Công cụ tính chuỗi PV
Số tấm mỗi chuỗi, dòng chuỗi và cầu dao cách ly cho dàn PV.
Reads AS/NZS 5033:2021 and AS/NZS 4777.2:2020. Tables checked 2 Oct 2026.
Thử một công việc 8
Mỗi công việc điền sẵn giá trị ví dụ. Hãy thay bằng giá trị của bạn.
- Size solar strings for a 600 V inverterThe modules per string for 49.5 V modules on a 600 V inverter at −5 °C.
- Check string fuses on three parallel stringsWhether three parallel strings of 13.9 A modules call for string fuses, and their rating.
- Size strings for a 1000 V inverterThe modules per string for a commercial inverter.
- Size strings for a cold inland siteThe modules per string at a record low of −8 °C, on a 600 V inverter.
- Check a string on a hot roofWhether the hot voltage stays above the tracker's minimum.
- Check two strings need no fuseWhether two strings in parallel need string fuses.
- Check the array current at the inverterThe array's short-circuit current against the inverter input.
- Size strings for a house trackerThe modules per string for a 450 V window.
Dữ liệu nhập
Ví dụ tính toán với dữ liệu nhập mặc định.
- Voc của tấm
- 49.5 V
- Vmp của tấm
- 41.5 V
- Isc của tấm
- 13.9 A
- Hệ số nhiệt độ Voc
- −0.27 %/K
- Hệ số nhiệt độ Vmp
- −0.35 %/K
- Cầu chì nối tiếp lớn nhất của tấm
- 25 A
- Hiệu chỉnh điện áp khi lạnh
- Hệ số của nhà sản xuất, Cl 4.2.1.2(a)
- Nhiệt độ thấp nhất ghi nhận
- −5 °C
- Nhiệt độ cao nhất ghi nhận
- 35 °C
- Mức tăng nhiệt của cell so với môi trường
- 35 K
- Lắp đặt
- Dân dụng, giới hạn 1000 V
- Số tấm mỗi chuỗi
- 10
- Các chuỗi song song
- 2
- KI, hệ số hai mặt
- 1
- Dòng ngược từ biến tần
- 0 A
- Định mức cầu chì chuỗi
- 0 A
- Điện áp một chiều cực đại của biến tần
- 600 V
- Điện áp cực tiểu MPPT
- 150 V
- Điện áp cực đại MPPT
- 550 V
- Isc PV của biến tần
- 0 A
Số tấm mỗi chuỗi
5 đến 11
- Điện áp lớn nhất của chuỗi
- 535.1V
- Vmp chuỗi tại ô nóng nhất
- 349.6V
- Dòng chuỗi tối đa
- 17.38A
- Dòng điện từ dãy pin đến biến tần
- 34.75A
- Cách ly một chiều, tối thiểu
- 34.75 A tại 535.1 V
- Cầu chì chuỗi
- Not called for
Kết quả này là công cụ hỗ trợ thiết kế. Hãy kiểm tra theo tiêu chuẩn hiện hành.
Các bước tính toán
- Hiệu chỉnh Voc, 1 + hệ số × (Tmin − 25 °C)×1.08
AS/NZS 5033:2021 Cl 4.2.1.2
- Điện áp tối đa của mô-đun tại ô lạnh nhất53.51V
AS/NZS 5033:2021 Cl 4.2.1.2
- Giới hạn cho lắp đặt dân dụng1,000V
AS/NZS 5033:2021 Cl 3.1
- Số mô-đun tối đa trên mỗi chuỗi11
AS/NZS 5033:2021 Cl 4.2.1.3.1
- Ô nóng nhất, mức cao nhất đã ghi cộng mức tăng70°C
- Vmp của mô-đun tại ô nóng nhất34.96V
- Số mô-đun ít nhất trên mỗi chuỗi để đạt mức tối thiểu của MPPT5
- Điện áp cực đại chuỗi535.1V
AS/NZS 5033:2021 Cl 4.2.1.3.1
- Vmp chuỗi tại ô nóng nhất349.6V
- Vmp chuỗi tại ô lạnh nhất458.6V
- Dòng chuỗi tối đa, 1.25 × KI × Isc17.38A
AS/NZS 5033:2021 Cl 3.3.3.1
- Dòng sự cố từ các chuỗi khác, (SA − 1) × ISTRING MAX17.38A
AS/NZS 5033:2021 Cl 3.3.3.2
- Dải cầu chì chuỗi, trên 1.2 × ISTRING MAX và không quá định mức mô-đuntrên 20.85 đến 25A
AS/NZS 5033:2021 Table 3.1
- Dòng điện cáp chuỗi17.38A
AS/NZS 5033:2021 Table 4.2
- Dòng điện cáp dãy pin đến biến tần34.75A
AS/NZS 5033:2021 Table 4.2
- Định mức dòng của công tắc cách ly một chiều, tối thiểu34.75A
AS/NZS 5033:2021 Table 4.3
- Định mức điện áp của công tắc cách ly một chiều, tối thiểu535.1V
AS/NZS 5033:2021 Table 4.3
- Dây dẫn nhỏ nhất4mm²
AS/NZS 5033:2021 Cl 4.4.2.3
- Nhiệt độ cáp gần các tấm pin, mức cao nhất ghi nhận cộng 40 K75°C
AS/NZS 5033:2021 Cl 4.4.2.2
Giới thiệu công cụ tính này
How this is calculated
The tool sizes a PV string. It finds how many modules fit in a string, the string current, the fuses and the d.c. isolator. It reads AS/NZS 5033:2021. It reads the inverter limits from the plate you enter.
- Cold voltage. The tool corrects the module Voc for the coldest cell (Cl 4.2.1.2). The factor is 1 + coefficient × (Tmin − 25 °C). Tmin is the record low.
- Most modules. It divides the voltage limit by the corrected Voc. The limit is the lower of the inverter maximum and the domestic limit in Cl 3.1 (Cl 4.2.1.3.1).
- Fewest modules. It finds the hot cell as the record high plus the cell rise you enter. It then finds the fewest modules that keep Vmp above the MPPT minimum.
- String current. It works 1.25 × KI × Isc (Cl 3.3.3.1). It adds the fault current from the other strings (Cl 3.3.3.2).
- Fuses. A fuse window sits above 1.2 times the string current and at most the module rating (Table 3.1).
- Cable and isolator. It gives the cable currents (Table 4.2), the isolator ratings (Table 4.3) and the smallest conductor (Cl 4.4.2.3).
| Step | Table or clause | What it decides |
|---|---|---|
| Cold voltage | Cl 4.2.1.2 | The module voltage at the coldest cell |
| String length | Cl 4.2.1.3.1 | The most modules in a string |
| String current | Cl 3.3.3.1 and Cl 3.3.3.2 | The current for cable and fuse |
| Fuse window | Table 3.1 | The fuse range |
| Isolator | Table 4.3 | The current and voltage ratings |
Worked example
- 10 modules of 49.5 V Voc, 2 strings, 600 V inverter. The tool gives 5 to 11 modules per string. The string maximum voltage is 535.1 V. The string current is 17.38 A and the array current is 34.75 A. No string fuses are called for.
Limits
- The tool derives the AS/NZS 5033 figures from the text until the Standard is checked. It says so in a warning.
- AS/NZS 5033 sets no cell rise. The tool uses the rise you enter.
- The inverter limits are the ones on its plate. Read them from the data sheet.
- The tool does not size the cable. Use the DC cable size calculator at these currents and at the hot cable temperature.
- Above 120 V, hold the voltage drop from the furthest module to the inverter to 5 % of Vmp.
See also: PV string voltage and temperature, Solar string sizing for a 600 V inverter and PV and inverter basics.
Câu hỏi
Kết quả chỉ là công cụ hỗ trợ thiết kế. Đối chiếu với tiêu chuẩn hiện hành.
Công cụ tìm số tấm nhiều nhất trên mỗi chuỗi như thế nào?
Công cụ hiệu chỉnh Voc của tấm về nhiệt độ thấp kỷ lục, theo hệ số của nhà sản xuất hoặc theo AS/NZS 5033 Table 4.1. Công cụ chia giá trị thấp hơn giữa mức tối đa của biến tần và giới hạn 1000 V hoặc 1500 V cho điện áp đó, rồi làm tròn xuống.
Công cụ tìm số tấm ít nhất trên mỗi chuỗi như thế nào?
Công cụ tính Vmp của tấm ở cell nóng nhất: nhiệt độ cao kỷ lục cộng với mức tăng nhiệt của cell bạn nhập. Công cụ chia mức tối thiểu MPPT cho điện áp đó rồi làm tròn lên. AS/NZS 5033 không quy định mức tăng nhiệt của cell, nên mặc định 35 K là giả định của AmpSize.
Khi nào một chuỗi cần cầu chì?
Khi các chuỗi đi song song, các chuỗi khác có thể cấp dòng cho một sự cố trong một chuỗi. Công cụ cộng dòng đó vào dòng hồi tiếp và so sánh với cầu chì nối tiếp tối đa của tấm pin. Nếu cao hơn, cầu chì nằm trên 1.2 lần dòng chuỗi tối đa và bằng hoặc thấp hơn định mức tấm pin.
Các số liệu AS/NZS 5033 đã được xác minh chưa?
Có. Table 4.1 và các giới hạn điện áp, dòng điện và cáp đã được đối chiếu với các trang in của AS/NZS 5033:2021. Hãy kiểm tra từng số liệu với tiêu chuẩn hiện hành trước khi dựa vào nó.
Các ví dụ tính sẵn
- DC isolator rating for a 10 kW solar arrayRate the d.c. isolator and size the frame earth for a four-string domestic array. Check one data sheet that passes and one that fails per pole.
- Solar string sizing for a 600 V inverterHow many 49.5 V modules fit a string on a 600 V inverter at −5 °C? Work cold Voc, hot Vmp, the string current, fuses and the d.c. isolator by AS/NZS 5033.
Nền
- PV array isolators and earthingHow parallel strings feed a fault, what Ithe, Ie and make and break mean for a d.c. isolator, and how AS/NZS 5033 earths and alarms a PV array.
- PV string voltage and temperatureWhy a PV string's voltage rises in the cold and falls in the heat, how AS/NZS 5033 limits it, and how the string current, fuses and isolator follow.
Các điều khoản và bảng mà công cụ này đọc
- AS/NZS 5033:2021 Cl 3.1Maximum voltage of PV d.c. circuits
- AS/NZS 5033:2021 Cl 3.3.3.1Maximum string current
- AS/NZS 5033:2021 Cl 3.3.3.2Fault current from parallel strings
- AS/NZS 5033:2021 Cl 3.3.4.1When strings take overcurrent protection
- AS/NZS 5033:2021 Cl 4.2.1.2PV module maximum voltage
- AS/NZS 5033:2021 Cl 4.2.1.3.1String voltage limit
- AS/NZS 5033:2021 Cl 4.4.2.2PV cable temperature
- AS/NZS 5033:2021 Cl 4.4.2.3Smallest PV conductor
Mọi điều khoản và bảng, kèm cách mỗi mục đã được kiểm chứng
Các bảng được kiểm tra lần cuối ngày 2 Oct 2026.
Công cụ liên quan
- Công cụ tính tiết diện cáp DCSize a d.c. cable up to 1500 V for current and voltage drop.AS/NZS 3008.1.1
- Công cụ tính cầu dao cách ly và nối đất PVRate the PV array cables, d.c. isolator and earthing.AS/NZS 5033AS/NZS 3000
- Công cụ tính bù hệ số công suấtFind the capacitor kvar to lift a power factor.AS/NZS 3000
Thông tin này có hữu ích không?
Có câu hỏi, hoặc giá trị có vẻ sai? Liên hệ chúng tôi.