Công cụ tính hệ số hiệu chỉnh
Đọc từng hệ số hiệu chỉnh và định mức mà cáp cần.
Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.
Thử một công việc 7
Mỗi công việc điền sẵn giá trị ví dụ. Hãy thay bằng giá trị của bạn.
- Find the correction factors in a hot ceilingThe factor for four circuits in a 50 °C ceiling space, and the rating the cable needs.
- Find the correction factors for a buried cableThe soil, depth and grouping factors for two buried three‑phase circuits.
- Find the factor for nine circuitsThe grouping factor for nine circuits on a tray.
- Find the factor on a 50 °C roofThe ambient factor at 50 °C.
- Find the factors in poor soilThe soil and depth factors at 2.5 K·m/W and 1 m.
- Find the factor for a harmonic loadThe factor for 40 % third harmonic in a four‑core cable.
- Compare the factors in AustraliaThe factors for 45 °C and four grouped circuits on the Australian tables.
Dữ liệu nhập
Ví dụ tính toán với dữ liệu nhập mặc định.
- Tiêu chuẩn
- NZ · AS/NZS 3008.1.2
- Phương pháp lắp đặt
- Đặt kín trong không khí
- Nhiệt độ môi trường
- 40 °C
- Các mạch đi chung nhóm
- 3
- Các pha
- Một pha
- Dòng thiết kế
- 32 A
- Tiết diện cáp
- 6 mm²
- Vật liệu
- Đồng
- Cách điện
- PVC 75 °C
- Lõi dây
- Nhiều lõi
- Cáp song song
- 1
Hệ số hiệu chỉnh tổng hợp
0.62x
- Dòng bảng yêu cầu
- 51.95A
- Dòng định mức theo bảng của 6 mm²
- 38A
- Định mức đã hiệu chỉnh Iz
- 23.41A
- Hệ số hiệu chỉnh nhiệt độ môi trường
- ×0.88
- Hệ số hiệu chỉnh nhóm
- ×0.70
Kết quả này là công cụ hỗ trợ thiết kế. Hãy kiểm tra theo tiêu chuẩn hiện hành.
Các bước tính toán
- Hệ số hiệu chỉnh nhiệt độ môi trường×0.88
AS/NZS 3008.1.2:2017 Table 27(1) p.88
- Hệ số hiệu chỉnh nhóm×0.70
AS/NZS 3008.1.2:2017 Tables 22, 25(1), 25(2) p.79, p.84–85
- Hệ số hiệu chỉnh tổng hợpKết quả×0.62
- Dòng điện bảng yêu cầu51.95A
AS/NZS 3000:2018 Cl 3.4
- Định mức theo bảng của 6 mm²38A
AS/NZS 3008.1.2:2017 Table 13 p.62–64
- Định mức đã hiệu chỉnh Iz23.41A
AS/NZS 3000:2018 Cl 3.4
Giới thiệu công cụ tính này
How this is calculated
The tool reads every factor that lowers or raises the current a cable can carry on your route. It is the same code the cable size calculator runs before it tests each size.
- Ambient. It reads the factor for the air temperature, or the soil temperature on a buried route. AS/NZS 3008.1.2 rates New Zealand cables for 30 °C air and 15 °C soil. AS/NZS 3008.1.1 rates Australian cables for 40 °C air and 25 °C soil, so a cooler route gives a factor above 1.
- Grouping. It reads the factor for the circuits that share the route, by how they sit. On a tray, ladder, rack or cleats, pick the cable support. Each parallel cable set counts as a circuit.
- Buried cable. For a buried route it reads the soil thermal resistivity factor and the burial depth factor. Cable buried direct reads its depth factor by conductor size.
- Harmonics. On three phases with third harmonic current, it reads the reduction factor. Above 33 %, it sizes on the neutral current.
- Product. It multiplies the factors into one correction factor (derating factor in 2017). It divides the design current by that factor to give the tabulated current the cable needs.
- One size. It reads the tabulated rating of the size you pick and multiplies it by the factor. The result is Iz, which it checks against the design current.
| Step | Table or clause | What it decides |
|---|---|---|
| Ambient | Tables 27(1) and 27(2) | The factor for the air or soil temperature |
| Grouping | Tables 22, 25(1) and 25(2) | The factor for circuits run together |
| Cable support | Tables 23 and 24 | The factor on a tray, ladder, rack or cleats |
| Buried cable | Table 29, Tables 28(1) and 28(2) | The factors for soil resistivity and depth |
| Harmonics | Table 2 and Cl 3.5.9 | The reduction for third harmonic current in the neutral |
| Required current | AS/NZS 3000 Cl 3.4 | The current the cable must carry in the table |
| Current rating | Table 13 or 14 for multicore, Tables 4, 5, 7 and 8 for single core | The tabulated rating of the size you pick |
Tables without a standard named are in the part of AS/NZS 3008.1 you pick. AS/NZS 3008.1.1:2025 numbers them by section, such as Table 3.44 for Table 27(1).
Common routes, worked with the tool
Each line states its route. Every line uses multicore copper cable with PVC insulation, except where a line names single‑core cable.
- Three circuits enclosed in 40 °C air, 32 A on 6 mm². The factors multiply to 0.62 x. The cable needs a tabulated 51.95 A, and 6 mm² carries only 23.41 A on this route.
- The same route on 16 mm². The factors still multiply to 0.62 x, and the cable needs a tabulated 51.95 A. 16 mm² carries 40.66 A, above the 32 A design current.
- Buried direct in Australia, 100 A on 35 mm² single‑core. Soil at 20 °C with a resistivity of 2 K·m/W, 1 m deep. The factors multiply to 0.8 x, and the cable needs a tabulated 125.31 A.
- Four three‑phase circuits touching, 80 A with 40 % third harmonic on 50 mm². The neutral carries 96 A, so the tool sizes on it. The factors multiply to 0.56 x, and the cable needs a tabulated 171.74 A.
New Zealand and Australia
The Standard select picks the part of AS/NZS 3008.1 the tool reads. For Australia, the Edition select picks 2025 or the superseded 2017 edition. The 2025 edition changed several ambient and grouping factors, so run both when you check an older design.
To size the cable from these factors, use the cable size calculator. To check a cable that is already installed, use the circuit check.
Câu hỏi
Kết quả chỉ là công cụ hỗ trợ thiết kế. Đối chiếu với tiêu chuẩn hiện hành.
Hệ số hiệu chỉnh có giống hệ số suy giảm không?
Có. AS/NZS 3008.1.1:2025 gọi chúng là hệ số hiệu chỉnh. Các phần của bản 2017 gọi là hệ số suy giảm. Cả hai đều nhân với định mức theo bảng để ra dòng điện mà cáp mang trên tuyến của bạn.
Làm thế nào để kết hợp các hệ số?
Nhân các hệ số lại với nhau. Nhiệt độ môi trường, đi chung nhóm, điện trở suất đất, độ sâu chôn và hệ số sóng hài đều áp dụng cho định mức. Chia dòng thiết kế cho tích đó để có dòng bảng mà cáp cần.
Vì sao cáp Úc ở 30 °C có hệ số lớn hơn 1?
AS/NZS 3008.1.1 định mức cáp theo không khí 40 °C và đất 25 °C. Tuyến đi mát hơn cho phép cáp mang dòng lớn hơn. AS/NZS 3008.1.2 định mức cáp New Zealand theo không khí 30 °C và đất 15 °C.
Các cáp đi song song có được tính là mạch đi chung nhóm không?
Có. Mỗi bộ cáp của mạch song song được tính là một mạch trong nhóm. Ba mạch, mỗi mạch gồm hai bộ song song, sẽ tra hệ số cho sáu mạch.
Vì sao hệ số độ sâu khác nhau với cáp lớn hơn?
Với cáp chôn trực tiếp, bảng độ sâu phân nhóm hệ số theo tiết diện dây dẫn: đến 50 mm², trên 50 đến 300 mm², và trên 300 mm². Công cụ đọc nhóm của tiết diện bạn chọn.
Các ví dụ tính sẵn
- Cable tray fill for a plant room: a second tierLay ten multicore cables on a 300 mm perforated tray in one layer, see when it takes a second tier, and carry the grouping factor into the cable size.
- Downlights in an insulated ceilingRe-insulate a NZ ceiling with downlights in it. Check which may be covered, which only abutted, which must come out, and the clearances and roof space sign.
- Three circuits in a hot ceiling: correction factorThree 32 A circuits in conduit across a 40 °C and a 50 °C ceiling space, worked with the NZ 2017 tables and again with AS/NZS 3008.1.1:2025.
Nền
- Downlights and insulation: IC-4, CA90 and Non‑ICThe six recessed luminaire classes, what insulation may do around each, which a NZ or AU home may have, the default clearances, and the roof space warning sign.
- Cable tray fill: one layer, tiers and groupingHow cables lie on a tray or ladder for AS/NZS 3008.1, touching or spaced, when a run needs another tier, and why there is no fill percentage to work to.
- Correction factors in the 2017 and 2025 editionsWhat each AS/NZS 3008 correction factor does, how the factors multiply, and which values changed when AS/NZS 3008.1.1:2025 replaced the 2017 tables.
Các điều khoản và bảng mà công cụ này đọc
- AS/NZS 3000:2018 Cl 3.4Current-carrying capacity
- AS/NZS 3008.1.2:2017 Cl 3.5.9Third harmonic current in the neutral
- AS/NZS 3008.1.2:2017 Table 2Reduction factors for harmonic currents in 4- and 5‑core cables
- AS/NZS 3008.1.2:2017 Table 13Current ratings, multicore cable with three or four cores, thermoplastic 75 °C
- AS/NZS 3008.1.2:2017 Table 22, 25(1), 25(2)Grouping factors for bunched circuits, buried circuits and underground wiring enclosures
- AS/NZS 3008.1.2:2017 Table 23Grouping factors for single‑core circuits on trays, ladder supports, racks and cleats in air
- AS/NZS 3008.1.2:2017 Table 24Grouping factors for multicore cables on trays, ladder supports, racks and cleats in air
- AS/NZS 3008.1.2:2017 Table 27(1), 27(2)Rating factors for air and soil ambient temperature
Mọi điều khoản và bảng, kèm cách mỗi mục đã được kiểm chứng
Các bảng được kiểm tra lần cuối ngày 27 Sept 2026.
Công cụ liên quan
- Công cụ tính tiết diện cápFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Công cụ tính sụt ápCalculate voltage drop on a cable run and check the limit.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Độ lấp đầy máng cáp và thang cápTray or ladder width, tiers, kg/m and the grouping factor.AS/NZS 3008.1
Thông tin này có hữu ích không?
Có câu hỏi, hoặc giá trị có vẻ sai? Liên hệ chúng tôi.