63 A three‑phase submain buried in Queensland

केबल आकार कैलकुलेटर

+5 references

Worked to AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.

A drawn result card from the Cable Size tool: conductor size 16 mm² for a buried submain.

A workshop in Queensland needs a submain from the main board. The cable runs 60 m, buried direct. Summer ground near a hot slab can stay warm for weeks. This guide sizes the cable on AS/NZS 3008.1.1:2025 and shows which factors do the work.

The inputs

  • Australia, edition 2025.
  • Three phase, 400 V, power factor 0.9.
  • Design current 63 A, run length 60 m.
  • Copper, PVC insulated, multicore, buried direct at 0.5 m.
  • Temperature entry 40 °C. This is a hot-ground assumption, not a typical value.
  • Soil thermal resistivity 1.2 K·m/W.

AS/NZS 3000:2018 Cl 3.4 sets the check. The derated capacity must meet the design current.

The factors

For a buried method the tool applies Tables 3.44 and 3.45 to the temperature entry. At 40 °C the factor is 0.84. Table 3.48 covers the soil. Resistivity 1.2 K·m/W gives 1. Tables 3.46 and 3.47 cover depth, and 0.5 m gives 1. The total derating factor is 0.84.

The cable needs a tabulated 75 A. Divide 63 A by 0.84 to see it.

Aluminium instead

Some submains use aluminium. Aluminium at 40 °C also picks 16 mm². Its derated capacity is 63 A, which meets the design current with no margin. The drop is 3.49 %. Aluminium has a higher resistance and a lower rating than copper of the same size. Run the next size and compare.

The tool does not check the protective device here. Match the device to the cable rating, and the cable to the load.

On site

The 40 °C entry is a stress case. Ordinary summer ground is cooler. Run the cable at the ground temperature you expect. Then run it again at the stress value and compare the sizes. A big gap between them is a warning. It tells you the design has little margin.

Soil is the other unknown. Dry sand and rock hold heat. Damp clay sheds it. If the trench passes through more than one soil, size for the worst section. Record the soil resistivity you assumed in the schedule.

The result on 2025

Open the 2025 run. The tool picks 16 mm². Table 3.18 rates it at 96 A. The derated capacity is 80.64 A, a margin of 17.64 A. The voltage drop is 2.12 %, with 2.88 % to spare.

10 mm² at the same temperature derates to 62.16 A, and its drop is 3.35 %. It falls short of 63 A, and a near miss still fails.

Soil and depth

Hot ground is one risk. Dry ground is another. At soil 2.5 K·m/W, the soil factor is 0.74. The tool then picks 25 mm², with a derated capacity of 77.7 A.

Depth also counts. At 0.8 m, the depth factor is 0.97. The derated capacity of 16 mm² falls to 78.22 A. It still passes.

Ground at 25 °C

Set the temperature entry to 25 °C and the factor goes to 1. The 25 °C run picks 10 mm² with a capacity of 74 A. The tool adds a note. The 2025 edition calculates buried-direct ratings up to 10 mm². Check that the protective device lets the cable reach that rating.

The 2017 edition

On 2017 the tool reads Table 13. The ambient factor is 0.83. It also picks 16 mm², with a capacity of 79.68 A.

The result

CaseSizeDerated capacityVoltage drop
2025, 40 °C, soil 1.216 mm²80.64 A2.12 %
2025, 40 °C, soil 2.525 mm²77.7 A1.36 %
2025, 40 °C, 0.8 m deep16 mm²78.22 A2.12 %
2025, 25 °C, soil 1.210 mm²74 A3.35 %
2017, 40 °C, soil 1.216 mm²79.68 A2.12 %

The submain needs 16 mm² at 40 °C and soil 1.2. Soil resistivity moves the size more than depth does. Try it with these inputs.

This page is a design aid. Verify every value against the current edition of the standard.

See also: Cable size for a 32 A circuit, Australia 2025, Underground cables and civil interfaces and AS/NZS 3008.1.1:2025: what changed from 2017.

इन इनपुट के साथ आज़माएँ

परिवेश का तापमान
40 °C
गाड़ने की गहराई
0.5 m
कोर
मल्टीकोर
संस्करण
AS/NZS 3008.1.1:2025
समूहित सर्किट
1
इंसुलेशन
PVC 75 °C
मानक
AU · AS/NZS 3008.1.1
रन की लंबाई
60 m
डिज़ाइन करंट
63 A
सामग्री
तांबा
इंस्टॉलेशन विधि
Buried direct
पावर फ़ैक्टर
0.9
फ़ेज़
थ्री-फ़ेज़
मिट्टी की थर्मल रेज़िस्टिविटी
1.2 K·m/W
वोल्टेज
400 V
इन इनपुट के साथ कैलकुलेटर खोलें

आगे कहाँ जाएँ

इसके पीछे के विचार

और उदाहरण

AmpSize एक डिज़ाइन सहायक है। परिणामों को वर्तमान मानक से जाँचें।

क्या यह उपयोगी था?

कोई सवाल, या कोई मान गलत लगता है? हमसे संपर्क करें।