Kiểm tra mạch hiện có
Kiểm tra một mạch đã lắp đặt: cáp, thiết bị, sụt áp và Zs.
Reads AS/NZS 3008.1.2:2017 (NZ), AS/NZS 3008.1.1:2017 and 2025 (AU) and AS/NZS 3000:2018. Tables checked 27 Sept 2026.
Thử một công việc 7
Mỗi công việc điền sẵn giá trị ví dụ. Hãy thay bằng giá trị của bạn.
- Check the breaker on a 4 mm² circuitWhether a 32 A breaker suits 4 mm² cable, and the largest breaker the cable allows.
- Check an existing three‑phase submainWhether 16 mm² on a 63 A breaker over 80 m passes the cable, drop and Zs checks.
- Check a 20 A breaker on 2.5 mm²Whether a 20 A breaker suits a 2.5 mm² circuit.
- Check a 32 A breaker on 6 mm²Whether a 32 A breaker suits a 6 mm² circuit.
- Check a 16 A breaker on 1.5 mm²Whether a 16 A breaker suits a 1.5 mm² circuit.
- Check a 63 A breaker on 16 mm²Whether a 63 A breaker suits 16 mm² mains.
- Check a 10 A breaker on 1 mm²Whether a 10 A breaker suits a 1 mm² lighting circuit.
Dữ liệu nhập
Ví dụ tính toán với dữ liệu nhập mặc định.
- Các pha
- Một pha
- Điện áp
- 230 V
- Dòng thiết kế
- 20 A
- Hệ số công suất
- 0.9
- Tiêu chuẩn
- NZ · AS/NZS 3008.1.2
- Chiều dài đoạn dây
- 30 m
- Phương pháp lắp đặt
- Đặt kín trong không khí
- Nhiệt độ môi trường
- 30 °C
- Các mạch đi chung nhóm
- 1
- Tiết diện cáp đã lắp đặt
- 2.5 mm²
- Vật liệu
- Đồng
- Cách điện
- PVC 75 °C
- Lõi dây
- Nhiều lõi
- Cáp song song
- 1
- Giới hạn sụt áp
- 5 %
- Tổng trở ngoài Ze
- 0.35 Ω
- Dòng ngắn mạch dự kiến
- 0 kA
- Đường đặc tính của thiết bị
- Đường đặc tính C
- Định mức thiết bị
- 20 A
Mạch dùng 2.5 mm²
Đạt
- Định mức đã hiệu chỉnh Iz
- 23A
- Sụt áp
- 4.25%
- Tổng trở mạch vòng sự cố chạm đất
- 0.89Ω
- Zs tối đa của thiết bị
- 1.53Ω
- Tiết diện nhỏ nhất đạt
- 2.5mm²
- Thiết bị đặc tính C lớn nhất mà cáp cho phép
- 20A
- Hệ số hiệu chỉnh tổng hợp
- ×1.00
Kết quả này là công cụ hỗ trợ thiết kế. Hãy kiểm tra theo tiêu chuẩn hiện hành.
Các bước tính toán
- Tiết diện dây dẫn đã lắp2.5mm²
AS/NZS 3008.1.2:2017 Table 13 p.62–64
- Định mức theo bảng của 2.5 mm²23A
AS/NZS 3008.1.2:2017 Table 13 p.62–64
- Hệ số hiệu chỉnh nhiệt độ môi trường×1.00
AS/NZS 3008.1.2:2017 Tables 27(1), 27(2) p.88
- Hệ số hiệu chỉnh nhóm×1.00
One circuit, no grouping factor
- Hệ số hiệu chỉnh tổng hợp×1.00
- Định mức đã hiệu chỉnh Iz23A
AS/NZS 3000:2018 Cl 3.4
- Sụt áp9.78V
- Phần trăm sụt áp4.25%
AS/NZS 3000:2018 Cl 3.6.2
- Định mức thiết bị In20A
AS/NZS 3000:2018 Cl 2.5.3.1
- Tiết diện dây dẫn nối đất2.5mm²
AS/NZS 3000:2018 Table 5.1
- Trở kháng vòng lặp sự cố chạm đất ở 230 V pha với đất0.89Ω
AS/NZS 3000:2018 Table 8.1
- Zs lớn nhất cho thiết bị1.53Ω
AS/NZS 3000:2018 Table 8.1
- Tiết diện nhỏ nhất đạt yêu cầu2.5mm²
AS/NZS 3000:2018 Cl 3.4
Giới thiệu công cụ tính này
How this is calculated
The tool takes a circuit that is already installed and runs the five checks of the cable size calculator at its size. It uses the same code, so the two tools agree on every size.
- Current capacity. It reads the tabulated rating of the installed size for your material, insulation, core count and installation method. It multiplies the rating by the correction factors for the route to get Iz. Iz must be at or above the design current Ib.
- Voltage drop. It works out the drop for the run length, the power factor and the conductor. It compares the drop with the limit you set.
- Breaker rating. The breaker rating In must sit between the two: Ib at or below In, and In at or below Iz. The tool gives both margins.
- Loop impedance. It adds the active and earth conductor resistance to the external impedance Ze. The total Zs must stay under the maximum for the breaker curve and rating.
- Fault withstand. If you enter a prospective fault current, the conductor must withstand it for the clearing time.
- Result. The circuit passes when every check it runs passes. The tool gives the smallest standard size that passes with the same breaker, and the largest breaker of the same curve that the cable allows.
| Step | Table or clause | What it decides |
|---|---|---|
| Current rating | Table 13 or 14 for multicore, Tables 4, 5, 7 and 8 for single core | The tabulated rating of the installed size |
| Correction factors | Tables 22 to 29 and Table 2 | The factors for the route |
| Voltage drop | Tables 30, 34 and 35, AS/NZS 3000 Cl 3.6.2 | The drop over the run and its limit |
| Breaker rating | AS/NZS 3000 Cl 2.5.3.1 | That In sits between Ib and Iz |
| Earth and Zs | AS/NZS 3000 Table 5.1 and Table 8.1 | The earth conductor size and the maximum loop impedance |
| Fault withstand | Table 52 and Cl 5.3 | The fault current the conductor survives |
Tables without a standard named are in the part of AS/NZS 3008.1 you pick. AS/NZS 3008.1.1:2025 numbers them by section.
Common circuits, worked with the tool
Each line states its circuit. Every line uses multicore copper cable with PVC insulation and one circuit on the route, enclosed in air at 30 °C. Every breaker is a C curve and Ze is 0.35 Ω, on the New Zealand tables.
- Socket‑outlets, 2.5 mm² on a 20 A breaker over 30 m. It passes every check. The drop is 4.25 %, close to the 5 % limit.
- The same cable on a 32 A breaker with a 25 A load. It fails the current, drop and breaker checks. 6 mm² is the smallest size that passes.
- 4 mm² on a 32 A breaker over 20 m. It fails the breaker check, because Iz is 29 A. The largest breaker the cable allows is 25 A, and 6 mm² is the smallest size that passes on 32 A.
- Three‑phase submain, 16 mm² on a 63 A breaker over 80 m. It fails on loop impedance: Zs is 0.76 Ω against a maximum of 0.49 Ω. With this breaker, 70 mm² is the smallest size that passes.
New Zealand and Australia
The Standard select picks the part of AS/NZS 3008.1 the tool reads. For Australia, the Edition select picks 2025 or the superseded 2017 edition. The breaker and Zs rules come from AS/NZS 3000, which is the same in both countries.
What the tool does not check
The tool works from the inputs, not from a test. Measure Ze and Zs on site and compare the reading with the maximum it gives. It does not check RCD rules or discrimination between breakers.
To size a new circuit, use the cable size calculator. To read the factors for a route on their own, use the correction factors calculator.
Câu hỏi
Kết quả chỉ là công cụ hỗ trợ thiết kế. Đối chiếu với tiêu chuẩn hiện hành.
Aptomat cỡ nào có thể đặt trên cáp 4 mm²?
Tùy thuộc vào tuyến. Khi đi kín trong không khí 30 °C và đi riêng, cáp đồng 4 mm² có khả năng mang dòng 29 A tại New Zealand, nên aptomat 25 A là cỡ tiêu chuẩn lớn nhất. Đi chung nhóm, nhiệt độ cao hoặc vật liệu cách nhiệt làm giảm giá trị này. Nhập tuyến của bạn để xem aptomat lớn nhất mà cáp cho phép.
Ib ≤ In ≤ Iz nghĩa là gì?
Ib là dòng thiết kế của phụ tải, In là định mức aptomat và Iz là khả năng mang dòng của cáp sau hiệu chỉnh. Aptomat phải mang được phụ tải và cáp phải mang được định mức aptomat. AS/NZS 3000 Clause 2.5.3.1 quy định quy tắc này.
Vì sao mạch dài không đạt về tổng trở mạch vòng?
Cáp dài hoặc nhỏ có tổng trở mạch vòng sự cố chạm đất cao. Khi đó dòng sự cố quá thấp để aptomat cắt kịp thời ở cài đặt từ. Hãy dùng cáp lớn hơn, định mức aptomat thấp hơn, đường cong B, hoặc kiểm tra quy tắc RCD cho mạch.
Công cụ có đo mạch của tôi không?
Không. Công cụ tính từ tiết diện cáp, tuyến cáp và tổng trở ngoài Ze bạn nhập. Hãy đo Ze và Zs tại hiện trường và so sánh kết quả đo với Zs tối đa mà công cụ cho.
Công cụ gợi ý cỡ nào khi mạch không đạt?
Tiết diện tiêu chuẩn nhỏ nhất đạt mọi kiểm tra với cùng aptomat, tuyến đi và phụ tải. Đây là kết quả mà công cụ tính tiết diện cáp đưa ra cho cùng mạch.
Các ví dụ tính sẵn
- A circuit chart for a house board with solarThe circuit chart and labels for a six-circuit house board with a solar inverter: ways, devices, RCDs, MAIN SWITCH, MAIN SWITCH SOLAR and a shared neutral.
- What size breaker for 4 mm² cable4 mm² copper enclosed in air takes a 25 A breaker, and 32 A fails at an Iz of 29 A. Grouping, a hot ceiling, insulation and a long run lower it.
Nền
Các điều khoản và bảng mà công cụ này đọc
- AS/NZS 3000:2018 Cl 2.5.3.1Protective device coordination
- AS/NZS 3000:2018 Cl 3.4Current-carrying capacity
- AS/NZS 3000:2018 Cl 3.6.2Voltage drop limit
- AS/NZS 3000:2018 Table 5.1Minimum earthing conductor size by active conductor size
- AS/NZS 3000:2018 Table 8.1Maximum earth fault loop impedance multipliers by MCB curve
- AS/NZS 3008.1.2:2017 Table 4Current ratings, single‑core cable, two cables per circuit, thermoplastic 75 °C
- AS/NZS 3008.1.2:2017 Table 5Current ratings, single‑core cable, two cables per circuit, cross-linked 90 °C
- AS/NZS 3008.1.2:2017 Table 7Current ratings, single‑core cable, three cables per circuit, thermoplastic 75 °C
Mọi điều khoản và bảng, kèm cách mỗi mục đã được kiểm chứng
Các bảng được kiểm tra lần cuối ngày 27 Sept 2026.
Công cụ liên quan
- Công cụ tính tiết diện cápFind the smallest cable size that passes each check.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Công cụ tính tổng trở mạch vòng sự cố chạm đấtCheck earth fault loop impedance against the maximum Zs.AS/NZS 3008.1.2AS/NZS 3008.1.1AS/NZS 3000
- Bộ chọn cáp đơn giảnRead the Appendix C device rating and voltage drop tables.AS/NZS 3000