इम्पीडेंस
- 0.89Ω
- डिवाइस के लिए अधिकतम Zs
- 1.53Ω
- सबसे छोटा आकार जो पास हो
- 2.5mm²
- केबल की अनुमति के अनुसार सबसे बड़ा C कर्व डिवाइस
- 20A
- संयुक्त सुधार गुणांक
- ×1.00
यह परिणाम डिज़ाइन में सहायता के लिए है। इसे मौजूदा मानक से सत्यापित करें।
गणना के चरण
- लगाया गया कंडक्टर आकार2.5mm²
AS/NZS 3008.1.2:2017 Table 13 p.62–64
- 2.5 mm² की सारणीबद्ध रेटिंग23A
AS/NZS 3008.1.2:2017 Table 13 p.62–64
- परिवेश सुधार फ़ैक्टर×1.00
AS/NZS 3008.1.2:2017 Tables 27(1), 27(2) p.88
- समूहन सुधार गुणांक×1.00
One circuit, no grouping factor
- संयुक्त सुधार गुणांक×1.00
- सुधारी गई रेटिंग Iz23A
AS/NZS 3000:2018 Cl 3.4
- वोल्टेज ड्रॉप9.78V
- वोल्टेज ड्रॉप प्रतिशत4.25%
AS/NZS 3000:2018 Cl 3.6.2
- डिवाइस रेटिंग In20A
AS/NZS 3000:2018 Cl 2.5.3.1
- अर्थ कंडक्टर का आकार2.5mm²
AS/NZS 3000:2018 Table 5.1
- 230 V फ़ेज़ से अर्थ पर अर्थ फ़ॉल्ट लूप इम्पीडेंस0.89Ω
AS/NZS 3000:2018 Table 8.1
- डिवाइस के लिए अधिकतम Zs1.53Ω
AS/NZS 3000:2018 Table 8.1
- सबसे छोटा आकार जो पास होता है2.5mm²
AS/NZS 3000:2018 Cl 3.4
इस कैलकुलेटर के बारे में
How this is calculated
The tool takes a circuit that is already installed and runs the five checks of the cable size calculator at its size. It uses the same code, so the two tools agree on every size.
- Current capacity. It reads the tabulated rating of the installed size for your material, insulation, core count and installation method. It multiplies the rating by the correction factors for the route to get Iz. Iz must be at or above the design current Ib.
- Voltage drop. It works out the drop for the run length, the power factor and the conductor. It compares the drop with the limit you set.
- Breaker rating. The breaker rating In must sit between the two: Ib at or below In, and In at or below Iz. The tool gives both margins.
- Loop impedance. It adds the active and earth conductor resistance to the external impedance Ze. The total Zs must stay under the maximum for the breaker curve and rating.
- Fault withstand. If you enter a prospective fault current, the conductor must withstand it for the clearing time.
- Result. The circuit passes when every check it runs passes. The tool gives the smallest standard size that passes with the same breaker, and the largest breaker of the same curve that the cable allows.
| Step | Table or clause | What it decides |
|---|---|---|
| Current rating | Table 13 or 14 for multicore, Tables 4, 5, 7 and 8 for single core | The tabulated rating of the installed size |
| Correction factors | Tables 22 to 29 and Table 2 | The factors for the route |
| Voltage drop | Tables 30, 34 and 35, AS/NZS 3000 Cl 3.6.2 | The drop over the run and its limit |
| Breaker rating | AS/NZS 3000 Cl 2.5.3.1 | That In sits between Ib and Iz |
| Earth and Zs | AS/NZS 3000 Table 5.1 and Table 8.1 | The earth conductor size and the maximum loop impedance |
| Fault withstand | Table 52 and Cl 5.3 | The fault current the conductor survives |
Tables without a standard named are in the part of AS/NZS 3008.1 you pick. AS/NZS 3008.1.1:2025 numbers them by section.
Common circuits, worked with the tool
Each line states its circuit. Every line uses multicore copper cable with PVC insulation and one circuit on the route, enclosed in air at 30 °C. Every breaker is a C curve and Ze is 0.35 Ω, on the New Zealand tables.
- Socket‑outlets, 2.5 mm² on a 20 A breaker over 30 m. It passes every check. The drop is 4.25 %, close to the 5 % limit.
- The same cable on a 32 A breaker with a 25 A load. It fails the current, drop and breaker checks. 6 mm² is the smallest size that passes.
- 4 mm² on a 32 A breaker over 20 m. It fails the breaker check, because Iz is 29 A. The largest breaker the cable allows is 25 A, and 6 mm² is the smallest size that passes on 32 A.
- Three‑phase submain, 16 mm² on a 63 A breaker over 80 m. It fails on loop impedance: Zs is 0.76 Ω against a maximum of 0.49 Ω. With this breaker, 70 mm² is the smallest size that passes.
New Zealand and Australia
The Standard select picks the part of AS/NZS 3008.1 the tool reads. For Australia, the Edition select picks 2025 or the superseded 2017 edition. The breaker and Zs rules come from AS/NZS 3000, which is the same in both countries.
What the tool does not check
The tool works from the inputs, not from a test. Measure Ze and Zs on site and compare the reading with the maximum it gives. It does not check RCD rules or discrimination between breakers.
To size a new circuit, use the cable size calculator. To read the factors for a route on their own, use the correction factors calculator.
सवाल
परिणाम एक डिज़ाइन सहायता है। मौजूदा मानक से सत्यापित करें।
4 mm² केबल पर कौन सा आकार का ब्रेकर लग सकता है?
यह रूट पर निर्भर करता है। 30 °C हवा में अकेले एन्क्लोज़्ड, 4 mm² कॉपर न्यूज़ीलैंड में 29 A रेट होता है, इसलिए 25 A ब्रेकर सबसे बड़ा मानक आकार है। ग्रुपिंग, गर्मी या इंसुलेशन इसे कम करते हैं। केबल जितना बड़ा ब्रेकर अनुमत करती है, वह पढ़ने के लिए अपना रूट दर्ज करें।
Ib ≤ In ≤ Iz का क्या मतलब है?
Ib लोड का डिज़ाइन करंट है, In ब्रेकर रेटिंग है, और Iz सुधार के बाद केबल रेटिंग। ब्रेकर लोड ले जाए, और केबल ब्रेकर रेटिंग ले जाए। AS/NZS 3000 Clause 2.5.3.1 यह नियम तय करता है।
लंबा सर्किट लूप इम्पीडेंस पर क्यों फ़ेल होता है?
लंबी या छोटी केबल का अर्थ फ़ॉल्ट लूप इम्पीडेंस ऊँचा होता है। तब फ़ॉल्ट करंट इतना कम होता है कि ब्रेकर अपनी मैग्नेटिक सेटिंग पर समय पर ट्रिप न हो। बड़ी केबल, कम ब्रेकर रेटिंग, B कर्व इस्तेमाल करें, या सर्किट के लिए RCD नियम जाँचें।
क्या टूल मेरा सर्किट मापता है?
नहीं। यह आपके दर्ज किए केबल आकार, रूट और बाहरी इम्पीडेंस Ze से काम करता है। साइट पर Ze और Zs मापें और रीडिंग की तुलना टूल द्वारा दिए गए अधिकतम Zs से करें।
जब सर्किट फ़ेल हो, तो टूल कौन सा आकार सुझाता है?
सबसे छोटा मानक आकार जो एक ही ब्रेकर, रूट और लोड के साथ हर जाँच पास करे। यह वही उत्तर है जो केबल आकार कैलकुलेटर उसी सर्किट के लिए देता है।
हल किए गए उदाहरण
- A circuit chart for a house board with solarThe circuit chart and labels for a six-circuit house board with a solar inverter: ways, devices, RCDs, MAIN SWITCH, MAIN SWITCH SOLAR and a shared neutral.
- What size breaker for 4 mm² cable4 mm² copper enclosed in air takes a 25 A breaker, and 32 A fails at an Iz of 29 A. Grouping, a hot ceiling, insulation and a long run lower it.
बैकग्राउंड
वे Clauses और Tables जो यह टूल पढ़ता है
- AS/NZS 3000:2018 Cl 2.5.3.1Protective device coordination
- AS/NZS 3000:2018 Cl 3.4Current-carrying capacity
- AS/NZS 3000:2018 Cl 3.6.2Voltage drop limit
- AS/NZS 3000:2018 Table 5.1Minimum earthing conductor size by active conductor size
- AS/NZS 3000:2018 Table 8.1Maximum earth fault loop impedance multipliers by MCB curve
- AS/NZS 3008.1.2:2017 Table 4Current ratings, single‑core cable, two cables per circuit, thermoplastic 75 °C
- AS/NZS 3008.1.2:2017 Table 5Current ratings, single‑core cable, two cables per circuit, cross-linked 90 °C
- AS/NZS 3008.1.2:2017 Table 7Current ratings, single‑core cable, three cables per circuit, thermoplastic 75 °C
हर Clause और Table, और उनकी सत्यापन की विधि
Tables आख़िरी बार 27 Sept 2026 को जाँची गईं।
संबंधित टूल
- केबल आकार कैलकुलेटरFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- अर्थ फ़ॉल्ट लूप इम्पीडेंस कैलकुलेटरCheck earth fault loop impedance against the maximum Zs.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- सरल केबल सिलेक्टरRead the Appendix C device rating and voltage drop tables.AS/NZS 3000
क्या यह उपयोगी था?
कोई सवाल, या कोई मान गलत लगता है? हमसे संपर्क करें।