Bỏ qua nội dung
AmpSize

Công cụ tính phụ tải cực đại

Ước tính phụ tải cực đại cho phụ tải dân dụng hoặc không dân dụng.

Reads AS/NZS 3000:2018 and Electricity (Safety) Regulations 2010. Tables checked 19 Sept 2026.

Dữ liệu nhập

Ví dụ tính toán với dữ liệu nhập mặc định.

Bảng nhu cầu
Table C1 · dân dụng
Lắp đặt
Dân dụng đơn lẻ hoặc một căn hộ
Các pha
Một pha
Điện áp pha
230 V
Nhóm tải
4 hàng

Phụ tải cực đại

50.43A

Mỗi pha
50.43A
A(i) · Lighting
5A
B(i) · Socket-outlets and permanently connected equipment up to 10 A
15A
C · Ranges, cooking appliances and laundry equipment
17.39A
F · Storage water heaters
13.04A

Kết quả này là công cụ hỗ trợ thiết kế. Hãy kiểm tra theo tiêu chuẩn hiện hành.

Các bước tính toán

  1. Bảng nhu cầuC1 · single domestic

    AS/NZS 3000:2018 Table C1

  2. A(i) · Lighting5A

    AS/NZS 3000:2018 Table C1

  3. B(i) · Socket‑outlets and permanently connected equipment up to 10 A15A

    AS/NZS 3000:2018 Table C1

  4. C · Ranges, cooking appliances and laundry equipment17.39A

    AS/NZS 3000:2018 Table C1

  5. F · Storage water heaters13.04A

    AS/NZS 3000:2018 Table C1

  6. Nhu cầu cực đại50.43A

    AS/NZS 3000:2018 Table C1

  7. Nhu cầu cực đại mỗi phaKết quả50.43A

    AS/NZS 3000:2018 Table C1

Giới thiệu công cụ tính này

How this is calculated

The tool works out the maximum demand of an installation from its loads. It follows the load group method of AS/NZS 3000 Appendix C.

  1. Table. Table C1 covers domestic installations: one house or living unit, or a block of living units. Table C2 covers other installations. For Table C2 you pick the occupancy.
  2. Load groups. You enter each load in its group, such as lighting points, socket‑outlet points or kW of cooking. The tool lists only the groups the table assesses for your choice.
  3. Group demand. Each group has its own rule for its load. The tool applies that rule and gives the group demand in amperes. It converts each kW load at the phase voltage you enter.
  4. Living units per phase. A block of living units can take more than one phase. The tool then divides the units by the number of phases and rounds up. It reads the column for that number of units per phase.
  5. Total. The maximum demand is the sum of the group demands.
  6. Per phase. On three phases, the tool divides the total by three. That assumes you spread the load evenly over the phases. Where you cannot, allocate the loads per phase and check the heaviest phase.
StepTable or clauseWhat it decides
Domestic loadsAS/NZS 3000 Table C1The rule for each load group in a house or a block of living units
Other loadsAS/NZS 3000 Table C2The rule for each load group, by occupancy
Living units per phaseTable C1 Note 2The column a block of living units reads on more than one phase
Total and per phaseTable C1 or Table C2The sum of the groups and the share on each phase

Phase voltage

Enter the phase voltage, line to neutral, such as 230 V. The tool converts every kW load at that voltage. The 400 V between lines would read every kW group 42 % low. On a three‑phase supply the tool refuses a line voltage and asks for the phase voltage.

Common installations, worked with the tool

Each line states its loads. Every line uses a phase voltage of 230 V.

  • House on one phase. It uses Table C1 for one house. The loads are 30 lighting points, 25 socket‑outlet points, 8 kW of cooking and a 3 kW storage water heater. The maximum demand is 50.43 A.
  • The same house on three phases. The maximum demand is 16.81 A per phase and 50.43 A over all phases.
  • Block of 12 living units on three phases. Table C1 for blocks of living units, with the same load rows. The tool reads 4 units per phase. The maximum demand is 75 A per phase and 225 A over all phases.
  • Office on three phases. It uses Table C2 for factories, shops and offices. The loads are 10 kW of lighting, 20 socket‑outlets and motors of 15 A, 10 A and 5 A. The maximum demand is 44.93 A per phase and 134.78 A over all phases.

New Zealand and Australia

AS/NZS 3000 Appendix C applies in both countries, so the tool has no country select.

Keep the result

Every input sits in the page address, so the link in your browser reproduces the calculation. The PDF button prints the result with its steps and table references. Saving a calculation to a project needs a free account.

See also: Commercial maximum demand with Table C2, Domestic maximum demand with Table C1 and Maximum demand and diversity.

Câu hỏi

Kết quả chỉ là công cụ hỗ trợ thiết kế. Đối chiếu với tiêu chuẩn hiện hành.

Công cụ tính phụ tải cực đại làm gì?

Công cụ áp dụng quy tắc phụ tải tính toán cho từng nhóm phụ tải bạn thêm vào. Nó liệt kê phụ tải tính toán bằng ampe cho từng nhóm, rồi báo tổng phụ tải tính toán và phụ tải tính toán theo từng pha. Mỗi dòng ghi bảng và cột đã tạo ra kết quả đó.

Công cụ tính phụ tải cực đại dùng những bảng AS/NZS 3000 nào?

Công cụ dùng AS/NZS 3000:2018 Table C1 cho một lắp đặt dân dụng hoặc một khối đơn vị ở. Công cụ dùng Table C2 cho các lắp đặt khác, với cột dân cư hoặc thương mại. Hãy chọn bảng và chế độ trước, vì chúng thay đổi quy tắc mà mỗi nhóm phụ tải áp dụng.

Điều gì quyết định quy tắc phụ tải tính toán cho từng nhóm phụ tải?

Bảng và chế độ quyết định quy tắc cho mọi nhóm. Điện áp nguồn cấp đổi các nhóm cho bằng kW sang ampe. Số pha chia tổng. Ở chế độ căn hộ, số căn hộ trên mỗi pha quyết định kết quả. Nhập tổng số căn hộ và số pha.

Các đơn vị ở trên ba pha được tính như thế nào?

Công cụ chia số căn hộ cho ba, như Table C1 Note b yêu cầu. Một số nhóm nhận danh sách từng thiết bị, không phải một số lượng. Một số nhóm tính theo đánh giá và không cộng thêm gì. Một ghi chú hiện phía trên các ngưỡng của regulation 59.

Tôi có thể chia sẻ hoặc lưu một phép tính phụ tải không?

Có. Bảng, chế độ, điện áp, số pha và mọi dòng phụ tải đều nằm trong địa chỉ trang. Sao chép liên kết để gửi cùng bản đánh giá nhu cầu này cho người khác. Lưu dưới tên dự án cần có tài khoản. Điều kiện New Zealand là mặc định.

Các ví dụ tính sẵn

Tất cả 8 hướng dẫn cho công cụ tính này

Nền

Các điều khoản và bảng mà công cụ này đọc

Mọi điều khoản và bảng, kèm cách mỗi mục đã được kiểm chứng

Các bảng được kiểm tra lần cuối ngày 19 Sept 2026.

Thông tin này có hữu ích không?

Có câu hỏi, hoặc giá trị có vẻ sai? Liên hệ chúng tôi.