AS/NZS 3000:2018
Table 8.1, B4.5 मल्टीप्लायर
Maximum earth fault loop impedance multipliers by MCB curve
The loop impedance and cable size tools read the highest loop impedance a circuit may have for its device curve and rating. The measured or calculated Zs is compared with it.
सत्यापित: छपे मानक से जाँचा गया, पेज 427, 449। जाँच की गई 27 Sept 2026।
यूनिट: Multiplier ×In
ये वे मान हैं जिन्हें AmpSize एन्कोड करता है। मानक का पाठ दोहराया नहीं गया है। मौजूदा मानक से सत्यापित करें।
3 पंक्तियाँ
| Curve | Multiplier (×In) |
|---|---|
| B | 4 |
| C | 7.5 |
| D | 12.5 |