IP रेटिंग चार्ट और डिकोडर
IP कोड को डिकोड करें और किसी स्थान के लिए सबसे कम IP कोड खोजें।
Reads AS 60529:2004 and AS/NZS 3000:2018. Tables checked 1 Oct 2026.
कोई प्रोजेक्ट आज़माएँ 4
हर जॉब में उदाहरण मान भरे होते हैं। उन्हें अपने मानों से बदलें।
- Read what IP44 meansEach digit of an IP code, by AS 60529.
- Check an outdoor power point codeAn IP44 socket‑outlet outside the eave area against IP33.
- Choose a code for a hosed areaThe least code for high-pressure hosing, and an IP66 light checked.
- Check a light for a sauna roomAn IPX4 light against the IPX4B or IP24 a sauna needs.
इनपुट
डिफ़ॉल्ट इनपुट के साथ एक कार्य-उदाहरण।
- प्रश्न
- इस IP कोड का क्या अर्थ है
- IP कोड
- IP65
कोड का अर्थ
Dust-tight · Water jets
- ठोस वस्तुएँ
- Dust-tight
- खतरनाक भागों तक पहुँच
- A wire
- पानी
- Water jets
यह परिणाम डिज़ाइन में सहायता के लिए है। इसे मौजूदा मानक से सत्यापित करें।
गणना के चरण
- कोडIP65
AS 60529-2004 Cl 4.1
- पहला अंक 6Dust-tight; a wire
AS 60529-2004 Tables 1 and 2
- दूसरा अंक 5Water jets
AS 60529-2004 Table 3
इस कैलकुलेटर के बारे में
How this is calculated
The tool answers two questions: what an IP code means, and which code a location needs.
To decode, it reads the code the way the IP code standard lays it out. After the letters IP come two characteristic numerals. The first, 0 to 6, covers solid objects and access to hazardous parts: the size of object kept out, and the part of a person kept off, from the back of a hand to a wire. The second, 0 to 8, covers water, from dripping to continuous immersion. An X stands for a numeral that is not stated. An optional additional letter, A to D, marks access protection better than the first numeral gives. Optional supplementary letters, H, M, S and W, add information for a product standard. A dual code such as IPX5/IPX7 meets both of its parts. Up to 6, a second numeral also meets every lower one, but a 7 or 8 alone is for immersion and does not meet water jets.
To select, the tool reads the least code the wiring rules name for the location, outside the zones around baths, showers, pools and spas. It says whether the clause is a requirement, a NOTE or an informative recommendation. With a device's code, it compares element by element: each numeral at or above the one required, and an access letter met by the letter or by the first numeral.
| Step | Table or clause | What it decides |
|---|---|---|
| Reading the code | AS 60529 Cl 4.1 | The numerals and letters, and X |
| Objects and access | AS 60529 Tables 1 and 2 | What the first numeral keeps out |
| Water | AS 60529 Table 3 and Cl 6 | What the second numeral resists, and dual codes |
| Access letter | AS 60529 Table 4 | What the additional letter keeps off |
| Enclosures | Cl 1.5.4.4 | The least code around live parts |
| Outdoor accessories | Cl 4.1.3 | The code outside the eave area |
| Switchboards | Cl 2.10.2.5 | Hosing, sprinklers and exits |
| Saunas and hosed areas | Cl 6.5.4.1 and Cl 6.7.4.1 | The code in the room or zone |
| Outdoor EV point | App P | The recommended code |
Worked examples
- IP65. Dust-tight, with no access even by a wire, and protected against water jets from any direction.
- IPX4B. No object numeral is stated. The letter B keeps a finger off, so access is by a finger at worst, and the code resists splashing water from any direction.
- An IP44 power point outside the eave. IP44 meets IP33, the code Cl 4.1.3 sets outside the area an eave protects.
- An IP67 light in a dairy hosed at high pressure. IP67 is below IPX6: a 7 alone is for immersion, not jets.
- A sauna light marked IPX4. IPX4 is below IP24 or IPX4B: the sauna also needs the finger kept off.
Limits
The tool reads AS 60529-2004, which stops the second numeral at 8; a 9 comes from a later IEC edition. It does not test anything: a code is what the maker has proven for the enclosure as tested. Drilling a drain hole, or a gland that does not seal, loses the code. For a bathroom, laundry, pool or spa, use the wet area zones tool: the code depends on the zone.
See also: IP ratings explained: each digit and letter, IP ratings for an outdoor point and a hosed shed and Wet Area Zones.
सवाल
परिणाम एक डिज़ाइन सहायता है। मौजूदा मानक से सत्यापित करें।
IP65 का क्या मतलब है?
पहला अंक, 6, का मतलब है डस्ट-टाइट, खतरनाक हिस्सों तक पहुँच नहीं, तार से भी नहीं। दूसरा, 5, का मतलब है किसी भी दिशा से पानी की धार से सुरक्षित। AS 60529 दोनों को परिभाषित करता है।
क्या IP67, IP65 से बेहतर है?
वॉटर जेट के लिए नहीं। अकेला 7 या 8 इमर्शन के लिए है, और AS 60529 इसे वॉटर जेट के खिलाफ़ प्रोटेक्शन नहीं गिनता। जो उत्पाद दोनों के लिए है, उसका दोहरा कोड होता है, जैसे IP65/IP67।
आउटडोर पावर पॉइंट को किस IP रेटिंग की ज़रूरत है?
AS/NZS 3000 Cl 4.1.3 के अनुसार, जहाँ यह उस एरिया के बाहर हो जिसे छज्जा या वरांडा सुरक्षित करता है, वहाँ IP33। उस एरिया के भीतर, सॉफ़िट के नीचे और दीवार तक 30 डिग्री रेखा के भीतर, एक्सेसरी को IP मार्किंग की ज़रूरत नहीं होती।
X और अक्षरों का क्या मतलब है?
X एक ऐसे अंक के लिए है जो बताया नहीं गया है। A से D तक का अतिरिक्त अक्षर पहले अंक से बेहतर एक्सेस प्रोटेक्शन को चिह्नित करता है। H, M, S या W का सप्लीमेंटरी अक्षर प्रोडक्ट मानक के लिए जानकारी जोड़ता है।
बाथरूम में मुझे किस IP रेटिंग की ज़रूरत है?
यह बाथ, शावर या बेसिन के आसपास के ज़ोन पर निर्भर करता है। वेट एरिया ज़ोन टूल इस्तेमाल करें: यह दूरी से ज़ोन खोजता है और उस ज़ोन के लिए ज़रूरी कोड नियम बताता है।
हल किए गए उदाहरण
बैकग्राउंड
वे Clauses और Tables जो यह टूल पढ़ता है
- AS 60529-2004 Cl 4.1Arrangement of the IP code
- AS 60529-2004 Cl 6Second numeral: protection against water
- AS/NZS 3000:2018 IP codes by locationThe least IP code AS/NZS 3000 names for a location, outside the Section 6 zones
- AS 60529-2004 Cl 4 and Tables 1 to 4The IP code: characteristic numerals, additional and supplementary letters
हर Clause और Table, और उनकी सत्यापन की विधि
Tables आख़िरी बार 1 Oct 2026 को जाँची गईं।
संबंधित टूल
क्या यह उपयोगी था?
कोई सवाल, या कोई मान गलत लगता है? हमसे संपर्क करें।