PV स्ट्रिंग कैलकुलेटर
PV के लिए प्रति स्ट्रिंग मॉड्यूल, स्ट्रिंग करंट और आइसोलेटर।
Reads AS/NZS 5033:2021 and AS/NZS 4777.2:2020. Tables checked 2 Oct 2026.
कोई प्रोजेक्ट आज़माएँ 8
हर जॉब में उदाहरण मान भरे होते हैं। उन्हें अपने मानों से बदलें।
- Size solar strings for a 600 V inverterThe modules per string for 49.5 V modules on a 600 V inverter at −5 °C.
- Check string fuses on three parallel stringsWhether three parallel strings of 13.9 A modules call for string fuses, and their rating.
- Size strings for a 1000 V inverterThe modules per string for a commercial inverter.
- Size strings for a cold inland siteThe modules per string at a record low of −8 °C, on a 600 V inverter.
- Check a string on a hot roofWhether the hot voltage stays above the tracker's minimum.
- Check two strings need no fuseWhether two strings in parallel need string fuses.
- Check the array current at the inverterThe array's short-circuit current against the inverter input.
- Size strings for a house trackerThe modules per string for a 450 V window.
इनपुट
डिफ़ॉल्ट इनपुट के साथ एक कार्य-उदाहरण।
- मॉड्यूल Voc
- 49.5 V
- मॉड्यूल Vmp
- 41.5 V
- मॉड्यूल Isc
- 13.9 A
- Voc तापमान गुणांक
- −0.27 %/K
- Vmp तापमान गुणांक
- −0.35 %/K
- मॉड्यूल का अधिकतम श्रेणी फ़्यूज़
- 25 A
- ठंडे वोल्टेज का सुधार
- निर्माता का गुणांक, Cl 4.2.1.2(a)
- रिकॉर्ड निम्नतम तापमान
- −5 °C
- रिकॉर्ड उच्चतम तापमान
- 35 °C
- परिवेश से ऊपर सेल की बढ़ोतरी
- 35 K
- इंस्टॉलेशन
- घरेलू, 1000 V सीमा
- स्ट्रिंग में मॉड्यूल
- 10
- समानांतर में स्ट्रिंग
- 2
- KI, द्विपक्षीय गुणांक
- 1
- इन्वर्टर से बैकफ़ीड करंट
- 0 A
- स्ट्रिंग फ़्यूज़ रेटिंग
- 0 A
- इन्वर्टर अधिकतम d.c. वोल्टेज
- 600 V
- MPPT न्यूनतम वोल्टेज
- 150 V
- MPPT अधिकतम वोल्टेज
- 550 V
- इन्वर्टर Isc PV
- 0 A
स्ट्रिंग में मॉड्यूल
5 से 11
- स्ट्रिंग अधिकतम वोल्टेज
- 535.1V
- सबसे गर्म सेल पर स्ट्रिंग Vmp
- 349.6V
- अधिकतम स्ट्रिंग करंट
- 17.38A
- इन्वर्टर तक ऐरे करंट
- 34.75A
- d.c. आइसोलेटर, कम से कम
- 535.1 V पर 34.75 A
- स्ट्रिंग फ़्यूज़
- Not called for
यह परिणाम डिज़ाइन में सहायता के लिए है। इसे मौजूदा मानक से सत्यापित करें।
गणना के चरण
- Voc सुधार, 1 + गुणांक × (Tmin − 25 °C)×1.08
AS/NZS 5033:2021 Cl 4.2.1.2
- सबसे ठंडे सेल पर मॉड्यूल अधिकतम वोल्टेज53.51V
AS/NZS 5033:2021 Cl 4.2.1.2
- घरेलू इंस्टॉलेशन के लिए सीमा1,000V
AS/NZS 5033:2021 Cl 3.1
- प्रति स्ट्रिंग अधिकतम मॉड्यूल11
AS/NZS 5033:2021 Cl 4.2.1.3.1
- सबसे गर्म सेल, रिकॉर्ड उच्च तापमान और वृद्धि70°C
- सबसे गर्म सेल पर मॉड्यूल Vmp34.96V
- MPPT न्यूनतम के लिए प्रति स्ट्रिंग सबसे कम मॉड्यूल5
- स्ट्रिंग अधिकतम वोल्टेज535.1V
AS/NZS 5033:2021 Cl 4.2.1.3.1
- सबसे गर्म सेल पर स्ट्रिंग Vmp349.6V
- सबसे ठंडे सेल पर स्ट्रिंग Vmp458.6V
- अधिकतम स्ट्रिंग धारा, 1.25 × KI × Isc17.38A
AS/NZS 5033:2021 Cl 3.3.3.1
- अन्य स्ट्रिंग से फ़ॉल्ट करंट, (SA − 1) × ISTRING MAX17.38A
AS/NZS 5033:2021 Cl 3.3.3.2
- स्ट्रिंग फ़्यूज़ विंडो, 1.2 × ISTRING MAX से ऊपर और मॉड्यूल रेटिंग तक20.85 से 25 तकA
AS/NZS 5033:2021 Table 3.1
- स्ट्रिंग केबल धारा17.38A
AS/NZS 5033:2021 Table 4.2
- इन्वर्टर तक ऐरे केबल करंट34.75A
AS/NZS 5033:2021 Table 4.2
- d.c. आइसोलेटर धारा रेटिंग, कम से कम34.75A
AS/NZS 5033:2021 Table 4.3
- d.c. आइसोलेटर वोल्टेज रेटिंग, कम से कम535.1V
AS/NZS 5033:2021 Table 4.3
- सबसे छोटा कंडक्टर4mm²
AS/NZS 5033:2021 Cl 4.4.2.3
- मॉड्यूल के पास केबल तापमान, रिकॉर्ड उच्च + 40 K75°C
AS/NZS 5033:2021 Cl 4.4.2.2
इस कैलकुलेटर के बारे में
How this is calculated
The tool sizes a PV string. It finds how many modules fit in a string, the string current, the fuses and the d.c. isolator. It reads AS/NZS 5033:2021. It reads the inverter limits from the plate you enter.
- Cold voltage. The tool corrects the module Voc for the coldest cell (Cl 4.2.1.2). The factor is 1 + coefficient × (Tmin − 25 °C). Tmin is the record low.
- Most modules. It divides the voltage limit by the corrected Voc. The limit is the lower of the inverter maximum and the domestic limit in Cl 3.1 (Cl 4.2.1.3.1).
- Fewest modules. It finds the hot cell as the record high plus the cell rise you enter. It then finds the fewest modules that keep Vmp above the MPPT minimum.
- String current. It works 1.25 × KI × Isc (Cl 3.3.3.1). It adds the fault current from the other strings (Cl 3.3.3.2).
- Fuses. A fuse window sits above 1.2 times the string current and at most the module rating (Table 3.1).
- Cable and isolator. It gives the cable currents (Table 4.2), the isolator ratings (Table 4.3) and the smallest conductor (Cl 4.4.2.3).
| Step | Table or clause | What it decides |
|---|---|---|
| Cold voltage | Cl 4.2.1.2 | The module voltage at the coldest cell |
| String length | Cl 4.2.1.3.1 | The most modules in a string |
| String current | Cl 3.3.3.1 and Cl 3.3.3.2 | The current for cable and fuse |
| Fuse window | Table 3.1 | The fuse range |
| Isolator | Table 4.3 | The current and voltage ratings |
Worked example
- 10 modules of 49.5 V Voc, 2 strings, 600 V inverter. The tool gives 5 to 11 modules per string. The string maximum voltage is 535.1 V. The string current is 17.38 A and the array current is 34.75 A. No string fuses are called for.
Limits
- The tool derives the AS/NZS 5033 figures from the text until the Standard is checked. It says so in a warning.
- AS/NZS 5033 sets no cell rise. The tool uses the rise you enter.
- The inverter limits are the ones on its plate. Read them from the data sheet.
- The tool does not size the cable. Use the DC cable size calculator at these currents and at the hot cable temperature.
- Above 120 V, hold the voltage drop from the furthest module to the inverter to 5 % of Vmp.
See also: PV string voltage and temperature, Solar string sizing for a 600 V inverter and PV and inverter basics.
सवाल
परिणाम एक डिज़ाइन सहायता है। मौजूदा मानक से सत्यापित करें।
टूल प्रति स्ट्रिंग सबसे अधिक मॉड्यूल कैसे खोजता है?
यह मॉड्यूल Voc को रिकॉर्ड न्यूनतम तापमान पर सुधारता है, निर्माता के गुणांक से या AS/NZS 5033 Table 4.1 से। यह इन्वर्टर अधिकतम और 1000 V या 1500 V सीमा में से कम को उस वोल्टेज से भाग देता है, और नीचे की ओर राउंड करता है।
टूल प्रति स्ट्रिंग सबसे कम मॉड्यूल कैसे खोजता है?
यह सबसे गर्म सेल पर मॉड्यूल Vmp निकालता है: रिकॉर्ड उच्चतम तापमान और आपके दर्ज सेल राइज़ का योग। यह MPPT न्यूनतम को उस वोल्टेज से भाग देता है और ऊपर की ओर राउंड करता है। AS/NZS 5033 सेल राइज़ तय नहीं करता, इसलिए 35 K डिफ़ॉल्ट AmpSize की मान्यता है।
स्ट्रिंग को फ़्यूज़ कब लगता है?
जहाँ स्ट्रिंग समानांतर चलती हैं, बाकी स्ट्रिंगें एक स्ट्रिंग में फ़ॉल्ट फ़ीड कर सकती हैं। टूल उस करंट को बैकफ़ीड में जोड़ता है और उसकी तुलना मॉड्यूल के अधिकतम सीरीज़ फ़्यूज़ से करता है। जहाँ यह ज़्यादा हो, फ़्यूज़ अधिकतम स्ट्रिंग करंट के 1.2 गुना से ऊपर होता है और मॉड्यूल रेटिंग के बराबर या उससे कम।
क्या AS/NZS 5033 के आंकड़े सत्यापित हैं?
हाँ। Table 4.1 और वोल्टेज, करंट और केबल सीमाएँ AS/NZS 5033:2021 के छपे पन्नों से मिलाकर पढ़ी गईं। किसी भी आंकड़े पर भरोसा करने से पहले उसे मौजूदा मानक से जाँच लें।
हल किए गए उदाहरण
- DC isolator rating for a 10 kW solar arrayRate the d.c. isolator and size the frame earth for a four-string domestic array. Check one data sheet that passes and one that fails per pole.
- Solar string sizing for a 600 V inverterHow many 49.5 V modules fit a string on a 600 V inverter at −5 °C? Work cold Voc, hot Vmp, the string current, fuses and the d.c. isolator by AS/NZS 5033.
बैकग्राउंड
- PV array isolators and earthingHow parallel strings feed a fault, what Ithe, Ie and make and break mean for a d.c. isolator, and how AS/NZS 5033 earths and alarms a PV array.
- PV string voltage and temperatureWhy a PV string's voltage rises in the cold and falls in the heat, how AS/NZS 5033 limits it, and how the string current, fuses and isolator follow.
वे Clauses और Tables जो यह टूल पढ़ता है
- AS/NZS 5033:2021 Cl 3.1Maximum voltage of PV d.c. circuits
- AS/NZS 5033:2021 Cl 3.3.3.1Maximum string current
- AS/NZS 5033:2021 Cl 3.3.3.2Fault current from parallel strings
- AS/NZS 5033:2021 Cl 3.3.4.1When strings take overcurrent protection
- AS/NZS 5033:2021 Cl 4.2.1.2PV module maximum voltage
- AS/NZS 5033:2021 Cl 4.2.1.3.1String voltage limit
- AS/NZS 5033:2021 Cl 4.4.2.2PV cable temperature
- AS/NZS 5033:2021 Cl 4.4.2.3Smallest PV conductor
हर Clause और Table, और उनकी सत्यापन की विधि
Tables आख़िरी बार 2 Oct 2026 को जाँची गईं।
संबंधित टूल
क्या यह उपयोगी था?
कोई सवाल, या कोई मान गलत लगता है? हमसे संपर्क करें।