4-20 mA लूप के लिए लूप पावर बजट
ट्रांसमीटर से 4–20 mA लूप को कितना वोल्टेज बचता है, जाँचें।
Reads AS/NZS 3008.1.2:2017 (NZ) and AS/NZS 3008.1.1:2017 and 2025 (AU). Tables checked 27 Sept 2026.
कोई प्रोजेक्ट आज़माएँ 6
हर जॉब में उदाहरण मान भरे होते हैं। उन्हें अपने मानों से बदलें।
- Check a 4–20 mA loop's power budgetThe supply, the series resistance and the cable give the voltage left at the transmitter.
- Check a loop with a HART resistorThe voltage left with a 250 Ω HART resistor in the loop.
- Check a loop through a barrierThe voltage left with 300 Ω of barrier in series.
- Check a 2 km loopThe voltage left on 1 mm² cable over 2000 m.
- Check a loop on a 12 V supplyWhether a 12 V supply drives the loop.
- Check a loop at fault currentThe voltage left at 22 mA.
इनपुट
डिफ़ॉल्ट इनपुट के साथ एक कार्य-उदाहरण।
- लूप आपूर्ति वोल्टेज
- 24 V
- ट्रांसमीटर न्यूनतम वोल्टेज
- 12 V
- लूप धारा
- 20 mA
- इनपुट रेज़िस्टेंस
- 250 Ω
- HART रेज़िस्टर
- 0 Ω
- अन्य श्रेणी प्रतिरोध
- 0 Ω
- केबल लंबाई, एक तरफ़
- 500 m
- कंडक्टर प्रतिरोध
- कंडक्टर के आकार से
- कंडक्टर का आकार
- 1 mm²
- मानक
- NZ · AS/NZS 3008.1.2
वोल्टेज मार्जिन
6.48V
- ट्रांसमीटर पर वोल्टेज
- 18.48V
- लूप प्रतिरोध
- 275.8Ω
- केबल प्रतिरोध
- 25.8Ω
- अधिकतम लूप प्रतिरोध
- 600Ω
- अधिकतम केबल लंबाई
- 6,782m
यह परिणाम डिज़ाइन में सहायता के लिए है। इसे मौजूदा मानक से सत्यापित करें।
गणना के चरण
- कंडक्टर प्रतिरोध25.8Ω/km
AS/NZS 3008.1.2:2017 Tables 34 to 35
- केबल प्रतिरोध, दोनों कंडक्टर25.8Ω
- श्रृंखला प्रतिरोध250Ω
- लूप प्रतिरोध275.8Ω
- लूप धारा20mA
- लूप में वोल्टेज ड्रॉप5.52V
- ट्रांसमीटर पर वोल्टेज18.48V
- वोल्टेज मार्जिनपरिणाम6.48V
- अधिकतम लूप प्रतिरोध600Ω
- अधिकतम केबल लंबाई6,782m
इस कैलकुलेटर के बारे में
How the tool checks the loop
A 4–20 mA loop is one series circuit. The loop supply drives the current through the transmitter, the cable and the receiver input. The transmitter needs a minimum voltage at its terminals to work.
- Conductor resistance. The tool reads the resistance of a copper conductor for the size you pick. It can also take the value from the cable data.
- Cable resistance. The current goes out on one conductor and comes back on the other. So the tool doubles the one-way length.
- Loop resistance. It adds the cable resistance to the input resistance, the HART resistor and any other series parts.
- Voltage at the transmitter. It multiplies the loop current by the loop resistance and subtracts that drop from the supply voltage.
- Voltage margin. It subtracts the transmitter minimum voltage. A margin of 0 V or more passes.
- Maximum length. It gives the longest one-way run that keeps the margin at 0 V or more.
Worked loops
Each line opens the tool with its values. Every line uses a 24 V supply, a 12 V transmitter minimum voltage and a 250 Ω receiver input.
- Pressure transmitter, 500 m of 1 mm² at 20 mA. The loop passes with a margin of 6.48 V.
- HART loop, 400 m of 1 mm² at 22 mA. A 250 Ω HART resistor sits in the loop. The loop passes with a margin of 0.55 V.
- HART loop, 500 m of a 36 Ω/km pair at 22 mA. The resistance comes from the cable data. The loop passes with a margin of 0.21 V.
- The same HART loop at 700 m. The loop fails with a margin of −0.11 V. Shorten the run, use a larger conductor or raise the supply.
New Zealand and Australia
The Standard select picks the part of AS/NZS 3008.1 the tool reads for the conductor resistance. Part 1.2 is the New Zealand part, 2017 edition. Part 1.1 is the Australian part. For Australia, the Edition select picks 2025 or the superseded 2017 edition. All three print the same resistance values. The impedance table entry says how AmpSize checked them.
Related checks
- The comms cable selector checks the cable construction and the run length for the interface.
- The DC cable size calculator sizes the 24 V d.c. supply cable to the transmitter panel.
- The segregation checker checks the spacing between the loop cable and power cables.
सवाल
परिणाम एक डिज़ाइन सहायता है। मौजूदा मानक से सत्यापित करें।
4–20 mA लूप कितनी दूर चल सकता है, यह क्या तय करता है?
सप्लाई वोल्टेज, ट्रांसमीटर के न्यूनतम वोल्टेज को घटाकर, बजट है। हर सीरीज़ रेज़िस्टेंस से गुज़रता लूप करंट उसे खर्च करता है। केबल दोनों कंडक्टरों का रेज़िस्टेंस जोड़ता है, इसलिए लंबा रन या पतला कंडक्टर ज़्यादा खर्च करता है।
20 mA से ज़्यादा पर जाँच क्यों करें?
ट्रांसमीटर 20 mA से ज़्यादा ड्राइव कर सकता है, जैसे 22 mA के आसपास एक अपस्केल अलार्म। लूप में ड्रॉप करंट के साथ बढ़ता है। उस सबसे ऊँचे करंट पर जाँच करें जो ट्रांसमीटर ड्राइव करता है।
ट्रांसमीटर का न्यूनतम वोल्टेज कहाँ मिलेगा?
ट्रांसमीटर डेटा शीट इसे देती है, अक्सर लिफ़्ट-ऑफ़ वोल्टेज या न्यूनतम टर्मिनल वोल्टेज के रूप में। कुछ डेटा शीट इसके बजाय लोड लाइन देती हैं। सबसे ज़्यादा लूप करंट पर वोल्टेज पढ़ें।
बैकग्राउंड
वे Clauses और Tables जो यह टूल पढ़ता है
- AS/NZS 3008.1.2:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2017 Table 30, 34, 35Reactance at 50 Hz and a.c. resistance at 50 Hz
- AS/NZS 3008.1.1:2025 Table 4.1(A), 4.1(B), 4.5(A), 4.5(B)Reactance at 50 Hz and a.c. resistance at 50 Hz